65
Technical data
Power supply:
210 ... 250V~ 50-60 Hz
Power input:
max. 3 VA
Fuse:
3.15 A fast-acting ( output)
Supply cable:
3x 1mm² H05VV-F conforming to EN 60730-1
Case:
plastic: ABS, flame resistance: Class V0 to UL94 Norm
Protection rating:
II - safety insulated
Protection class:
IP40
Dimensions (W/H/D):
152x101x48 mm
Weight:
210
g
Allowed ambient temperature:
0 to 45° C
6 inputs:
6 inputs- optional for temperature sensor (KTY (2 k
), PT1000),
radiation sensor as digital input,
or as pulse input for volume flow encoder (only input 6)
3 outputs:
output
A1
.....
Triac
output (minimum load of 20W required)
output
A2 ..... Relay output
output
A3 ..... Relay output
Rated current load:
Output 1: max. 1.5 A ohmic inductive cos phi 0.6
Output 2 and 3: max. 2.5 A ohmic inductive cos phi 0.6
2 control outputs:
0 - 10V / 20mA switchable to PWM (10V / 500 Hz),
5 V DC / 10 mA or connection of the auxiliary relay HIREL-
STAG
Cylinder sensor BF:
diameter 6 mm incl. 2 m cable
BF
PT1000
–
to
90°C
continuous
load
BF KTY – to 90°C continuous load
Boiler sensor KE:
diameter 6 mm incl. 2 m cable
KE
PT1000 – to 160°C continuous load (momentary to 180°C)
KE KTY – to 160°C continuous load
The sensor lines on the inputs having a cross-section of 0.50 mm² can be extended
to a length of 50 m.
Consumers (e.g.: pumps, valves...) having a cable cross-section of 0.75 mm² can be con-
nected at a distance of up to 30 m.
Differential temperature:
adjustable from 0 to 99°C
Minimum threshold / Maximum threshold:
adjustable from -20 to 149°C
Temperature display:
-40 to 140°C
Resolution:
from -40 to 99.9°C in 0.1°C increments; from 100 to 140°C in 1°C increments
Accuracy:
Accuracy: type +-0.3%.
We reserve the right to make technical
changes.
© 2016