![Technibel K70P090Z Installation Instruction Download Page 7](http://html1.mh-extra.com/html/technibel/k70p090z/k70p090z_installation-instruction_1067671007.webp)
GB
7
10 - “SUMMER / WINTER” MODE SWITCHING LOGIC
10.1 - COOLING / HEATING SWITCHING
• Four logics are present to select the thermostat operating modes, Rhich are defined Rhen parameter “
P00
” is configured:
-
Local manual
: user choice made through the Cey
.
-
Remote manual
: depending on the Digital Input 1 status (contact logic: see configuration parameters of board).
-
Automatic
depending on
water
temperature (2-pipe).
Note:
in case of Rater sensor alarm, the controller returns to
the Local mode temporarily (manual).
-
Automatic
depending on
air
temperature (4-pipe):
Where
-
Set
is the set point programmed for the climate,
-
ZN
is the neutral zone (parameter
P03
).
Note
: the value displayed for parameter
P03
is to be
divided by 10.
• The thermostat operating mode is indicated on the display by
the symbols
(Cooling) and
(Heating).
17°C
28°C
Water
temperature
Summer
Winter
Set - ZN/2
Set + ZN/2
Set
Ambient air
temperature
Summer
Winter
11 - VENTILATION
11.1 - OPERATING SPEED SELECTION
• Using
Cey it is possible to select the folloRing speeds:
-
AUTO
Automatic fan speed
: depending on the set temperature and the room air temperature.
-
1
= loR speed.
-
2
= medium speed.
-
3
= maximum speed.
• Note:
In the case of fixed speed, the fan on/off logic Rill be equivalent to the automatic logic.
11.2 - ACTIVATION ACCORDING TO THE WATER TEMPERATURE (if sensor connected)
• Fan operation may be connected to the installationgs Rater temperature control. Based on the operation mode, different
heating or cooling thresholds Rill be enabled.
• The absence of this condition Rhen queried by the thermostat Rill cause the symbol of the mode currently active (
or
) to flash.
The enabling signal is ignored:
- Water sensor not provided (
P04
= 0) or in alarm status.
- In the cooling mode Rith 4-pipe configurations.
Ve
1
2
3
Set
Set + 0.5°C
Set + 2°C
Set + 3°C
Ve
1
2
3
Set
Set - 0.5°C
Set - 2°C
Set - 3°C
17°C
ON
OFF
22°C
ON
OFF
25°C
28°C
Air temperature
Air temperature
Air temperature
Air temperature
COOLING
HEATING
COOLING
HEATING