6
Hydraulic diagrams
Diagram 0: Heating circuit with up to 2 heat sources
A1 = (S4 > min1 ) & (Heating = active)
If no room sensor is used, the room influence
RI
in menu
MIXER
must be set to zero and the
sensor
S1
in the
SENSOR
menu set to
FIXED VALUE (e.g. 20°C)
.
Program 0:
Enabling of heating circuit pump
A1
, when the sensor
S4
has exceeded the
minimum threshold
min1
.
If the sensor
S4
is not used, then it must
not
be switched to
OFF
.
To avoid the display "
999
" it is possible to allocate the sensor
S4
in the menu
SENSOR
a
fixed temperature, which must be higher than
min1
.
All pr1:
As program 0 however the heating circuit pump
A1
is also enabled by
sensor
S5
and minimum threshold
min2
(2 generators for the heating circuit).
A1 = ((S4 > min1 ) or (S5 > min2)) & (Heating = active)
A1 off
S4 < min1
A1 on
Switch-off cond.
PUMP
A1 off
Required settings:
Basic control level
Time
Operating mode (preferably
AUTO
)
Set room temperature for lowering mode
RTL
Set room temperature for normal operation
RTN
Time program for normal operation
Parameter menu
Program number
PR
min1...
cylinder
S4
A1
(if heating circuit active)
min2 ...
see all pr 1
Heating curve
TEMP
or
R RISE
Flow maximum and minimum temp. (
PRE
max,
PRE
min)
Parameter frost protection mode (
OTF
,
RTF
)
Menu Men
MIXER
(Room influence etc.) and
PUMP
(Switch-off
conditions)
S5 for p1