IST-2126.KM03.02

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/8

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

 

from the floor

 and be placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation in-

takes 

Mounting

: The 

Fig. 2

 shows the instrument size. It has to be wall-mounted by four screw anchors. The 

normally 

closed manually resetting valve

 for the gas cut-off should be installed outside the room in a clearly indicated posi-

tion and should be protected from rain. 

Cable glands

: the lower side of the housing has 3 inputs designed for metric cable glands (

M20x1.5 that accept 

external cables Ø 6÷12 mm

). These passages are closed, but they are not 

manually breakable

, according to the in-

stallation requirements, they must be drilling. To facilitate the operation, they have a centering for the drill bit. 

Electrical Connection:

 

The installation must be provided for the mains, a bipolar disconnect switch dedicated for 

the gas detection system. The device, clearly identified, must act only on Phase and Neutral. If it is necessary, you 
may install a surge or lightning protector, etc. 

The instrument is supply with non-reversible and plug-in terminals. Therefore the cables should be anchored to the 
case in order to avoid terminal overstress. The connection to the detector does not need any hearting. 

Fig. 3

 shows the 230VAC powering connection with alarm siren and normally closed manual resetting valve. 

Fig. 4

 shows the 230VAC powering connection with alarm siren and normally open manual resetting valve. 

Fig. 5

 shows the 230VAC powering connection with alarm siren and our normally closed manual resetting valve 

with positioning sensor (models VR420÷VR480,) to verify, if an alarm occurs, the really gas cut-off. 

Fig. 5

 shows the 12VDC powering connection with both 12VDC alarm siren and normally closed manual resetting 

valve  with,  for  example,  our  power  supply  unit  PS175  (1,2A)  or  PS180  (2,5A)  with  internal  12VDC-7Ah  battery  to 
maintain the system powered on in absence of Main power supply. 

In this case, it is possible to connect the power 

supply also to 230VAC.

 

WARNING 

The detector 

doesn't need adjustments

 after being installed. 

Average life

the sensitive element used in this detector has an excellent stability in time. In fresh air and in normal 

working condition the sensor's life is more than 5 years from the date of installation. 

Important

: Catalytic sensors can operate only in presence of Oxygen. Do not use pure gases or a lighter directly 

on the sensor since they could damage it irremediably

. The detector is not able to detect gas leaks occurring out-

side the room where it is installed, neither inside walls nor under the floor. 

Attention

:  please  note  that  in  polluted  environments,  where  vapours  of  flammable  agents,  especially  solvents, 

might be present, the sensor's life can be reduced. Some substances cause a permanent reduction in sensitivity. 
Avoid  contacts  of  the  sensor  with  vapours  of  Silicone  compounds  (paintings  and  sealing paste), Tetra-ethyl Lead 
and  Phosphate  esters.  Some  other  substances  produce  a  temporary  loss  of sensitivity. These “inhibitors” include 
Hydrogen sulphide, Chlorine, Chlorinated hydrocarbons and halogenated compounds. The sensitivity is recovered 
after a short period of running in clear air. 

FUNTIONAL TESTING 

Periodical testing

we advise to carry out working tests every 6-12 months. 

PAY  ATTENTION

:  This  procedure  has  to  be  made  with extreme attention and by authorized and trained people; 

because starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. 
The 

TEST

 key is deactivating when an alarm condition occurs. 

Instrument operation check

: push the 

TEST

 button for 3 seconds until all Led and relays deactivates.  

Then  the  LED  will  illuminate  in  sequence.  With  the  LEDs  the  corresponding  relays  will  activate  (Yellow  LED  and 
FAULT  relay,  2

nd

  red  LED and PREAL. Relay, 3

rd

 red LED and ALARM relay). After 5 seconds the instrument re-

turns to normal working condition. NOTE: during the Test some conditions occur: 

All 5 LEDs illuminates

ONLY

 when the detector is connected with a control wire for certain types of valves. In this 

case the test results correct. 

Yellow  LED off (after red LEDs)

: indicates the lack of control wire of the valve or that the valve is closed. If this 

wire is disconnected from the detector the test results correct, if not please check the valve and repeat test. If test 
result is unchanged, electrical problems are in place, please contact the supplier.  

The  3rd  Red  LED  off

ONLY 

when the detector is connected with a control wire for certain types of valves. The 

control wire is disconnected or the valve is open. Please check both the valve status and the wire connection and 
repeat the test. If wire is disconnected, check if the wire on the terminal “AUX” is connected and repeat the test. 

