6.1.4 Alarm Monitoring Configuration
Monitoring Function ON / OFF
In Configuration section on Modules page, click Alarm Control to Enable/Disable Monitoring Function.
Temperature, +12V, +5V Voltage Alarm Levels Management
By default, temperature, +12 V, +5 V, - 5V voltage alarms are all set to ON. The check box ☑ as shown in
Figure 6-4
controls the detection is set to ON or OFF. When the check box is checked (detection ON), the text in the text box will be
solid black. The parameters cannot be changed. The parameters instruction is shown in
Figure 6-4, Table 6-1 below.
Figure 6.4
Table 6 1 Modules Page Alarms Threshold Parameters Instruction
Parameter
Units
HIHI
HI
Normal
LO
LOLO
DeadBand
Threshold
changeable
by user
Default
Alarm
Enable
Temperature
oC
70
65
-
0
-5
2
N
ON
+12V Input voltage
Vdc
13,5
-
12
-
10,5
0,2
N
ON
+5V Input voltage
Vdc
6
-
5
-
4,4
0,1
N
ON
-5V Input voltage
Vdc
-4,4
-
5
-
-6
0,1
N
ON