OPERATIONAL DESCRIPTION 

Preheating

: when the central unit is supplied, the yellow LED starts to flash and it means the detector is heating. 

After 60 seconds, the green LED switches on and it means the normal working. 

NORMAL OPERATING

: the central unit reads the gas concentration through the remote detector 

1

st

 Red LED:

 

it switch on if the gas concentration exceeds 5% LEL. 

2

nd

 Red LED (ALARM 1):

 

it switch on if the gas concentration exceeds 10% LEL; if within 4 seconds the gas is 

not reduced, the 

PREAL.

 relay will activate. This relay is normally used as a prealarm using a siren (

SE301A).

 

3

rd

 Red LED:

 

it switch on if the gas concentration exceeds 20% LIE; if the gas persists, the 4

th

 red LED 

ALARM 2

 

switches  on  within  30  seconds  and  the 

ALARM

  relay  will  activate.  It  is normally used to stop the gas through the 

manual reset solenoid valve (NO or NC) and/or the interruption of the electrical energy. 

If it has been installed a manual reset solenoid valve N.C. with magnetic sensor (mod. VR420÷VR480) connected to “AUX” input, in the 
case that the gas is still open, the yellow LED and the 

FAULT

 Relay will activate (see 

FAULTS

 section). 

RESET Key

:

 The alarm condition remains latched, LEDs and relays remain activated, even if the gas concentra-

tion is reduced, because the mounted valve is closed. To reset the normal working conditions and/or switch off the 
siren push the 

RESET

 key. 

Buzzer: 

the 

PREAL

. relay will be deactivated and the red LED flashes, only if the gas concentration is higher than 

10% LEL. After 20 seconds, both of them will return in preallarm. (the siren rings) 

If  it  has  been  used a manual reset solenoid valve NC with the magnetic sensor  and in the case that it is snapped, the yellow LED will 
switch off and the 

FAULT

 relay will be deactivated. (See 

FAULTS

 section). 

Alarm

 

RESET:

 

The  central  unit  will  begin  to  the  normal  working,  only  if the gas concentration is lower than 10% 

LEL, the 

ALARM

 relay will be deactivated and the 3

rd

 and 4

th

 red LED will switch off. If activated, the 

FAULT

 relay 

will be deactivated and the yellow LED will switch off. (see 

FAULTS

 sections). 

Warning

:

  Pushing  the 

RESET

  key, 

if  the  gas  concentration  is  higher  than  F.S.,

  it  can  happen  that  the  first 

PREAL

. relay will be deactivated and the first three Rrd LEDs will switch off. The yellow LED will illuminate and the 

FAULT

 relay will activate. 

A fault on the Remote Detector is most probable in this case

. Eliminate the alarm’s 

cause, if the condition persist pushing the RESET button, please consult the 

FAULTS

 section. 

FAULTS

:  The  central  unit  signal  different  kind  of  failures  activating  the  yellow  LED  and  the 

FAULT

  relay.  That  is 

normally activated. This relay, if necessary, can be used both to signal remotely an occurred damage and to signal 
the absence of power to the instrument. 

Yellow and green LEDs and FAULT relay activate:

 

this happens when the remote detector is not working. If this 

condition do not change, it will be necessary to replace the detector or to send it to the supplier back to repair.

 

Yellow, green, 4

th

 red LEDs, FAULT and ALARM relays activate:

 

(

ONLY

 after press 

RESET

 key) this happens 

when the remote detector is not working or in few cases when there is a higher gas concentration. In this case the 
central  unit  will  remain  in  alarm,  as  described  in  the  OPERATING>WARNING  section.  If  there  are  not  any  gas 
leaks,  please  verify  the  cable  connection  between  remote  detector  and  central  unit.  If  the  condition  does  not 
change, replace the remote detector and/or send it back for reparation to the supplier. 

Manual reset solenoid valve NC with magnetic sensor failure: 

this situation appears 

ONLY

 when is installed an electro 

valve with magnetic sensor; if it not close the gas, the 

ALARM

 relay will activate (gas concentration higher than 20% LEL) and the magnetic 

sensor signals to the central unit the this bad working. In this case all led will be lighted and relays will be activated. The failure condition (yel-
low led lighted and 

FAULT

 relay activated) will be cancelled if pressing the 

RESET

 key, the solution of the problem will be visualized.

 

INSTALLATION 

The 

SE128K

 should be installed according to the national disposition in force on the matter.  

Positioning:

 

the central unit should be wall-mounted in an accessible position and easily visible. The central unit 

should not be installed to the open air.

 

The remote Detector:

 

it has to be installed as described in the specific instructions attached with it. 

After  the  installation  and  referred  to  the  gas  indicated  on  the  testing  label  of  the  remote  detector,  apply  on  the 
SE128K, the self-sticking label with the name of the calibration gas inserted in the housing. 

