ORYX202 ORYX204 ORYX208 Conventional Fire Panels
– INSTALLATION & OPERATION MANUAL
PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
- 48 -
◼
Normal Operating Range
Description
Measurement
Possible Cause
Action Required
Resistance
Voltage
Zone 1 Normal
2k4
Ω –
4k2
Ω
25.4 V DC
–
26.2 V DC
Correct EOL Used
No Action required.
Follow SANS10139 Commissioning and
Testing Guidelines to confirm system
operates as required.
Zone 2 Normal
25.6 V DC
–
26.6 V DC
(For IS Zone)
Zone 3 Normal
Zone 4 Normal
Zone 5 Normal
Zone 6 Normal
Zone 7 Normal
Zone 8 Normal
Input 1 Normal
2k4
Ω –
4k2
Ω
0.5 V DC
–
0.8 V DC
Input 2 Normal
Sounder 1 Normal
0.5 V DC
–
0.8 V DC
Sounder 2 Normal
6
WARRANTY
General Terms and Conditions are available from the Technoswitch website
Alternatively, please contact your local Sales Office for further information.
7
DISCLAIMER
Although the contents of our product literature have been prepared with the greatest care, Technoswitch can
accept no liability whatsoever for any direct or indirect damages of any kind that may arise due to either errors or
omissions in them, or amendments to products or other specifications following publication.
8
REVISION INFORMATION
Revision
Date Issued
Reason for Change
Reference
Rev 01.00
20210514
New Document
ECR-0092
Rev 01.01
20210707
Figure 15 updated. Document page numbering amended.
ECR-0108
Rev 01.02
20210907
Figure 7, Figure 8, Figure 23 & Specifications updated.
ECR-0111
Rev 02.00
20220224
Technical updates. Reference to ORYX Repeater range added.
DCR-0248