Visual inspection
Please check here
• whether the smoke detectors are still attached to the ceiling.
• whether the casing is damaged.
• whether fire smoke can reach the smoke detectors unhindered.
This can be hindered, for example, by the later installation of room
partitions or very high cupboards or shelves.
The minimum gap to walls, items of furniture etc. must be 60 cm.
• whether the individual rooms are used differently.
Minimum equip-
ping:
in bedrooms, children’s rooms and hallways which serve as
escape routes.
• whether smoke detectors are very dusty or, for example, are heavily
soiled by cobwebs. The smoke inlets (grey grating) must be free.
• whether fluorescent tubes, fireplaces, stoves, air-conditioning and/or
ventilation devices have been installed later in the vicinity of the
smoke detectors.
In case of variances, please refer as fast as possible to the
Techem Hotline: 0
18
02/00
12
64
(6 cents / call from German landlines, max. 42 cents / minute from
German mobile phones).
Techem radio frequency smoke detector 2 – operating instructions
20
Summary of Contents for smoke detector 2
Page 30: ...2 Te chem 2 Techem 2 30...
Page 31: ...2 Techem 2 Techem Techem 2 31...
Page 32: ...1 1 2 15 2 15 32 Techem 2...
Page 33: ...Techem 33 Techem 2...
Page 34: ...1 1 2 Techem 0 18 02 00 12 64 6 42 34 Techem 2...
Page 35: ...60 Techem 0 18 02 00 12 64 6 42 35 Techem 2...
Page 36: ...1 2 3 4 2 Techem 36 Techem 2...
Page 37: ...60 10 Techem 0 18 02 00 12 64 6 42 37 Techem 2...
Page 38: ...2 10 2 30 3 2 30 3 1 38 Techem 2...
Page 39: ...Techem 0 18 02 00 12 64 6 42 3 5 1 5 39 Techem 2...
Page 40: ...3 1 5 3 1 60 40 Techem 2...
Page 41: ...60 868 Techem data III Techem Smart 41 Techem 2 60 cm...
Page 42: ...60 85 A 75 A 75 A 42 Techem 2...
Page 43: ...43 Techem 2 3 15 10 1 30 6 60 2 DIN EN 14604 CE 1772 CPD 100459...