Program 80 - Single solar power system and tank load from boiler
Program 80:
Pump
A1
runs when:
S1
is greater than the threshold
min1
and
S1
is greater than
S2
by the difference
diff1
and
S2
has not exceeded the threshold
max1
.
The feed pump
A2
runs when:
S3
is greater than the threshold
min2
and
S3
is greater than
S4
by the difference
diff2
and
S4
has not exceeded the threshold
max2
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S3 > (S4 + diff2) & S3 > min2 & S4 < max2