All other cases: 

If some LEDs do not light on or some relays do not switch, the detector is damaged. In this case 

please replace it or send it back to the supplier. 

Calibration testing with gas mixture

the calibration is carried out with specific gas in our laboratory. We advise 

to check the calibration only 

using sample gas bottles with a mixture about 20% or 25%LEL Gas in Air (

20.9% 

Oxygen

) (Gas Methane for SE126KM and Butane for SE126KG). Catalytic sensors cannot work without Oxy-

gen

. The calibration testing should be done with Calibration Kit model TC011 (See specific user’s manual). Connect 

the  sample  gas  bottle  to  the  flow  meter,  open  Gas  (0.3  l/min  flow  rate),  wait  for  3  minutes  and  check  that  the  in-
strument activate Alarms as shown in chapter OPERATIONAL DESCRIPTION.

 Note

: In case the values are not the 

required ones please apply to our Laboratory. 

 

FR

 

 DESCRIPTION 

Le 

SE126K

 est un détecteur de gaz pour chaufferies, pour montage aux murs. Utilise un capteur de type catalytique 

pour  gaz  inflammables.  Elle  est  alimentée  en  230Vca  ou  12÷24Vcc/ca  et  l'indice  de  protection  du  détecteur  est 

Summary of Contents for SE126K

Page 1: ...n de alarme 1 10 LIE LEL Intervención de alarma 2 2nd Alarm intervention Seuil d intervention de alarme 2 20 LIE LEL Contactos relé Contacts rating Contact relais 230Vac 3A SPDT Tiempo respuesta T90 Response Time T90 Temps de réponse T90 30 segundos seconds secondes Temperatura y humedad de funcionamiento Operation Temp Humidity Temp et humidité de fonctionnement 10 50 C 5 90 RH sin condensación n...

Page 2: ...n a la condición de prealarma Suena la sirena Si se ha usado una electroválvula de rearmado manual NC con sensor magnético y ha sido activada el LED amarillo se apagará y el relé FAULT se desactivará Véase la sección FALLOS Rearmado después de un alarma El detector volverá al funcionamiento normal solo si la concentración de gas es inferior al 10 LEL el relé ALARM se desactivará y los LEDs rojos 3...

Page 3: ...o ni en el interior de paredes o debajo del suelo Atención tener en cuenta que la vida útil del sensor puede verse reducida si se encuentra en entornos contaminados con presencia de vapores o agentes inflamables especialmente disolventes Algunas sustancias provocan una reducción permanente de la sensibilidad Evitar el contacto del sensor con vapores de compuestos de silicona pinturas y selladores ...

Page 4: ...ith the magnetic sensor and in the case that it is snapped the yellow LED will switch off and the FAULT relay will be deactivated See FAULTS section Alarm RESET The detector will begin to the normal working only if the gas concentration is lower than 10 LEL the ALARM relay will be deactivated and the 3 rd and 4 th red LED will switch off If activated the FAULT relay will be deactivated and the yel...

Page 5: ...nces cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds paintings and sealing paste Tetra ethyl Lead and Phosphate esters Some other substances produce a temporary loss of sensitivity These inhibitors include Hydrogen sulphide Chlorine Chlorinated hydrocarbons and halogenated compounds The sensitivity is recovered after a short period of runn...

Page 6: ... relais Dérangement se désactive Voir section relais Dérangement Réarmement après une d alarme L appareil revient au fonctionnement normal si la concentration de gaz est in férieure 10 de la LIE Le relais ALARME sera désactivé le 3 et 4 led rouge s étendent Si le relais Dérangement est activé il vient désactivé et le LED jaune s étende Voir section relais Dérangement Attention Apres avoir appuyé l...

Page 7: ... que le capteur vienne au contact de vapeurs de silicone plomb tetraethyl ou hydrocarbures chlo rés ces substances pouvant en réduire irréversiblement la sensibilité Le contact occasionnel avec des solvants type trichloréthylène ou tétrachlorure de carbone peuvent inhiber temporairement le capteur Après un bref temps en air pur le capteur reprend son fonctionnement normal VERIFICATIONS PERIODIQUES...

Page 8: ...C NA NC C NA NC C NA L N SE301A PREAL ALARM VR420 VR480 FAULT AUX Fig 4 Esquema con válvula de rearmado manual norm abierta Wiring diagram with a normally open manual resetting valve Schéma avec vanne à réarmement manuel norm ouverte 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Válvula NA NO Valve Vanne n o FAULT AUX Fig 3 Esquema con válvula de rearmado manual norm cerrada Wiring diagram...

Reviews: