5-4 Dry Mode Operation
Dry operation remove moisture from indoor air running, in cooling mode, at a low level without
reducing the ambient temperature.
This is done cycling ON and OFF indoor and outdoor units according to below.
ROOM
DRY LEVEL
TEMP
≥
SPT+2°C
LEVEL 0
Operation according to COOLING mode
CM on
< SPT+2°C
LEVEL 1
FMO on
≥
SPT-1°C
FMI switches between L and off (30 seconds)
RV off
CM switches 9 minutes off and 3 minutes on
< SPT-1°C
LEVEL 2
FMO switches 9 minutes off and 3 minutes ON
≥
15°C
FMI switches off and L during CM operation
RV off
CM off
< 15°C
DRY OFF ZONE
FMO off
FMI off
RV off
SPT = Set Point Temperature
5-5 Fan Mode Operation
With this mode, the indoor fan is turned on while CM, FMO and RV stay off all the time.
The user can select between 3 speeds: HIGH, MEDIUM and LOW.
5-6 Auto Fan speed
With this option selected, the indoor fan speed changes automatically according to
the difference between the detected air temperature (RAT sensor) and the set point (SPT):
COOLING MODE
2
≤
(RAT – SPT):
HIGH speed
1
≤
(RAT – SPT)
<
2:
MEDIUM speed
(RAT – SPT)
<
1:
LOW speed
HEATING MODE
2
≤
(SPT - RAT):
HIGH speed
(SPT - RAT)
<
2:
MEDIUM speed
NOTE
SPT = Set Point Temperature
18
Summary of Contents for 38.7104.070
Page 9: ...2 DIMENSIONAL DATA 9...
Page 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams HEAT PUMP MODELS COOLING MODELS 13...
Page 14: ...4 2 Wiring System Diagram HEAT PUMP MODELS COOLING MODELS 14...
Page 29: ...6 5 Some Parts of the Air Conditioner Do Not Operate 5...
Page 30: ...6 6 Air Conditioner Operates But Abnormalities Are Observed 6...
Page 31: ...7...
Page 32: ...6 7 Poor Cooling or Heating 8...
Page 33: ...6 8 Excessive Cooling or Heating 6 9 A Sensor is Defective 9...