37.4163.271.
1
0
1
/200
6
EG
I
F
D
E
INSTALLATION INSTRUCTIONS
- Cassette split units -
FULL SCALE
1
DIAGRAM
*
Available only for heat pump models.
**
Available only for CAF94-124
DRAIN
1
ELBOW
*
ACCESSORIES SUPPLIED WITH THE UNIT
PARTS
FIGURE
Q.TY
PARTS
FIGURE
Q.TY
4
SCREW M5 X 30
REMOTE
1
CONTROL UNIT
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits ø 5
1
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for reburring)
16. Hex. key
Tools required for installation (not supplied)
DECLARATION OF CONFORMITY
This product is marked as it satisfies Directives:
– Low voltage no. 73/23 EEC and 93/68 EEC.
– Electromagnetic compatibility no. 89/336 ECC, 92/31 EEC and 93/68 EEC.
This declaration will become void in case of misuse and/or non observance though partial of manufacturer's installation and/or
operating instructions.
OPERATING LIMITS
Cooling Maximum conditions
Outdoor temperature :
46°C D.B.
Room temperature
:
32°C D.B. / 23°C W.B.
Cooling Minimum conditions
Outdoor temperature :
19°C D.B.
Room temperature
:
19°C D.B. / 14°C W.B.
Heating Maximum conditions
Outdoor temperature :
24°C D.B. / 18°C W.B.
Room temperature
:
27°C D.B.
Heating Minimum conditions
Outdoor temperature :
–8°C D.B. / –9°C W.B.
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Units
Outdoor Units
CAF94R5TA-
GRF94C5TA-
GRF95L5TA-
GRF94R5TA-
CAF124R5TA-
GRF124C5TA-
GRF125L5TA-
GRF124R5TA-
CAF185R5TA-
GRF185C5TA-
GRF185C7TA-
GRF185L5TA-
GRF185L7TA-
GRF185R5TA-
GRF185R7TA-
TWIN WIRE CABLE
1
**
MOUNTING PADS
4
Power Supply:
5:
220 - 240 V ~ 50 Hz /
7:
380-400 V - 3N ~ 50 Hz