INSTALLATION 

The gas detector must be accurately installed and testing according to the national dispositions in force on 
the safety of the plants and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Avoid  obstacles that  block the view  of the detector or the diffusion of air around the sensor. Consider that the air 
movements can affect the detection of gas. Avoid mounting in corners, near doors or windows or in the direct flow 
of air intakes or ventilation systems. Normally, the detector should be installed indoors, but if it was outside, should 
be protected from direct sun and rain, and should be avoided fast heat drops. 

Models TS293IM

 should be fixed at 20-30 cm from the ceiling (Methane is lighter than air). 

Model TS293IG 

should be fixed at 20-30 cm from the floor (LPG gas is heavier than air). 

Models TS293IB 

should be fixed at 20-30 cm from the floor (Petrol vapours are heavier than air). 

Model TS293IX 

should be fixed in high position with a gas Vapour Density less than 1 (

the gas is lighter than air

) or in 

bottom position with a density greater than 1, (

the gas is heavier than air

) (

see Table 3 - column n.7

). 

Electrical Connection 

(

see Fig.2

)

: the maximum distance to install each detector from the Gas Control Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The opening of the enclosure and the connections must be affected with detector not powered. 

To open the detector, remove the two Allen screws, and then remove the cover carefully. 
The terminals (

+ - S

), are polarized plug-in type, it is necessary to extract them to make the connection. 

NOTE: Dip-Switch should be set with instrument powered off. You can inhibit the operation of the Red LED 

(ALARM) 

(

See Table 2

). 

Important

:

 Once installation is completed, close the housing,

 

power up the unit. It is not necessary perform any ad-

justment, wait about 20 to 30 minutes and then, if it is required, carry out the "

Operation Check

"

 

(

see ‘

Test and Calibra-

tion

).

 

COMPATIBILITY WITH OTHER CENTRAL UNITS: In case of a central unit other than Tecnocontrol

, please 

verify the max load resistor as shown in 

Fig. 4

. We suggest using 24Vdc power supply. 

We accept no liability for any malfunction, failure or damage caused by products that are not compatible or 
not of our production. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

After  an  exposure  above  the  limits  of measurement  (100%LEL),  the  functioning  of  the  detector  must  be  checked 
with the titled gas as indicated in paragraph "

CALIBRATION CHECK

". 

Periodical testing

: we recommend performing tests, at least annually or more frequently (3-6 months) depending 

on  environmental  conditions  and  safety  requirements.  Tests: 

OPERATION  CHECK,  ZERO  ADJUST

  and  with  Gas/Air 

mixture, the 

CALIBRATION CHECK

 

and if necessary the 

CALIBRATION 

as explained in chapter “

Tests and Calibration

”. 

Note:

  the  detector  is  not  able  to  detect  gas  leaks  occurring  outside  the  room  where  it  is  installed,  neither  inside 

walls nor under the floor. 

Warning:

 

Consider that  in  polluted  environments, with the continued  presence  of vapours of flammable gases or 

over the standard temperature and pressure, the useful life of the sensor can be reduced. 

TEST and CALIBRATION 

PAY ATTENTION

This following procedure has to be made by competent and trained personnel because, 

are activated control unit outputs (relays), causing the intervention of the connected alarm devices. 

Operation Check, Zero Adjust and Calibration

:

 are different code protected functions. To access these functions 

is necessary to insert the relevant “

Code

" through the keys F1 and F2. To have the key pressure recognized, hold 

pressing it for around a second (

until the Green LED doesn't switch off for a moment

). Then the next key can be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Cylinders

 (

for Calibration Check and Calibration

) please, only uses a mixture: 

MODEL 

Sample Gas Cylinder for Calibration 

Tecnocontrol Code 

TS293IM

-Methane

 

TS293IX

-Methanol

 

2.2% Volume 

(= 50% LEL)

  

Methane

 (CH

4

)

 

in air

 

Available on request

 

TS293IG

-

LPG

 

TS293IB

-Petrol

 

TS293IX

-Heptane

 

0.7% Volume 

(= 50% LEL) 

 

Butane

 (C

4

H

10

)

 

in air 

Available on request

 

 

 

 

You  can  use 

disposable  cylinder,  complete  with  adjust  valve

.  Is  also  necessary  to  use 

the  calibration  kit 

Tecnocontrol model TC011

 (

for non-corrosive gases only

) or 

TC014

 (

Stainless steel for corrosive gases

).

 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having inserted the "

Check Code

", all LED are switched off. Then LED will switch on in se-

quence, from the yellow up to the red. At the end all the LED will remain lighted for around 5 seconds, and then the 
detector returns at the conditions of normal operation. It is advisable to perform this operation every 12 months ac-
cording to the use. 

Note

: this function is not working if the red LED is already switched on. 

Summary of Contents for TS293IM

Page 1: ... de mesure TS293 IM IG IB 0 100 LIE LEL TS293 IX Vedi Tabella 3 seeTable 3 Tableau 3 Risoluzione Resolution résolution 1 LIE LEL Vita media in aria Average Life in air Vie moyenne en air MTBF Sensore Sensor Capteur 5 anni years ans Tempo di Preriscaldo Warm up time Temps de préchauffage 60 sec funzionamento operational fonctionnement 5 min a specifiche Full specification Stabilité Tempo di rispost...

Page 2: ...sore NDIR si basa sul principio fisico che alcuni tipi di gas assorbono determi nate lunghezze d onda di energia infrarossa In pratica un filamento genera l energia a infrarossi che concentrata passa attraverso il gas da misurare e arriva al rivelatore Il sensore è doppio il primo definito attivo ha un filtro ot tico specifico per il gas da rilevare mentre il secondo chiamato riferimento ha un fil...

Page 3: ...esto la Verifica di funzionamento COMPATIBILITÀ CON ALTRE CENTRALI Se non si usa una centrale gas Tecnocontrol calcolare la resistenza di carico massima utilizzando il grafico in Fig 4 Si consiglia in ogni caso di utilizzare un alimentazione a 24Vcc Si declina ogni responsabilità per malfunzionamenti guasti o danni causati da prodotti non compatibili oppure non di nostra produzione AVVERTENZE Vita...

Page 4: ... premere il tasto F2 e tenerlo premuto finché il LED rosso non rimane spento per almeno 2 secondi se invece il LED rosso continua a lampeggiare oltre 4 5 minuti indica un flusso di gas non costante o in sufficiente o la concentrazione non è quella richiesta Per uscire dalla calibrazione premere F1 e F2 contempora neamente Chiudere la bombola e togliere il TC011 o il TC014 A questo punto si possono...

Page 5: ...ses absorb certain wavelengths of infrared energy The sensor is double the first defined as active has an optical filter for the specific gas to be detected while the second called reference has a filter with a different wavelength and provides the Zero value The signal differ ence between the two sensors provides the value of the gas concentration The advantage of this technique is that the senso...

Page 6: ...n time In fresh air and in nor mal working condition the sensor s life is about 5 years from the date of installation After this period the yellow LED FAULT flashes every 4 seconds is necessary replacing the Cartridge Sensor After an exposure above the limits of measurement 100 LEL the functioning of the detector must be checked with the titled gas as indicated in paragraph CALIBRATION CHECK Perio...

Page 7: ... to turn off and turn on the unit or replace the Cartridge Sensor NOTE It is possible to exit at any time from the calibration function by pressing the F1 and F2 keys in this way the system returns to normal operation CALIBRATION CHECK no Code required using the gas mixture indicated above according to the model this al lows you to check the correct response to the gas and can be performed after C...

Page 8: ...onnement normal Après ce temps le capteur est apte à détecter le gaz mais il n atteint les conditions de stabilité optimale qu après une heure environ de fonctionnement continu Fonctionnement Normal seule la Led vert ON doit être allumée Le Led Rouge ALARM s allume si la concentration de gaz dépasse le 20 LIE Uniquement si elle est activée avec les Dip switches Dérangement La centrale signale les ...

Page 9: ...les limites de mesure 100 LIE le fonctionnement du détec teur doit être vérifié avec le gaz titré comme indiqué au paragraphe VÉRIFICATION Vérifications Périodiques nous conseillons d exécuter tous les ans ou plus fréquemment 3 6 mois en fonction des conditions environnementales et de sécurité requises la vérification de fonctionnement du détecteur Test Élec trique Réglage du Zéro et avec mélange ...

Page 10: ...la sonde relit les données de la Cartouche capteur avec clignotement de la Led rouge jusqu à stabilité ensuite elle est prête pour une nouvelle tentative de calibra tion Répéter la Calibration en appuyant sur F2 Si la condition d erreur persiste essayer en coupant puis réta blissant l alimentation de la sonde ou bien substituer la Cartouche capteur NOTA il est possible de sortir à tout moment de l...

Page 11: ...ire à l air Tabella 4 Table 4 Tableau 4 1 2 3 3 4 3 5 3 Modello e Gas Rilevato Model and detected Gas Modèle et Gaz détecté Bombola di Gas per Calibrazione e Verifica Gas Cylinder for Calibration and verification Bouteille de gaz titré pour calibration et vérification TESTmV TP1 TP2 mV Uscita Output Sortie mA LIE LEL TS293IM Metano Methane Méthane 2 2 Vol 50 vol LIE LEL Metano in aria Methane in a...

Page 12: ...Area di funzionamento Allowable oparating region 350 700 800 Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration TC011 o or ou TC014 0 3 L min S 12 24V mA 12 24Vdc Alimentazione Power Supply Alimentation Centrale rivelazione gas Gas Central Unit Centrale de détection RL S Test Uscita Output Test Sortie Test 40 200mV TP1 TP2 S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Fig 2 Sch...

Reviews: