5-7 Forced Mode
In this mode the system operates (COOLING or HEATING mode – fixed settings) or is switched off by
means of the MODE button of the indoor unit control board. The operation modes can be selected
pressing the button in a cyclic way (OFF
Ö
COOL
Ö
HEAT
Ö
OFF…). The settings are:
COOLING mode
SET POINT temperature = 25°C
FAN SPEED = HIGH
HEATING mode
SET POINT temperature = 21°C
FAN SPEED = HIGH
5-8 Protection operations in Cool and Dry Mode
8.1 Freeze-up
This protection prevents ice formation on the indoor coil heat exchanger. The protection is activated by
the indoor coil temperature (ICT sensor) and only after 6 minutes of compressor operation. This
protection acts in 2 levels:
LEVEL 1
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: ON
OUTDOOR FAN: cycling (30 seconds ON
B
30 seconds OFF).
LEVEL 2
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: OFF for at least 6 minutes and until ICT
≥
8°C
OUTDOOR FAN: OFF for at least 6 minutes and until ICT
≥
8°C
The system exit this protection routine when ICT temperature rises above 8°C.
19
Summary of Contents for 38.7104.070
Page 9: ...2 DIMENSIONAL DATA 9...
Page 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams HEAT PUMP MODELS COOLING MODELS 13...
Page 14: ...4 2 Wiring System Diagram HEAT PUMP MODELS COOLING MODELS 14...
Page 29: ...6 5 Some Parts of the Air Conditioner Do Not Operate 5...
Page 30: ...6 6 Air Conditioner Operates But Abnormalities Are Observed 6...
Page 31: ...7...
Page 32: ...6 7 Poor Cooling or Heating 8...
Page 33: ...6 8 Excessive Cooling or Heating 6 9 A Sensor is Defective 9...