Before carrying out this procedure, it is essential that the
technician is completely familiar with the equipment and all its
detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required
prior to re-use of reclaimed refrigerant. It is essential that
electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
•
mechanical handling equipment is available, if required, for
handling refrigerant cylinders;
•
all personal protective equipment is available and being used
correctly;
•
the recovery process is supervised at all times by a
competent person;
•
recovery equipment and cylinders conform to the appropriate
standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before
recovery takes place.
g) Start the recovery machine and operate in accordance with
manufacturer's instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid
charge).
i) Do not exceed the maximum working pressure of the cylinder,
even temporarily.
j) When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment are