Tecno Control TS292KB User Manual Download Page 5

IST-2292.KM02.01/A

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/10

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

connect and connect the unit, finally try to replace a new 

“Cartridge Sensor

”. If the condition is not change, it will be 

necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (>

24mA output signal

):

 

this happens when the “

Cartridge Sensor

” is not working or gas concen-

tration is out of scale (higher than 25% LIE) If there are not any gas leaks and the condition is not change, it will be 
necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed according to the national dispositions in force on the safety of the plants 
and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Model TS292KG positioning

:

 

it should be fixed at 20-30 cm from the floor (LPG gas is heavier than air). 

Model TS292KM positioning

:

 

it should be fixed at 20-30 cm from the ceiling (Methane gas is lighter than air). 

Model TS292KI positioning

:

 

it should be fixed at 30-40 cm cm from the floor (Hydrogen gas is heavier than air). 

Model TS292KB positioning

:

 

it should be fixed at 30-40 cm cm from the floor (Petrol gas is heavier than air). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the Gas Central Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The terminals (+

 - S

), are plug-in type, it is necessary to extract them to make the connection. Pay attention when 

you insert them again, being polarized. With the

 

Dip-Switches the Alarm Red Led activation is determined. 

Note:

 Dip-Switch should be set with instrument powered off. Dip-Switch 1 settled ON activates ALARM Led indica-

tion (

see Table 2

). 

Important

:

 

Once installation is completed,

 it is necessary to adjust the sensor to the environment conditions,

 con-

nect the unit, wait about 20÷30 minutes and the carry out the 

”Zero Ad just” 

(see ‘

Test and Calibration >

). 

COMPATIBILITY WITH OTHER CENTRAL UNITS: In case of a central unit other then Tecnocontrol, 

please 

verify the max load resistor as shown in 

Fig. 4

. We suggest using 24Vdc power supply. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 4 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 12 months. 

Operation Check, Zero Adjust, Calibration Check 

and Calibration

 with Gas/Air mixture as explained on page 4 chapter “

Tests and Calibration

”. 

Note:

 the detector is not able to detect gas leaks occurring outside the room where it is installed, neither inside 

walls nor under the floor. 

Important:

 

The catalytic sensor operates only in presence of Oxygen. Do not use pure gases or a lighter directly 

on the sensor since they could damage it irremediably. 

Warning:

 

some substances cause a permanent reduction in sensitivity. Avoid contacts of the sensor with vapours 

of Silicone compounds, Tetra-ethyl Lead (petrol antiknock additive) and Phosphate esters, since they can reduce 
irremediably its sensitivity. Some substances produce a temporary loss of sensitivity. This “inhibitors” include Hy-
drogen sulphides, Chlorine, Chlorinated hydrocarbons and halogenated compounds. The sensitivity is recovered 
after a short period of running in clear air. 

TEST and CALIBRATION 

PAY ATTENTION

: This procedure has to be made with extreme attention and by authorized and trained people; 

because starting this procedure it will increase mA Output causing the activation of connected alarm devices to the 
gas Central Unit. 

Operation Check, Zero Adjust, Calibration Check and Calibration

:

 are different code protected functions. To ac-

cess these functions is necessary to insert the relevant “

Code

" through the keys F1 and F2. To have the key pressure 

recognized, hold pressing it for around a second (

until the Green Led doesn't switch off for a moment

). Then the next key can 

be pressed. In case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Bottles

 

(for Calibration Check and Calibration)

 

please, only

 

using a mixture 20%LEL 

(0.88%v/v)

 

Methane in Air (20.9% Oxygen).

 

Catalytic sensors cannot work without Oxygen

. It is possible to 

use either the disposable one litre cylinders with adjust valve or the high pressure ones with reduction gear. Is also 
necessary the Tecnocontrol Calibration Kit model TC011. 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having put the system in safety and inserted the "

Code Test

", all Led are switched off. Then 

they will switch on in sequence, the Led, from the yellow up to the red. At the end all the Leds will remain lighted for 
around 5 seconds, then the instrument returns at the conditions of normal operation. It is advisable to perform this 
operation every 6-12 months according to the use. 

Note: this function is not working if the red Led is already turned on 

 

“ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (

environment without the presence of gas or other pollutants

). Immediately after having inserted the "

Zero Code

", as a 

confirmation of the operation carried out there will be 

1

 flash of the Red Led and the output will become 4,0mA. We 

suggest performing this operation after the installation or after the change of the cartridge and every 6-12 months 
based on the environmental conditions. 

Note

This function is not working if mA output is more than 12mA (10% LEL) and/or red Led is already 

been switched on. In this case, it will be necessary to recalibrate the unit and/or replacing the “Cartridge” 

“CALIBRATION” (

Calibration Code

: F2, F2, F2, F1, F2, F2)

this function allows completely recalibrate the sensor.

 

Summary of Contents for TS292KB

Page 1: ...rico load resistor résistance de charge 50 ohm 12Vdc 10 500 ohm 24Vdc 10 Campo di misura Standard Range Champ de mesure 0 20 LIE LEL Limite Scala Limits Limite echelle 35 LIE LEL 32mA Vita media in aria pulita Average Life in fresh air Vie moyenne en air pur 5 anni years ans Tempo di risposta T90 Response Time T90 Temps de réponse T90 60 secondi seconds secondes Ripetibilità Repeatability Répétibi...

Page 2: ... stabilità ottimali dopo circa 4 ore di funzionamento continuo Funzionamento Normale deve essere acceso il solo Led Verde ON Il Led Rosso ALARM si accende se è stato abilitato se la concentrazione di Gas supera il 20 LIE I Guasti possibili sotto elencati sono indicati dall accensione del Led giallo FAULT e portando l uscita S a 0mA Il Led Giallo si accende ogni 4 secondi con il Led Verde acceso pe...

Page 3: ...ccessivo In caso d errore basta aspettare circa 10 secondi e la sequenza è automaticamente cancellata Kit di Taratura e Bombole con Miscela Aria Gas per Calibrazione e Verifica la miscela da utilizzare è Gas Meta no al 20 LIE 0 88 v v in aria 20 9 Ossigeno circa in quanto i sensori catalitici non possono assolutamen te funzionare in assenza d ossigeno È possibile usare sia bombole monouso con valv...

Page 4: ...ter than air Its density as to air is 0 55 and its LEL Lower Explosive Limit is 4 4 v v volume TS292KG GPL is calibrated to detect LPG a gas heavier than air and consists of a mixture of 20 30 Propane C3H8 and 80 70 Butane C4H10 Propane density as to air is 1 56 while Butane is 2 05 The LEL is 1 7 v v for Propane and 1 4 v v for Butane Standard calibration to LPG is carried out for Butane gas TS29...

Page 5: ...r under the floor Important The catalytic sensor operates only in presence of Oxygen Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably Warning some substances cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds Tetra ethyl Lead petrol antiknock additive and Phosphate esters since they can reduce ...

Page 6: ...alue result is more different is necessary to recalibrate the sensor see Calibration Then close the gas bottle re move TC011 press the key F2 on the instrument to restore the normal working conditions and the mA out put will slowly decrease up to 4mA F DESCRIPTION Le TS292K est un transmetteur 4 20mA pour gaz et vapeurs combustibles avec capteur catalytique pouvant également être utilisé en systèm...

Page 7: ... dans les zones avec dangers d explosions et les normes de sûreté des installations Montage en Fig 1 sont indiquées les dimensions Le détecteur doit être monté en position verticale avec le cap teur tourné vers le bas Positionnement du TS292KM il doit être fixé à environ 20 30 cm du plafond le gaz méthane étant plus léger que l air Positionnement du TS292KG il doit être fixé à environ 20 30 cm du ...

Page 8: ...pè riere a 10 de la LIE 12mA Dans le cas il necessaire de procéder a la calibration ou bien de sustituer la cartouche ETALONNAGE Code de Etalonnage F2 F2 F2 F1 F2 F1 cette fonction permet l étalonnage du capteur Le mélange à utiliser est le mélange méthane 20 LIE 0 88 v v en air 20 9 oxygène environ Durant la procédure une rare possibilité existe que la LED Jaune clignote chaque 8 secondes dans ce...

Page 9: ... è Tthe max distance to install each detector from the Gas Central Unit Model CE100 CE400 CE600 CE700 CE380UR is La maxi distance à laquelle peuvent être raccordées les sondes à les centrales CE100 CE400 CE600 CE700 CE380UR est 0 75 mm2 26 Ω km 100 m 300 m 1 mm2 20 Ω km 150 m 400 m 1 5 mm2 14 Ω km 200 m 500 m 2 5 mm2 8 Ω km 400 m 800 m Tabella 2 Table 2 Tableau 2 S1 SET Dip Switch Led Allarme Alar...

Page 10: ...velazione gas Gas Central Unit Centrale de détection RL S S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm Fig 4 Alimentazione Resistenza di Carico ...

Reviews: