5.

HART COMMUNICATION 

 
The CH420R transmitters have a HART communication MODEM 
The details of the characteristics with respect to the HART communication are available in the 
appropriate Field Device Specification  
 
Resume of the principal communications characteristics: 

Manufacturer, Model and Revision 

Tecfluid S.A.,  CH420R, Rev. 0 

Device type 

Transmitter 

Hart Revision  

6.0 

Device Description available 

No 

Number and type of sensors 

1, external  

Number and type of actuators 

Number and type of host side signals 

1, 4 – 20 mA analog 

Number of Device Variables 

Number of Dynamic Variables 

Mappable Dynamic Variables 

No 

Number of Common Practice Commands 

13 

Number of Device Specific Commands 

Bits of Additional Device Status 

12 

Alternative operating modes? 

No 

Burst mode? 

No 

Write Protection? 

Yes 

 
Analog loop electrical characteristics for communications :  
             Reception Impedance : 
                                        Rx          >           8,5 M

 

                                        Cx          <           200 pF 
 

4.

PUSH BUTTON INHIBIT AND “WRITE PROTECT”. 

 

The transmitter has a jumper situated behind the PCB at the top left corner, which can be used to 
avoid changes in the configuration. When the jumper is removed, the push buttons are disabled 
and the HART write protect is activated, thus inhibiting any changes in the configuration. 
To gain access, remove the left hand side  cover. 

Summary of Contents for CP420R

Page 1: ...Programmable flow rate transmitter CP420R CH420R Instructions Manual R MI CH420R Rev 0 English version...

Page 2: ...There are three push buttons with the following functions 2 1 Programming In all the programming screens the RESET push button exits the screen without saving the data in the memory even if changes in...

Page 3: ...rogramming In the first screen we program the flow rate equivalent to 4 mA lower range The measuring units will be the ones chosen in the previous screen The push buttons have the same function as the...

Page 4: ...in the instrument Example 1 Shortage of volume If we have a flow meter body which specifies i l 1 985 and when we check the volume of a batch we find that instead of having 100 litres as programmed we...

Page 5: ...er of Device Variables 2 Number of Dynamic Variables 1 Mappable Dynamic Variables No Number of Common Practice Commands 13 Number of Device Specific Commands 2 Bits of Additional Device Status 12 Alte...

Page 6: ...digits 7 Size of the digit 8 mm Reset By means of push button 8 3 Flow rate Indication N of digits 5 Size of the digit 5 mm 8 4 General characteristics Ingress protection IP40 Ambient temperature rang...

Page 7: ...imum input frequency is 0 06 Hz 8 6 2 Turbine If the Pulse input is configured for Turbine jumpers in position 1 2 a coil of a magnetic pick up can be connected between terminals 1 2 The input impedan...

Page 8: ...specified in the order the result of service or modification by un authorized persons bad handling or accident This warranty is limited to cover the repair or replacement defective parts which have no...

Reviews: