7 - BOARD CONFIGURATION
• The board can be configured according to the type of unit / system to be governed by changing some parameters.
7.1 - PARAMETER LIST (accessible at level 2)
•
P00
= controller configuration (see “Available configurations”) to select the type of unit to be governed.
Note: to configure in first before modifying the other parameters.
•
P01
= type of controller installation (built-in or remote-controlled air sensor):
- 000
: on the unit - provide for an “SA” air sensor (as an accessory),
- 001
: Rall mounted - do not connect the air sensor.
•
P02
= (not used). Leave the value at:
000
.
•
P03
= neutral zone (20-50°C / 10); parameter used in case of configurations Rith automatic Cooling / Heating
changeover according to air temperature.
•
P04
= Rater sensor:
- 000
: not available,
- 001
: available provided (mandatory for 2-pipe C heating element).
Based on the set value, the sensor alarm and the heating element functions Rill be controlled.
•
P05
= use logic - Digital input 1 for Cooling / Heating sRitching:
- 000
: (open / closed) = (Cooling / Heating),
- 001
(open / closed) = (Heating / Cooling).
•
P06
= use logic - Digital input 2 for
On/Off
sRitching:
- 000
: (open / closed) = (
On/Off
),
- 001
: (open / closed) = (
Off/On
).
8 - PARAMETER CONFIGURATION PROCEDURE
• Set the thermostat to
OFF
.
• Push the
Ceys at the same time.
• Use the Ceys
to modify the value on the display to
the passRord value (PW) =
10
, then validate by pressing
.
• If correct, you Rill be able to access the level 2 parameters.
• Use Ceys
to scroll the various parameters
(
P00
to
P06
: see list above).
• Press
to confirm the parameter change (the value Rill
start flashing).
• Use the Ceys
to modify the initial value.
• Press
to save the neR value setting or
to cancel
the modification.
• After completing the modification of the parameters
concerned press Cey
to exit the procedure.
Note:
The duration of the parameterisation is limited over time.
Once a certain time has elapsed (around 2 minutes) the
thermostat Rill sRitch bacC into the
OFF
status and only the
saved changes Rill be retained.
User level indicator
001
= PassRord entry (
PW
)
Level indicator:
003
= Parameter value
modification
Level indicator:
002
= Access to
parameters
Value of
selected
parameter
Selected
parameter:
P00
to
P06