6.4 REGULATIONS
Compressor
The compressor can be active only in START function when the room probe has no error.
If the presence of door is on (PI=I), the door must be closed to permit the starting of the compressor only
if P6=0. With P6=0 the compressor is active even if the door is open and with arrested fan. The compressor
starts according to the SET POINT on, corresponding to the selected cycle and according to the differential of
temperature set (Parameter P8).
The protection time for the compressor are:
• P9: minimum delay that must exist between the switching off and the next starting up of the compressor.
This parameter is used also like reset of the card.
• P10: minimum delay that must exist between 2 consecutive starting ups of the compressor.
Manual defrosting
The defrosting is carried out with open door, without the use of neither the heater nor the hot gas.
Parameters
Pressing contemporarily Up and Down to enter the parameter setting for at least 4 sec.
At this point on the display appears the number itself of the parameter (P0). Pressing the SET
key, it is pos-
sible to see the value of the parameter itself and modify it.
THE KEYS UP AND DOWN
, WHEN THE PARAMETER SETTING IS ON, ALLOW TO PASS TO THE NEXT/FORMER PARAMETER; WHEN THE
VALUE OF THE PARAMETER IS ON, THEY MODIFY IT.
Par.
Description
Min
Max
Def.
4R
Def.
3R
Unit
P0
When switching to conservation the buzzer sounds for secs. indicated
0
1
10
10
n°
P1 Door present 0=door absent; 1=door present
0
1
1
1
n°
P2 Fan during the process 0=together with the compressor 1=always on
0
1
1
1
n°
P3 Permit to enter the core probe function
0
1
1
1
n°
P4 Permit to enter the negative process
0
1
1
1
n°
P5 Permit to enter the defrosting
0
1
1
1
n°
P6 Stopping functions when the door is open 0=comfans; 1=fans
0
1
1
1
n°
P7 Configuration RL2 0=defrosting: I=fan+defrosting
0
1
1
1
n°
P8 Hysteresis of regulation
1
20
3
3
°C
P9 Protection of the compressor Off/On (also valid as reset)
0
99
2
2
min
P10 Protection of the compressor On/On
0
99
3
3
min
P11 Defrosting duration
0
99
10
10
min
P12 Dripping duration
0
99
3
3
min
P13 Core probe for the positive process
-50
99
3
3
°C
P14 Core probe for the negative process
-50
99
-18
-18
°C
P15 Room probe for the positive process
-50
99
-2
-2
°C
P16 Room probe for the negative process
-50
99
-35
-35
°C
P17 Room probe for the positive conservation process
-50
99
0
0
°C
P18 Room probe for the negative conservation process
-50
99
-25
-25
°C
P19 Positive time process duration
0
599
89
89
Min
P20 Negative time process duration
0
599
270
270
Min
P21 Set condenser temperature for second fan
-50
99
34
34
°C
P22 Enable controller for secondary fan
1
0
1
1
n°
P23 Relay 4 configuration; 0 = disabled; 1 = UV lamp;
2 = Probe heating; 3 = 3rd condenser fan
0
3
3
0
n°
P24 Sterilization duration setting
1
999
15
15
Min
P25 Sterilization temperature threshold setting
-50
99
5
5
°C
P26 3 ° condenser fan temperature threshold setting
-50
99
36
36
°C
P27 Pressure switch setting. 0 = pressure switch disabled;
1,2,3,4 = alarm counting before locking the loads
0
4
0
0
n°
P28 Probe heating duration setting
1
10
2
2
Min
P29 Probe heating temperature set point
0
90
4
4