Mounting

: The 

Fig. 2

 shows the instrument size. It has to be wall-mounted by four screw anchors. The 

normally 

closed manually resetting valve

 for the gas cut-off should be installed outside the room in a clearly indicated posi-

tion and should be protected from rain. 

Cable glands

: the lower side of the housing has 3 inputs designed for metric cable glands (

M20x1.5 that accept 

external cables Ø 6÷12 mm

). These passages are closed, but they are not 

manually breakable

, according to thr in-

stallation requirements, they must be drilling. To facilitate the operation, they have a centering for the drill bit. 

Electrical Connection:

 

The installation must be provided for the mains, a bipolar disconnect switch dedicated for 

the gas detection system. The device, clearly identified, must act only on Phase and Neutral. If it is necessary, you 
may install a surge or lightning protector, etc. 

The  instrument  is  supply  with  non  reversible  and  plug-in  terminals.  Therefore  the  cables  should  be  anchored  to  the 
case in order to avoid terminal overstress. The connection to the central unit does not need any hearting. The remote 
detector can be placed at a max. distance of 100 meters from the central unit with a cable of 3x1.5mm

2

 or to a distance 

of 200 meters using a 3x2.5 mm

2

 cable. It is not necessary to use shielded cables. 

Fig. 3

 shows the 230VAC powering connection with alarm siren and normally closed manual resetting valve. 

Fig. 4

 shows the 230VAC powering connection with alarm siren and normally open manual resetting valve. 

Fig. 5

 shows the 230VAC powering connection with alarm siren and our normally closed manual resetting valve 

with positioning sensor (models VR420÷VR480,) to verify, if an alarm occurs, the really gas cut-off. 

Summary of Contents for SE128K

Page 1: ...tandard Range Champ de mesure 0 20 LIE LEL Intervención de alarma 1 1st Alarm intervention Seuil d intervention de alarme 1 10 LIE LEL Intervención de alarma 2 2nd Alarm intervention Seuil d intervention de alarme 2 20 LIE LEL Contactos relé Contacts rating Contact relais 230Vac 3A SPDT Temperatura y humedad de funcionamiento Operation Temp Humidity Temp et humidité de fonctionnement 10 50 C 5 90 ...

Page 2: ...i la concentración de gas es superior al 10 del LEL Después de 20 segundos los dos elementos volverán a la condición de prealarma Suena la sirena Si se ha usado una electroválvula de rearmado manual NC con sensor magnético y ha sido activada el LED amarillo se apagará y el relé FAULT se desactivará Véase la sección FALLOS Rearmado después de un alarma La unidad de control volverá al funcionamiento...

Page 3: ...Verificaciones periódicas recomendamos realizar pruebas de funcionamiento cada 6 12 meses ATENCIÓN Este procedimiento debe realizarse con mucha atención y por parte de personal cualificado y autori zado ya iniciarlo hará que se activen las dos salidas relés lo que a su vez activará los dispositivos de alarma co nectados El botón TEST se desactiva cuando se produce una condición de alarma Verificac...

Page 4: ...low green 4 th red LEDs FAULT and ALARM relays activate ONLY after press RESET key this happens when the remote detector is not working or in few cases when there is a higher gas concentration In this case the central unit will remain in alarm as described in the OPERATING WARNING section If there are not any gas leaks please verify the cable connection between remote detector and central unit If ...

Page 5: ...et SE183KG doit être utilisée avec des installations alimentée en GPL Sur la face avant de la centrale l on distingue la barre graphe indiquant l état de fonctionnement ainsi que la con centration de gaz détectée par la sonde extérieure L appareil est doté de 2 seuils d alarme avec sorties sur relais de type étanche avec contacts inverseurs libres de tension et une sortie sur relais pour dérangeme...

Page 6: ...nuel n f doit être installée à l extérieur du local clairement signalé et protégé de la pluie et des projections de liquide Entrées de câble au bas du boîtier dispose de 3 entrées destinées pour presse étoupes métriques M20x1 5 qui acceptent les câbles Ø externes 6 12 mm Ces passages sont fermés mais ils ne sont pas cassables manuelle ment comme requis pour l installation doivent être foré pour fa...

Page 7: ...closed manual resetting valve Schéma à 12Vcc avec vanne à réarmement manuel norm fermée NC C NA NC C NA NC C NA L N SE301A 12Vdc PREAL ALARM Válvula NC 12Vcc 12VDC NC Valve Vanne n f 12Vcc FAULT AUX 230Vca PS180 2 5A 7Ah 12Vdc 230Vca DETECTOR SONDE SE192K SE193K SE183K S S Fig 5 Esquema con válvula de rearmado manual norm cerrada Wiring diagram with a normally closed manual resetting valve Schéma ...

Reviews: