Cross sensitivity to other gases:

 this detector is designed to detect gas leaks at a very low concentration. The 

electrochemical  cells  employed  have  a  good  resistance  towards  products  such  as  sprays,  detergents,  glues  and 
paints. 

However, in case of products containing substances in great quantity, these could interfere with the Sensor 

and cause false alarms.

 We recommend ventilating the room when products like these are used. Alcohols, Hydro-

gen and volatile organic solvents in great quantity cause false alarms, and then the cell needs one or more hours in 
clean air to recover the normal sensitivity conditions. 

TEST and CALIBRATION 

PAY ATTENTION

: This procedure has to be made with extreme attention and by authorized and trained people; 

because starting this procedure it will increase mA output causing the activation of connected alarm devices. 

Operation  Check,  Zero  Adjust,  and  Calibration

:

  are  different  code  protected  functions.  To  access  these  func-

tions is necessary to insert the relevant “

Code

" through the keys F1s and F2. To have the key pressure recognized, 

hold  pressing  it  for  around  a  second  (

until  the  green  Led  doesn't  switch  off  for  a  moment

).  Then  the  next  key  can  be 

pressed. In case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 
The 

Calibration Check

 is a function code free. 

Calibration Kit, Sample Gas Bottles

 (

for Calibration Check and Calibration

) the mixture to be used depending  on the 

model installed is shown in the table below: 

MODEL 

Sample gas bottle

 

Our Code 

KIT Code 

TS220EA - TS220EA-H 

100 ppm 

Ammonia (NH

3

in Nitrogen 

Available on request

 

TC014 

TS220EC-S - TS220EC-H 

300 ppm 

Carbon monoxide (CO) 

in Nitrogen 

BO210 

TC011/TC014

 

TS220ES 

10 ppm 

Sulphur dioxide (SO

2

in Nitrogen 

Available on request 

TC014

 

TS220EH 

50 ppm 

Hydrogen sulphide (H

2

S)  in Nitrogen 

Available on request 

TC014

 

TS220EHCN 

10 ppm 

Hydrogen cyanide (HCN)  in Nitrogen 

Available on request 

TC014

 

TS220EN 

100 ppm 

Nitric oxide (NO) 

in Nitrogen 

Available on request 

TC014

 

TS220EN2 

30ppm 

Nitrogen dioxide (NO

2

in air 

Available on request 

TC014

 

TS220EHCL 

10ppm 

Hydrogen cloride (HCL) 

in Nitrogen 

Available on request 

TC014

 

TS220ECL 

10ppm 

Nitrogen dioxide (NO

2

in air 

Available on request 

TC014

 

It is  possible  to  use either  the 

disposable cylinders  with adjust valve

 or the  high pressure  ones  with reduction 

gear. Some cylinders have a fixed flow reducers, make the necessary value in 

Table, column 3, page 11

. Is also nec-

essary the 

Tecnocontrol calibration kit model TC014 (Inox)

. To ensure that the gas concentration reaches sen-

sor, use steel reduction gear and Teflon tubes or other compatible materials which do not disperse gas. 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of  the  detector.  After  having  inserted  the  "

Check  C

ode

",  all  Led  are  switched  off.  Then  Led  will  switch  on  in  se-

quence, from the yellow up to the red. At the end all the Led will remain lighted for around 5 seconds, then the de-
tector  returns  at  the  conditions  of  normal  operation.  It  is  advisable  to  perform  this  operation  every  12  months  ac-
cording to the use. 

Note

: this function is not working if the red LED is already switched on. 

“ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (

environment without the presence of toxic gas or other pollutants

). Consider that the TS220E series have a sophisti-

cated follower of zero, that every hour will reset the sensor, if of course there is the presence of gas. If necessary, 
perform  this  operation  after  installation  or  after  changing  the  “

Cartridge

”  or  every  6-12  months  depending  on  envi-

ronmental conditions. After entering the "

Zero Code

" as confirmation of the operation, there will be a flashing red Led 

and output becomes 4.0 mA. 

Note

: This function is not working if mA output is higher than the value shown in the table below, depending on the 

model, or if the red Led is already ON. In this case, please recalibrate the unit and/or replacing the “

Cartridge

”. 

TS220EA 

TS220EA-H 

TS220EC-S 
TS220EC-H 

TS220ES 

TS220EH 

TS220EHCN 

TS220EN 

TS220EN2 

TS220EHCL 

TS220ECL 

4,8 mA 

15ppm NH

3

 

4,8 mA 

15ppm CO 

6,4 mA 

3ppm SO

2

 

4,8 mA 

5ppm H

2

S

 

8 mA 

2,5ppm HCN

 

5,6 mA 

10ppm NO

 

6,6 mA 

5ppm NO

2

 

8 mA 

2,5ppm HCL

 

4,8 mA 

0,5ppm HCL

 

“CALIBRATION” (

Calibration Code

: F2, F2, F2, F1, F2, F1)

this function allows completely recalibrate the sensor 

using the gas mixture indicated above.

 

Warning

to guarantee that no errors of elaboration happen, the possibility exists that during the Calibration the yel-

low Led switch off every 8 seconds, in this case interrupt the procedure, switch off and switch on the instrument and 
repeat the Calibration. If condition persists it will be necessary to send the detector to the supplier for the reparation. 

Important note:

 

during Calibration routine the mA output indicates 0mA

.

 

The “

Calibration

” can be done in clean air only (

environment without the presence of toxic or other polluting gas

). With the keys 

perform the “

Calibration Code

". Wait until the yellow and green Led switch on fix and the red Led starts to flash. In-

sert the TC014 on the sensor holder and adjust the influx of the gas the way that the flow meter reaches the value 
indicates  in  table  below  in 

column 3

,  depending  on  the model  (

see also Fig.3

). 

Wait  around  3÷5  minutes

,  until  the 

red Led lights (

and while it is ON

), press the key F2 and hold it pressed until the red LED is switched off for at least 2 

seconds  (

but  if  the  red  LED  continues  to  blink  more  than  5-6  minutes  means  that  the  gas  flow  is  not  constant  or 

unsatisfactory, or the concentration is not as required, stop the operation, turn off the instrument and recalibrate

). 

Then, close the gas cylinder and remove TC014

. At this point we can have two possibilities: 

Yellow  and  green  Led  illuminates:

  the  calibration  routine  is  correct. 

Wait  8  seconds,  until  the  instrument  auto-

matically restores the normal working conditions

(

See “

Operational Description > Preheating

). 

Summary of Contents for TS220E Series

Page 1: ...1 TS220EHCN HCN Acido cianidrico Hydrogen cyanide ZS EHCN TS220EN NO Ossido di azoto Nitric oxide ZS EN1 TS220EN2 NO2 Biossido di azoto Dioxyde d azote ZS EN2 TS220EHCL HCL Acido cloridrico Hydrogen Chloride ZS EHCL TS220ECL CL2 Cloro Chlorine ZS ECL Con Cartuccia Sensore Sostituibile Inside Replaceable Cartridge Sensor Avec Cartouche Capteur échangeable Sommario Contents Sommaire Caratteristiche ...

Page 2: ...in aria pulita Average Life in fresh air Vie moyenne en air pur 2 anni years ans 2 anni years ans 3 anni years ans 2 anni years ans 2 anni years ans 2 anni years ans Tempo massimo di immagazzinamento Max Storage Time Temps maximum de stockage 3 mesi month mois 1 mese month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois Variazione dello Zero Zero shift Dérive du Zero 6...

Page 3: ... month mois 2 mese month mois 3 mese month mois 2 mese month mois Risoluzione Resolution Résolution 0 1 ppm 1 ppm 1 ppm 0 7 ppm 0 1 ppm Tempo di risposta T90 Response Time T90 Temps de réponse T90 120 secondi Seconds secondes 60 secondi Seconds secondes 60 secondi Seconds secondes 2 70 secondi Seconds secondes 50 secondi Seconds secondes Ripetibilità Repeatability Répétitivité 2 del segnale of the...

Page 4: ...5 Il suo TWA è 2 ppm Time Weighted Average e lo STEL è 5 ppm Short Term Exposure Limit L SO2 è un forte irritante per gli occhi e le vie respiratorie Per inalazione può causare edema polmonare e una prolungata esposizione può portare alla morte Nel caso si combini con l acqua forma Idrogeno Solforato H2S TS220EH ha un sensore in grado di rilevare Idrogeno Solforato H2S sinonimo Acido Solfidrico ch...

Page 5: ... spento uscita 0mA indica più possibilità di guasto 1 la configurazione dei Dip Switch non è corretta verificarne la posizione Vedi Tabella 4 2 la Cartuccia Sensore è guasta sostituirla con una nuova 3 se è installata una Cartuccia nuova o non è collegata correttamente o non è stata montata quella compatibile Controllare le connessioni con la cartuccia e la compatibilità vedi a pag 1 Eseguite le v...

Page 6: ...ita in mA cambiando valore attiva i dispositivi d allarme della Centrale cui è collegata Test Elettrico Regolazione dello Zero e Calibrazione per accedere a queste tre funzioni è necessario inserire il relativo Codice tramite i pulsanti F1 e F2 Per far sì che la pressione su un pulsante sia riconosciuta tenerlo premuto per circa un secondo finche non si spegne per un attimo il Led Verde Dopodichè ...

Page 7: ...che in quanto è l unico metodo per controllare l effettivo funzionamento del rilevatore Infilare il TC014 sul portasensore in funzione del modello regolare il riduttore della bombola in modo che il flus sometro indichi il valore indicato in colonna 3 vedi fig 3 Controllare che il multimetro con i puntali sui Test Point TEST mA vedi fig 2 raggiunga in 3 5 minuti circa il valore in mV indicato sotto...

Page 8: ...o air is 1 04 His TWA Time Weighted Average and STEL Short Term Exposure Limit are 25 ppm NO is a strong oxidant and reacts with combustible and reducing materials On contact with the air turns it into nitrogen dioxide NO2 Nitric oxide is irritating to eyes and respiratory tract Inhalation can cause pulmonary edema may also have effects on the blood causing the formation of metaemoglobina In more ...

Page 9: ...ES positioning should be fixed at 30 50 cm from the floor SO2 gas is heavier than air TS220EH positioning should be fixed at 30 50 cm from the floor H2S gas is heavier than air TS220EHCN positioning should be fixed at 1 60 m from the floor for the protection of persons or over the likely point of emission HCN gas is a little lighter than air TS220EN positioning should be fixed at 1 60 m from the f...

Page 10: ...inserted the Check Code all Led are switched off Then Led will switch on in se quence from the yellow up to the red At the end all the Led will remain lighted for around 5 seconds then the de tector returns at the conditions of normal operation It is advisable to perform this operation every 12 months ac cording to the use Note this function is not working if the red LED is already switched on ZER...

Page 11: ...ns la partie inférieure du boîtier est logée une car touche capteur échangeable contenant l élément sensible et les données identificatrices et de réglage Les TS220E sont sondes à transmetteur sur 3 fils avec un signal de sortie S 4 20mA linéaire avec fin d échelle du gaz mesuré comme indiqué sur la page 1 Il s utilise en se raccordant sur les centrales d alarmes mono et multi voies Tecnocontrol S...

Page 12: ...orme en acide ni trique et oxyde nitrique Le NO2 se forme par oxydation du monoxyde d azote NO lui même formé par combinai son directe de l azote et de l oxygène à haute température durant certains processus de combustion centrales thermiques installations de chauffage et véhicules surtout à moteurs diesel Le NO2 même à concentration modé rée provoque toux aigues douleurs thoraciques convulsions e...

Page 13: ...environ léger que l air Positionnement du TS220EN2 Il doit être fixé à environ 30 40cm du plancher le gaz NO2 étant plus lourdes que l air Positionnement du TS220EHCL Il doit être fixé à environ 30 40cm du plancher le gaz HCL étant plus lourdes que l air Positionnement du TS220ECL Il doit être fixé à environ 30 40cm du plancher le gaz CL2 étant plus lourdes que l air Raccordements électriques fig ...

Page 14: ...bles qui ne risquent pas d entraîner sa dispersion TEST ELECTRIQUE Code Test F2 F2 F1 F1 cette fonction permet d effectuer un test fonctionnel de l appareil lage Après avoir mis l installation en sécurité et avoir inséré le Code Test toutes les leds s éteignent Ils s allume ront ensuite en séquence de la led jaune jusqu à la rouge À la fin toutes les leds resteront allumées pendant envi ron 5 seco...

Page 15: ...e le débitmètre indique la valeur indique dans le tableau ci dessous dans la colonne 3 voir aussi Fig 3 Vérifiez avec le voltmètre sur les bornes de test TEST mA fig 2 que la valeur en mV indiquée dans la colonne 4 est atteinte Ou bien que la sortie en mA augmente jusqu à la valeur indiquée dans la colonne 5 et que la centrale à laquelle le détecteur est connecté indique une valeur en de la LIE co...

Page 16: ...ide dioxyde d azote 20 ppm 2 2 1 16 Cloro Clorine Chlore 1 ppm 0 0 0 Etanolo Ethanol Éthanol 200 ppm 0 0 2 5 0 Etilene Ethylene Éthylène 100 ppm 0 0 80 50 0 1 Idrogeno Hydrogen Hydrogène 100 ppm 0 0 2 46 40 1 6 Idrogeno Solforato Hydrogen sulphide Sulfure d hydrogène 15 ppm 3 0 3 0 0 75 0 15 3 4 Monossido di carbonio Carbon Monoxide Monoxyde de carbone 100 ppm 0 1 100 100 1 1 Ossido di azoto Nitri...

Page 17: ...de détection RL S S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration F1 F2 Tasti Key Touches 0 3 L min 1 L min TC014 Bombola di gas titolato Sample gas bottle Bouteille avec mélange de gaz titré Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de ch...

Reviews: