Tecnocontrol TS220E Series User Manual Download Page 9

IST-2220.EC04.01/D

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag. 9/17 

 

 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) ITALY 

Tel. +39 02 26922890 - Fax +39 02 2133734 

 

Alarm

The  red  Led  (

ALARM

)  illuminates  (

only  if  it  be  activate  by  Dip-Switch  no.1  set  to  ON

)  if  the  gas  concentration  ex-

ceeds the value indicated in the table below, depending on the model. 

TS220EA 

TS220EA-H 

TS220EC-S 
TS220EC-H 

TS220ES 

TS220EH 

TS220EHCN 

TS220EN 

TS220EN2 

TS220EHCL  TS220ECL 

50 ppm NH

3

 

200 ppm CO 

10 ppm SO

2

 

20 ppm H

2

5 ppm HCN 

25 ppm NO 

30 ppm NO

2

 

5 ppm HCL 

1 ppm CL 

Faults

the yellow Led illuminates and the "

S

" output falls down to 0mA. (The different faults are listed below). 

Yellow  Led  illuminates  each  4  seconds  (

with  green  Led  activate

):

 

this  happens  when  the  “

Cartridge  Sensor

”  has 

overcome its theoretical period of life and its correct operation is not longer guaranteed. The detector keeps on op-
erating normally but it is necessary to replace, as soon as possible, the “

Cartridge

” with a new one. The type to be 

required is described on 

Page 1

. The replacement procedure is described in the attached manual. 

Yellow Led activate, green Led off (

0 mA output signal

):

 

this signal different kind of faults. 

1)

 The Dip-Switch set 

up is wrong, please verify (

see Table 4

). 

2)

 The “

Cartridge

” is not working, please replace with new one. 

3)

 

If a new

 

Cartridge

”  is  installed  or  it  is  not  correctly  connected  or  a  not  compatible  one  is  mounted.  Please  check  the  car-

tridge connections and compatibility (

see on page 1

) these checks are made switching off and on the device.

 

If the 

condition does not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

Yellow and green Led activates (

0 mA output signal

):

 

this happens when the “

Cartridge

” is not working. First try to 

perform the procedure of “

ZERO

” as described in the section

 “

Test and Calibration

 

> Zero adjust

 

then disconnect and 

connect the unit, finally try to replace a new 

Cartridge

”. If the condition is not change, please replace

 

the unit and/or 

send it back to the supplier to repair. 

All  Led  activates 

only  if  reed  Led  be  activate  by  Dip-Switch  no.1  set  to  ON

  (

>20  mA  output  signal

):

 

this  happens  when  the 

Cartridge

” is not working or gas concentration is higher than F.S. If there are not any gas leaks and the condition is 

not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed and testing according to the national dispositions in force on the safety of 
the plants and installation of electric devices. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards.  

TS220EA and TS220EA-H positioning: 

should be fixed at 30÷50 cm from the ceiling (

NH

3

 

gas is lighter than air). 

TS220EC-S and TS220EC-H positioning: 

should be fixed at 1.60 m from the floor (

CO

 

gas is a little lighter than air). 

TS220ES positioning: 

should be fixed at 30÷50 cm from the floor (

SO

2

 gas is heavier than air) 

TS220EH positioning: 

should be fixed at 30-50 cm from the floor (

H

2

S

 gas is heavier than air). 

TS220EHCN positioning: 

should be fixed at 1.60 m from the floor for the protection of persons or over the likely 

point of emission. (

HCN 

gas is a little lighter than air

). 

TS220EN positioning: 

should be fixed at 1.60 m from the floor 

(

NO

 gas is heavy as air). 

TS220EN2 positioning: 

should be fixed at 30÷50 cm from the floor 

(

NO

2

 gas is heavier than air). 

TS220EHCL positioning

: should be fixed at 30÷50 cm from the floor 

(

HCL

 gas is heavier than air). 

TS220ECL positioning

: should be fixed at 30÷50 cm from the floor 

(

CL

2

 gas is much heavier than air). 

Electrical  Connection  (

see  Fig.2

)

:  the  maximum  distance  to  install  each  detector  from  the  Gas  Central  Unit  is 

show in the 

Table 1

. Normally use a tree wire shielded cable. 

The terminals (

+ - S

), are polarized plug-in type, it is necessary to extract them to make the connection. 

Note: Dip-Switch should be set with instrument powered off. Dip-Switch 1 settled ON activates ALARM red 

Led indication (see Table 2). 

Important:

 

Once installation is completed,

 

power up the unit, wait about 

30 to 60 minutes

 and then to adjust the 

sensor to the environment, only if it is necessary,

 

carry out the 

Zero Adjust

” 

(see ‘

Test and Calibration

). 

COMPATIBILITY WITH OTHER CENTRAL UNITS: 

In case of a central unit other then Tecnocontrol, 

please 

verify the max load resistor as shown in 

Fig. 4

. The max load resistor is 50 ohm with 12Vdc power supply, while is 

400 ohm with 24Vdc power supply. We suggest using 24Vdc power supply.

 

WARNING 

Average life

: In clean air and in normal working condition the 

sensor's life is

 

about 2 years.

 After this period the 

yellow Led “

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 6 or 12 months. Tests, Zero Adjust and Calibration 

with sample gas bottle, as explained in the next chapter “

Tests and Calibration

”. 

Note:

  the  detector  is  not  able  to  detect  gas  leaks  occurring  outside  the  room  where  it  is  installed,  neither  inside 

walls or under the floor. 

Sensor operating limits: 

the electrochemical cell, in any case, should not be exposed to temperatures lower than 

-40°C  or  higher  than  60°C.  The  electrochemical  cell  can  be  damaged,  if  it  is  exposed  to  concentrations  over  the 
limit specified in the table, depending on the model. If this condition occurs, please replace the “

Cartridge Sensor

”. 

TS220EA 

TS220EA-H 

TS220EC-S 
TS220EC-H 

TS220ES 

TS220EH 

TS220EHCN 

TS220EN 

TS220EN2 

TS220EHCL 

TS220ECL 

500ppm NH

3

  1000ppm CO  150ppm SO

2

  500ppm H

2

S  100ppm EHN  1000ppm NO  150ppm NO

2

  >30ppm HCL  >50ppm CL

2

 

Safety:

  electrochemical  Cell  contains  a  small  quantity  of  acid.  It  is  possible  that  either  a  very  strong  mechanical 

action or an incorrect instrument use beyond the limits of its operational functioning could provoke a liquid leak out 
of the sensor. Should this event occurs, please avoid touching the come out liquid. Should a contact with either the 
skin or eyes occur, wash immediately and abundantly with water. 

Summary of Contents for TS220E Series

Page 1: ...1 TS220EHCN HCN Acido cianidrico Hydrogen cyanide ZS EHCN TS220EN NO Ossido di azoto Nitric oxide ZS EN1 TS220EN2 NO2 Biossido di azoto Dioxyde d azote ZS EN2 TS220EHCL HCL Acido cloridrico Hydrogen Chloride ZS EHCL TS220ECL CL2 Cloro Chlorine ZS ECL Con Cartuccia Sensore Sostituibile Inside Replaceable Cartridge Sensor Avec Cartouche Capteur échangeable Sommario Contents Sommaire Caratteristiche ...

Page 2: ...in aria pulita Average Life in fresh air Vie moyenne en air pur 2 anni years ans 2 anni years ans 3 anni years ans 2 anni years ans 2 anni years ans 2 anni years ans Tempo massimo di immagazzinamento Max Storage Time Temps maximum de stockage 3 mesi month mois 1 mese month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois Variazione dello Zero Zero shift Dérive du Zero 6...

Page 3: ... month mois 2 mese month mois 3 mese month mois 2 mese month mois Risoluzione Resolution Résolution 0 1 ppm 1 ppm 1 ppm 0 7 ppm 0 1 ppm Tempo di risposta T90 Response Time T90 Temps de réponse T90 120 secondi Seconds secondes 60 secondi Seconds secondes 60 secondi Seconds secondes 2 70 secondi Seconds secondes 50 secondi Seconds secondes Ripetibilità Repeatability Répétitivité 2 del segnale of the...

Page 4: ...5 Il suo TWA è 2 ppm Time Weighted Average e lo STEL è 5 ppm Short Term Exposure Limit L SO2 è un forte irritante per gli occhi e le vie respiratorie Per inalazione può causare edema polmonare e una prolungata esposizione può portare alla morte Nel caso si combini con l acqua forma Idrogeno Solforato H2S TS220EH ha un sensore in grado di rilevare Idrogeno Solforato H2S sinonimo Acido Solfidrico ch...

Page 5: ... spento uscita 0mA indica più possibilità di guasto 1 la configurazione dei Dip Switch non è corretta verificarne la posizione Vedi Tabella 4 2 la Cartuccia Sensore è guasta sostituirla con una nuova 3 se è installata una Cartuccia nuova o non è collegata correttamente o non è stata montata quella compatibile Controllare le connessioni con la cartuccia e la compatibilità vedi a pag 1 Eseguite le v...

Page 6: ...ita in mA cambiando valore attiva i dispositivi d allarme della Centrale cui è collegata Test Elettrico Regolazione dello Zero e Calibrazione per accedere a queste tre funzioni è necessario inserire il relativo Codice tramite i pulsanti F1 e F2 Per far sì che la pressione su un pulsante sia riconosciuta tenerlo premuto per circa un secondo finche non si spegne per un attimo il Led Verde Dopodichè ...

Page 7: ...che in quanto è l unico metodo per controllare l effettivo funzionamento del rilevatore Infilare il TC014 sul portasensore in funzione del modello regolare il riduttore della bombola in modo che il flus sometro indichi il valore indicato in colonna 3 vedi fig 3 Controllare che il multimetro con i puntali sui Test Point TEST mA vedi fig 2 raggiunga in 3 5 minuti circa il valore in mV indicato sotto...

Page 8: ...o air is 1 04 His TWA Time Weighted Average and STEL Short Term Exposure Limit are 25 ppm NO is a strong oxidant and reacts with combustible and reducing materials On contact with the air turns it into nitrogen dioxide NO2 Nitric oxide is irritating to eyes and respiratory tract Inhalation can cause pulmonary edema may also have effects on the blood causing the formation of metaemoglobina In more ...

Page 9: ...ES positioning should be fixed at 30 50 cm from the floor SO2 gas is heavier than air TS220EH positioning should be fixed at 30 50 cm from the floor H2S gas is heavier than air TS220EHCN positioning should be fixed at 1 60 m from the floor for the protection of persons or over the likely point of emission HCN gas is a little lighter than air TS220EN positioning should be fixed at 1 60 m from the f...

Page 10: ...inserted the Check Code all Led are switched off Then Led will switch on in se quence from the yellow up to the red At the end all the Led will remain lighted for around 5 seconds then the de tector returns at the conditions of normal operation It is advisable to perform this operation every 12 months ac cording to the use Note this function is not working if the red LED is already switched on ZER...

Page 11: ...ns la partie inférieure du boîtier est logée une car touche capteur échangeable contenant l élément sensible et les données identificatrices et de réglage Les TS220E sont sondes à transmetteur sur 3 fils avec un signal de sortie S 4 20mA linéaire avec fin d échelle du gaz mesuré comme indiqué sur la page 1 Il s utilise en se raccordant sur les centrales d alarmes mono et multi voies Tecnocontrol S...

Page 12: ...orme en acide ni trique et oxyde nitrique Le NO2 se forme par oxydation du monoxyde d azote NO lui même formé par combinai son directe de l azote et de l oxygène à haute température durant certains processus de combustion centrales thermiques installations de chauffage et véhicules surtout à moteurs diesel Le NO2 même à concentration modé rée provoque toux aigues douleurs thoraciques convulsions e...

Page 13: ...environ léger que l air Positionnement du TS220EN2 Il doit être fixé à environ 30 40cm du plancher le gaz NO2 étant plus lourdes que l air Positionnement du TS220EHCL Il doit être fixé à environ 30 40cm du plancher le gaz HCL étant plus lourdes que l air Positionnement du TS220ECL Il doit être fixé à environ 30 40cm du plancher le gaz CL2 étant plus lourdes que l air Raccordements électriques fig ...

Page 14: ...bles qui ne risquent pas d entraîner sa dispersion TEST ELECTRIQUE Code Test F2 F2 F1 F1 cette fonction permet d effectuer un test fonctionnel de l appareil lage Après avoir mis l installation en sécurité et avoir inséré le Code Test toutes les leds s éteignent Ils s allume ront ensuite en séquence de la led jaune jusqu à la rouge À la fin toutes les leds resteront allumées pendant envi ron 5 seco...

Page 15: ...e le débitmètre indique la valeur indique dans le tableau ci dessous dans la colonne 3 voir aussi Fig 3 Vérifiez avec le voltmètre sur les bornes de test TEST mA fig 2 que la valeur en mV indiquée dans la colonne 4 est atteinte Ou bien que la sortie en mA augmente jusqu à la valeur indiquée dans la colonne 5 et que la centrale à laquelle le détecteur est connecté indique une valeur en de la LIE co...

Page 16: ...ide dioxyde d azote 20 ppm 2 2 1 16 Cloro Clorine Chlore 1 ppm 0 0 0 Etanolo Ethanol Éthanol 200 ppm 0 0 2 5 0 Etilene Ethylene Éthylène 100 ppm 0 0 80 50 0 1 Idrogeno Hydrogen Hydrogène 100 ppm 0 0 2 46 40 1 6 Idrogeno Solforato Hydrogen sulphide Sulfure d hydrogène 15 ppm 3 0 3 0 0 75 0 15 3 4 Monossido di carbonio Carbon Monoxide Monoxyde de carbone 100 ppm 0 1 100 100 1 1 Ossido di azoto Nitri...

Page 17: ...de détection RL S S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration F1 F2 Tasti Key Touches 0 3 L min 1 L min TC014 Bombola di gas titolato Sample gas bottle Bouteille avec mélange de gaz titré Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de ch...

Reviews: