33
S2
S4
S3
A3
A1
S5
A2
A1
S1
Program 352 - Layered tank and burner requirement
Layered system only effective with speed control activated.
(Absolute value control system: AC N1)
No symbol for S3, S5
and heat exchanger
Program 352:
Solar pumps
A1
run when:
S1
is greater than the threshold
min1
and
S1
is greater than
S2
by the difference
diff1
and
S2
has not exceeded the threshold
max1
.
The three-way valve
A2
switches
to up
when:
S5
is greater than the threshold
min2
or
S5
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
Output
A3
switches on when
S4
falls below
min3
.
Output
A3
switches off (dominant) when
S3
exceeds
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3
(on)
=
S4
<
min3
A3 (off) = S3 > max3
Program 353:
If
S4
has reached
max2
, the quick warm-up phase has been completed, and
the speed control is thus blocked
optimal efficiency.
If PSC (pump speed control) is activated, the speed level is set to the maximum level, if
control output 1 is activated; the analog level for the maximum speed is output. Control
output 2 is not changed and continues control.
All pr4:
The burner requirement (
A3
) only occurs via sensor
S4
.
A3
(on)
=
S4
<
min3
A3 (off) = S4 > max3
(dominant)
All pr8:
If one of the two solar circuits is active the burner requirement will be
blocked. If the solar circuit switch off the burner requirement is released again with a switch
delay of 5 minutes.
Required settings:
max1
… limit TK
S2
A1
max2
… limit TK
S4
A2
max3
… burner req. off TK
S3
A3
min1
… switch-on temp. coll.
S1
A1
min2
… switch-on temp.ssl.
S5
A2
min3
… burner req. on TK
S4
A3
diff1
… coll.
S1
– TK
S2
A1
diff2
… supply l.
S5
– TK
S4
A2
S1
S5 S5
min1
<min2 >min2
A2
S2
S4 S4
max1
max2 max2
diff2
A2
diff1
A1
Burner
A3
S4 min3
S3 max3