19
MODE 2
– the user sets the temperature deviations for all working days (Monday‐Friday) and for the
weekend (Saturday‐Sunday) separately.
Configuring mode 2:
Select: Set mode 2.
Select the part of the week to be edited.
Follow the same procedure as in the case of Mode 1.
Example:
Hour
Temperature ‐
weekly control
setting
(+/‐)
Monday ‐ Friday
PRE‐SET
4
00
‐ 7
00
+5
°
C
7
00
‐ 14
00
‐10
°
C
17
00
‐ 22
00
+7
°
C
Saturday ‐ Sunday
PRE‐SET
6
00
‐ 9
00
+5
°
C
17
00
‐ 22
00
+7
°
C
If
the
pre‐set
CH
boiler
temperature
is
50°C,
from
Monday
to
Friday
between
4
00
and 7
00
the CH boiler will increase by 5°C to reach 55°C; between 7
00
and 14
00
it will drop by 10°C, to reach 40°C, and
between 17
00
and 22
00
it will increase to reach 57°C.
Th the weekend, between 6
00
and 9
00
the temperature will increase by 5°C to reach 55°C, and between 17
00
and
22
00
it will increase to reach 57°C.
DHW operation schedule
This function enables the user to configure the periods of DHW tank activity on particular days of the week,
with the accuracy of 30 minutes.
4.3.6.1 CH boiler schedule, page: 17
4.3.7
Operation modes
MAIN MENU
OPE
RATION
MODES
House heating
Water tank priority
Parallel pumps
Summer mode
In this function the user activates one of the operation mode,s depending on current needs.
House heating
When this function is selected, only the house is heated. CH pump is activated when the temperature is above
the pump activation threshold. Below this temperature value (minus hysteresis) the pump is disabled.