Control unit

With built-in ambient temperature sensor.
To be installed in zone 1.

Load 

shedding

(if any)

Outside air

temperature

Installation

water outlet

temperature

Installation

water return
temperature

Control by pilot wire for 2

nd 

zone (if any) with electric convectors.

Application: 1 FLOOR ZONE or
1 TERMINAL UNIT ZONE or 1 RADIATORS ZONE.

ECO signal to remote controls.
For the terminal unit zone.
Application: 1 TERMINAL UNIT ZONE or 2 MIXED ZONES.

BUS connection:
• towards M2Z 2 zones module for application: 2 FLOOR ZONES or 2 MIXED ZONES.
• towards DHW preparation tank for application: 1 RADIATORS ZONE WITH DHW.

1 FLOOR ZONE WITH DHW.

Possible
connections to be
made depending on
the applications

PhRIe

System board 

A1

Control board

A2

Power board

A3

Communication line (BUs)

- 2-conductor shielded cable, minimum size 1 mm

2

with grounded shielding on heat pump side (*).

-

Total

length of the BUS connection: 40 meters (control unit conne 2-zone module, if any or DHW preparation

kit, if any ).

- To be connected to the (

+

) and (

-

) terminals if terminal strip.

(*) Refer to the ground shielding principle in paragraph 6.4.

Outside temperature sensor

- 2-conductor cable, min. size 0.5 mm

2

.

- Maximum length 25 meters.
- To be connected to the (

s13-1

) and (

s13-2

) terminals if terminal strip.

-

Note

:

This sensor must be located outside in a location that is representative of the temperature to be measured (on a wall facing
North  /  North-west)  and  located  away  from  parasitic  heat  sources  (chimney,  thermal  bridge,  etc..)  and  sheltered  from
inclement weather (under a roof overhand, for example). See paragraph 5.2.

electric support heater load shedding signal (if any)

- Two possibilities:

1) By a "remote info" signal coming from the electrical utility meter: 1 twisted pair (6/10) cable with shielding (shielding

grounded on heat pump side).

2) By a good quality, potential-free external contact.

- Contact closed = load shedding of the electric support heater.
- 2-conductor cable, min. size 0.5mm

2

.

- Maximum length 25 meters.

- To be connected to the system board 

A1.

eCO signal for remote controls (if any)

- In  order  to  send  reduced  mode  orders  (

eco

or 

standby

)  to  the  terminal  unit  remote  control  units  in  the  case  of

applications such as 1 terminal unit zone or 2 mixed zones.

- In the form of a potential-free contact which can used in VLV (Very Low Voltage), 2A max.
- To be connected to the system board 

A1

.

- Note:

The contact can control up to 10 

RCC10

(

70250051

) or 

RCC20

(

70250052

) type controls.

Consult the terminal unit and remote control documentation to connect this contact.

B

C

D

e

Summary of Contents for K 60 D 070 Z

Page 1: ...iNveRteR avec chaUFFaGe d appoiNt LectRiqUe system coNtRoL kit FoR iNveRteR heat pUmp with eLectRic sUppoRt heateR Mai 2013 10 11 566 F GB 02 k 60 d 070 z F GB Notice d iNstaLLatioN iNstaLLatioN iNstR...

Page 2: ...rials and components which can be recycled and reused At end of livetime it should be eliminated separately from your household waste Please dispose of this equipment at your local community waste col...

Page 3: ...Priority is given to thermodynamic heating See operating details in the technical control file supplied with this kit The system control kit K60D070Z is appropriate for standard applications using he...

Page 4: ...ves or behind curtains near sources or heat or directly exposed to sunlight The unit should be installed approximately 1 5 m above the floor Open the unit by removing the lower screw and secure the ba...

Page 5: ...min size 0 5 mm2 Maximum length 25 meters To be connected to the s13 1 and s13 2 terminals if terminal strip Note This sensor must be located outside in a location that is representative of the temper...

Page 6: ...1 Note The electrical power supplied to the convectors must be the same as that of the heat pump 6 2 heAT PUMP CONNeCTION DIAGRAM Route the pilot wire 230 V separately from the other control connectio...

Page 7: ...routed near 230 VAC cables Particular attention should be paid to the 230 VAC pilot wire Electrical connection conduits must be fixed ROUTING Of heAT PUMP CABles Route the cables through the cable gla...

Page 8: ...Due to our policy of continuous development our products are liable to modification without notice Z I Route d partementale 28 CS 40131 Reyrieux 01601 TR voux Cedex FRanCe T l 04 74 00 92 92 Fax 04 74...

Reviews: