5-14 Contacts for Building Automation
5-14.1 Input Contact (J4 - green)
The status of this input affects system operation according to the following:
Contact
OPEN
: system does not operate (always OFF)
– inputs from wireless remote controller are not processed
Contact
CLOSED
: system operates in the normal way according
to the inputs coming from wireless remote controller
5-14.2 Output Contact (J12)
This connector is directly tied to the contact (normally open) of a power relay which activates every time
the following alarm condition occur:
•
RAT damaged
•
ICT damaged
In this case when alarm happens, on poles 1 and 3 of J12 connector, 220 VAC-50Hz are available.
Max electrical load:
1A- 240VAC
1