ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 9 -
▪
The ABS Enclosure has two screws at the bottom to secure the lid to the back box. Loosen the two screws
and lift the lid upwards from the bottom to open the enclosure.
▪
The Weatherproof Enclosure is provided with a padlock assembly for securing the hinged door to the back
box. Lift the lever and turn it anti-clockwise to open the enclosure.
The chassis plate (fitted with the Main PCB) has pluggable connectors and a 90° swivel system to easily remove
the chassis plate and allow easy access to the batteries.
Figure 2
Installing the Enclosure
It is recommended that the chassis plate be removed from the enclosure before fitting the panel to the wall. To
remove the chassis:
▪
Unhook the chassis plate from the wing brackets and swivel 90° to slide into the vertical lock position as
shown in Figure 2.
▪
Unplug the 8-way connector feeding the 27.5 V DC supply to the Main PCB.
▪
Carefully remove the chassis from the rear enclosure by pulling it forward out of the vertical locking
position. Put in a safe place to prevent accidental damage.
NB:
Do not lift the chassis by holding onto any of the printed circuit cards. Hold the chassis by the metal
plate only.
NB:
Do not remove or tamper with the “DO NOT REMOVE” sticker to screw out the harness, this will void the
warranty. Unplug the harness only from the Main PCB and leave it connected to the PSU.
Firstly, remove the required knockouts for the installation wiring. There are sufficient knockouts on the top of the
ABS and Standard Enclosures for all installation wiring. In addition, there are knockouts at the top of the back
wall for rear entry cabling, if required.
The Weatherproof Enclosure has cable entry points at the bottom of the enclosure. Remove the rubber glands
to utilise the cable entry point. Cable entry should only be from the bottom through the provided points with
compression glands to ensure the integrity of the enclosure is maintained.
The ABS and Standard Enclosures each have three fixing points and the Weatherproof Enclosure has four
externally positioned fixing points.
The mounting holes and dimensions of the different enclosures are indicated as follows:
▪
Figure 3: ORYX202 & ORYX204 ABS Enclosure
▪
Figure 4: ORYX208 Standard Enclosure
▪
Figure 5: ORYX202 & ORYX204 Weatherproof Enclosure
▪
Figure 6: ORYX208 Weatherproof Enclosure
Use all mounting holes provided to ensure the panel is held securely to the wall.