background image

IST-2126.KM03.02

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.4/8

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

 

en  el  capítulo  DESCRIPCIÓN  DE  FUNCIONAMIENTO. 

Nota

: En caso de que los valores no sean los deseados, 

contactar con nuestro laboratorio.

 

EN

 

 DESCRIPTION 

The 

SE126K

 is a gas detector for heating plants, with a catalytic sensor for flammable gas. The unit is for wall in-

stallation and the protection code is IP44. It is normally powered at 230 AC and/or 12÷24VAC/DC. 
Two different models are available and the only difference is the calibration carried out with specific gas:  

 The SE126KM model should be used in plants using Methane. 

 The SE126KG model should be used in plants using LPG. 

On the front plate the LED bar shows both the working condition and the gas concentration detected by the sensor. 
The  detector  is  supplied  with  two  alarm  levels  with  sealed-type  outputs  relays  and  with  tension-free  change  over 
contacts. Furthermore it has an auxiliary outputs relays in positive security for FAULT situation and an auxiliary input 
(

AUX

) connectable to 

our Manual NC Resetting valve with Positioning Sensor

Fig. 1

 shows a typical mains supply wiring diagram with alarm siren and normally closed solenoid valve. 

OPERATIONAL DESCRIPTION 

Preheating

: when the central unit is supplied, the yellow LED starts to flash and it means the sensor is heating. 

After 60 seconds, the green LED switches on and it means the normal working.   

NORMAL OPERATING

: the detector reads the gas concentration through the internal sensor 

1

st

 Red LED:

 

it illuminates if the gas concentration exceeds

 

5% LIE. 

2

nd

 Red LED (ALARM 1):

 

it illuminates if the gas concentration exceeds

 

10% LEL; if within 4 seconds the gas is 

not reduced, the 

PREAL.

 relay will activate. This relay is normally used as a prealarm using a siren (

SE301A). 

3

rd

 Red LED:

 

it switch on if the gas concentration exceeds

 

20% LEL; if the gas persists, the 4

th

 red LED 

ALARM 2

 

switches  on  within  30  seconds  and  the 

ALARM

  relay  will  activate.  It  is  normally  used to stop the gas through the 

manual reset solenoid valve (NO or NC) and/or the interruption of the electrical energy. 

If it has been installed a manual reset solenoid valve N.C. with magnetic sensor (mod. VR420÷VR480) connected to 

AUX

 input, in the case that the 

gas is still open, the yellow LED and the 

FAULT

 Relay will activate (see 

FAULTS

 section). 

RESET Key

:

 The alarm condition remains latched, LEDs and relays remain activated, even if the gas concentra-

tion is reduced, because the mounted valve is closed. To reset the normal working conditions and/or switch off the 
siren push the 

RESET

 key. 

Buzzer

:

 the 

PREAL.

 relay will be deactivated and the red LED flashes, only if the gas concentration is higher than 

10% of LEL. After 20 seconds, both of them will return in preallarm. (The siren rings) 

If it has been used a manual reset solenoid valve NC with the magnetic sensor  and in the case that it is snapped, the yellow LED will switch 
off and the 

FAULT

 relay will be deactivated. (See 

FAULTS

 section). 

Alarm

 

RESET:

 

The detector will begin to the normal working, only if the gas concentration is lower than 10% LEL, 

the 

ALARM

 relay will be deactivated and the 3

rd

 and 4

th

 red LED will switch off. If activated, the 

FAULT

 relay will be 

deactivated and the yellow LED will switch off. (see 

FAULTS

 sections). 

Warning

:

  Pushing  the 

RESET

 button, 

if the gas concentration is higher than F.S.

, it can happen that the first 

PREAL.

 relay will be deactivated and the first three red LEDs will switch off. The yellow LED will illuminate and the 

FAULT

  relay  will  activate.  A  fault  on  the  sensor  is  most  probable  in  this  case.  Eliminate  the  alarm’s  cause,  if  the 

condition persist pushing the 

RESET

 key, please consult the 

FAULTS

 section. 

FAULTS

: The detector signal different kind of failures activating the yellow LED and the 

FAULT

 relay. That is nor-

mally  activated.  The 

FAULT

  relay,  if  necessary,  can  be  used  both  to  signal  remotely  an  occurred  damage and to 

signal the absence of power to the instrument. 

Yellow and green LEDs and FAULT relay activate:

 

this happens when the catalytic sensor is not working. If this 

condition do not change, it will be necessary to replace the unit or to send it to the supplier back to repair.

 

Yellow, green, 4

th

 red LEDs, FAULT and ALARM relays activate:

 

(

ONLY

 after press 

RESET

 key) this happens 

when the catalytic sensor is not working or in few cases when there is a higher gas concentration. In this case the 
detector will remain in alarm, as described in the OPERATING>WARNING section. If there are not any gas leaks 
and the condition is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

Manual reset solenoid valve NC with magnetic sensor failure: 

this situation appears 

ONLY

 when is installed an electro 

valve with magnetic sensor; if it not close the gas, the 

ALARM

 relay will activate (gas concentration higher than 20% LIE) and the magnetic 

sensor signals to the central unit the this bad working. In this case all led will be lighted and relays will be activated. The failure condition (yel-
low led lighted and 

FAULT

 relay activated) will be cancelled if pressing the 

RESET

 key, the solution of the problem will be visualized. 

INSTALLATION 

The 

SE126K

 should be installed according to the national disposition in force on the matter.  

Model  SE126KM  positioning:

  Methane

  (CH

4

)  is  a  combustible  gas  lighter  than  air.  Its  density  related  to  air  is 

0.55; its LEL (

Lower Explosion Limit

) is 4.4% volume. 

The instrument should be fixed at 30 cm from the ceiling

 and be 

placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes. 

Model  SE126KG  positioning

:

  

LPG

 is a gas mixture composed by 20-30% Propane (C

3

H

8

) and by 70-80% Bu-

tane (C

4

H

10

). LPG calibration must be carried out with 

Butane

 which is a combustible gas heavier than air. Its den-

sity  related  to  air  is  2  and  its  LEL  (

Lower  Explosion  Limit

)  is  1.4%  volume. 

The instrument should be fixed at 30 cm. 

Summary of Contents for SE126K

Page 1: ...n de alarme 1 10 LIE LEL Intervención de alarma 2 2nd Alarm intervention Seuil d intervention de alarme 2 20 LIE LEL Contactos relé Contacts rating Contact relais 230Vac 3A SPDT Tiempo respuesta T90 Response Time T90 Temps de réponse T90 30 segundos seconds secondes Temperatura y humedad de funcionamiento Operation Temp Humidity Temp et humidité de fonctionnement 10 50 C 5 90 RH sin condensación n...

Page 2: ...n a la condición de prealarma Suena la sirena Si se ha usado una electroválvula de rearmado manual NC con sensor magnético y ha sido activada el LED amarillo se apagará y el relé FAULT se desactivará Véase la sección FALLOS Rearmado después de un alarma El detector volverá al funcionamiento normal solo si la concentración de gas es inferior al 10 LEL el relé ALARM se desactivará y los LEDs rojos 3...

Page 3: ...o ni en el interior de paredes o debajo del suelo Atención tener en cuenta que la vida útil del sensor puede verse reducida si se encuentra en entornos contaminados con presencia de vapores o agentes inflamables especialmente disolventes Algunas sustancias provocan una reducción permanente de la sensibilidad Evitar el contacto del sensor con vapores de compuestos de silicona pinturas y selladores ...

Page 4: ...ith the magnetic sensor and in the case that it is snapped the yellow LED will switch off and the FAULT relay will be deactivated See FAULTS section Alarm RESET The detector will begin to the normal working only if the gas concentration is lower than 10 LEL the ALARM relay will be deactivated and the 3 rd and 4 th red LED will switch off If activated the FAULT relay will be deactivated and the yel...

Page 5: ...nces cause a permanent reduction in sensitivity Avoid contacts of the sensor with vapours of Silicone compounds paintings and sealing paste Tetra ethyl Lead and Phosphate esters Some other substances produce a temporary loss of sensitivity These inhibitors include Hydrogen sulphide Chlorine Chlorinated hydrocarbons and halogenated compounds The sensitivity is recovered after a short period of runn...

Page 6: ... relais Dérangement se désactive Voir section relais Dérangement Réarmement après une d alarme L appareil revient au fonctionnement normal si la concentration de gaz est in férieure 10 de la LIE Le relais ALARME sera désactivé le 3 et 4 led rouge s étendent Si le relais Dérangement est activé il vient désactivé et le LED jaune s étende Voir section relais Dérangement Attention Apres avoir appuyé l...

Page 7: ... que le capteur vienne au contact de vapeurs de silicone plomb tetraethyl ou hydrocarbures chlo rés ces substances pouvant en réduire irréversiblement la sensibilité Le contact occasionnel avec des solvants type trichloréthylène ou tétrachlorure de carbone peuvent inhiber temporairement le capteur Après un bref temps en air pur le capteur reprend son fonctionnement normal VERIFICATIONS PERIODIQUES...

Page 8: ...C NA NC C NA NC C NA L N SE301A PREAL ALARM VR420 VR480 FAULT AUX Fig 4 Esquema con válvula de rearmado manual norm abierta Wiring diagram with a normally open manual resetting valve Schéma avec vanne à réarmement manuel norm ouverte 230Vca NC C NA NC C NA NC C NA L N SE301A PREAL ALARM Válvula NA NO Valve Vanne n o FAULT AUX Fig 3 Esquema con válvula de rearmado manual norm cerrada Wiring diagram...

Reviews: