5.2.4 Transport till its location
Equipment’s in case have four casters, in order to make easier their transport until their location.
Nevertheless, if the reception area is far from the installation place, it is recommended to move
the equipment by means of pallet jack or the suitable means evaluating the remoteness
between both points. If the distance is long, it is recommended to move the equipment packed
till the installation area and later on unpack it.
For models in cabinet, it is essential to move it with mechanical means till the final location.
5.2.5 Connections
This equipment is ready to be installed in mains with power distribution system R, Y, B
& N keeping in mind during the installation the features of the used system and the national
electrical system of the final country
The cross cable sections used to supply the equipment and loads, will be in accordance with the
power stated in the nameplate sticked in the equipment, respecting the Low Voltage Electro
technical Regulation or norms of the corresponding country.
The installation will be provided with input protections, RCB and circuit breakers sized to the
current stated in the nameplate of the equipment at least, and characteristic equal to the stated
figure in the «Recommended installation» document. For equipment’s connected to IT
distribution power system, the protection will be four poles in order to break the lines and
neutral in the same maneuvering. Overload condition is considered as a nonpermanent and
exceptional operating mode, so these currents will not be kept in mind when sizing the
protection.
The output protection will be a circuit breaker with the characteristic equal to the stated figure
in the «Recommended installation» document.
Depending on the model of the stabilizer, some control connections can be accessible from the
rear of the equipment. Nevertheless any power connection is protected by a cover and those
models in cabinet, it is needed to open the door too. When the corresponding tasks are finished,
the terminal cover will be put back together with their fixing screws and those models in cabinet
and front door, the door will be closed by means of the foreseen mechanisms.
It is recommended to use spade terminals in all the cables connected to terminals.
Check the correct torque of terminal screws.