7. FUNCTION
7-1. Room Temperature Control
●
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
●
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the
controller in the indoor unit.
●
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least
3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant
pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
●
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor
operation.
●
Thermo. ON : When the room temperature is above T + 1°C (T°C is set temperature).
Compressor
➞
ON
●
Thermo. OFF : When the room temperature is equal to or below set temperature T°C.
Compressor
➞
OFF
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
5 minutes
ON OFF
ON OFF
ON OFF
Compressor
ON OFF
ON OFF
ON OFF
More than
5 minutes
Outdoor fan
Indoor fan
Set speed
T+1
°
C
T
°
C
set temp.
Thermo.
OFF
Thermo.
OFF
Thermo.
ON
Thermo.
OFF
Thermo.
ON
Thermo.
ON
Thermo.
ON
Room temp.
Signal from remote control unit
34