background image

Important Installation Notes for Air

Seal

Ambient

Air

Path

Enclosure

Internal Air

Path

Mounting Styles:

Vertical (Side/Front/Back) Mounting:

Condensate Removal System:

Top Mounting:

Maintenance:

Cautions:

Notes on condensation:

Both ‘thru mount’ and ‘flush mount’ units can be

positioned in any orientation and on any enclosure surface. It is important
to consider interior air flow patterns when determining the mounting
location. Also of importance is an unrestricted flow of ambient air thru
the hot side heat exchanger. Ease of access and inspection must
be considered for those applications in particularly severe
environments which may require occasional maintenance.

Vertical mounting refers to the vertical direction of the cold
side or interior fins and is recommended for applications with
high humidity, poor and incomplete cabinet seals or any
condition which may cause the cold side fins to be maintained
at temperatures below the dew point for long periods of time
allowing for the formation of condensation. The vertical fin
direction provides a drip path whereupon condensation can be
collected via a moisture removal system (standard on FHP-
units) or a drip pan positioned below the cold side fins. Drip pans are
optional for thru mount units.

All FHP-Series and AHP-1400 air conditioners contain a built-in condensate removal system. The condensate kit
consists of a antifungal sponge with a condensate wick. PVC tubing is also provided for drainage. Drip pans are
optional for thru mount units which must be evaluated on an individual basis. Equations defining a relationship between
the cold side fin and enclosure temperatures are provided to assist in the evaluation.

Though often the easiest location to mount it is often the most difficult to protect from condensation in this orientation
due to the fin orientation, gravity and any susceptible components below. If a drip pan is employed by the end user use
caution to place the pan far enough away from the internal fan to minimize the restriction of air flow. The pan should
cover the fin ends as well as the fan area. When there is a choice, the vertical orientation is preferred by most
users.

Since the technology is solid-state, there are no filters, compressors, or fluorocarbons to maintain. The only moving
parts are the fans.

It is recommended for harsh or dirty environments that the heat sinks be cleaned from time to

time. This can be accomplished by directing compressed air over the external fins or on NEMA 4 versions by hosing
the unit down. This will increase the overall life and performance of the system.

Take care when mounting not to damage the seal between the hot and cold side sinks. Do not attempt to mount a unit
to a warped surface or try to make the units mounting surface conform to an unflat surface. Do not pinch or damage
any leads when mounting. Do not over tighten any installation screw, use reasonable force. Always mount with any
condensate drain down. Do not compress the cold side between the hot side and any other surface. Do not obstruct
the airflow on either side. When mounting consider the natural air flows of the enclosure. Connect power only after the
installation is complete.

Condensation occurs at the cold side fins when the surface temperature goes below the dew point. To reduce or
remove condensate, consider the following:
• Regulate the Fin Temperature above the Dewpoint.
• Keep Enclosure Closed and Sealed from Outside Humidity.
• Use Desiccant (Moisture absorbing Granules.)
• Employ Condensate Removal System/Drip Pans.

If you have any questions regarding your installation, Please feel free to contact our technical department for assistance
at 773-342-4900.

Summary of Contents for 0-2171-0-000

Page 1: ...tallation Only qualified technicians should install this equipment If you have any questions regarding your equipment please do not hesitate to call us at 773 342 4900 and we will be happy to assist you We are open from 8 00 am 4 30 pm Central Time Included in this packet you will find Installation Notes for Air Conditioners Product Literature and Specifications Assembly Drawing SK050532 Wiring Dr...

Page 2: ...ften the most difficult to protect from condensation in this orientation due to the fin orientation gravity and any susceptible components below If a drip pan is employed by the end user use caution to place the pan far enough away from the internal fan to minimize the restriction of air flow The pan should cover the fin ends as well as the fan area When there is a choice the vertical orientation ...

Page 3: ...240 8 0 5 0 EXT 40 65 10 60 Wick UL1995 CSA22 2 AHP 1501HC 0 2131 1 000 1000 1100 120 240 8 0 5 0 TC 3F 40 65 10 60 Wick UL1995 CSA22 2 AHP 1501HC 0 2151 1 000 1000 1100 120 240 8 0 5 0 EXT 40 65 10 60 Wick UL1995 CSA22 2 AHP 1501XE 0 2181 4 000 1000 1100 120 240 8 0 5 0 TC 6F 40 65 10 60 Wick UL1995 CSA22 2 AHP 1501XE 0 21F1 4 000 1000 1100 120 240 8 0 5 0 85 F 30 C 40 65 10 60 Wick UL1995 CSA22 ...

Page 4: ...y 136x 42 6 Cold Sink y 10x 38 4 y 10x 40 5 y 10x 42 6 AHP 1501 DIMENSIONS MOUNTING STYLE Thru Mount ENVIRONMENTS SERVED NEMA 12 IP 52 NEMA 4 IP 56 RATING TRADITIONAL 1000 BTU hr 0 F T 1300 BTU hr 20 F T RATING DIN 3168 300 Watts L35 L35 187 Watts L35 L50 See page 10 AHP 1501 Air Conditioner Air Cooled Air Flow Pattern catalog 2011 working on qxp 6 28 2011 2 00 PM Page 27 ...

Page 5: ...55 116 5 52 140 8 X 10 32 Mounting taps 4 X 6 32 Mounting taps optional 15 05 382 4 59 117 4 57 116 11 99 305 Input Power Cord Temperature adjustment Circuit Breakers Notes Dimensions Inches Millimeters Dimensions do not include hardware ...

Page 6: ......

Page 7: ...ilisé par des personnes enfants compris dont les capacités physiques sensorielles ou mentales ou le manque d expérience et de connaissances à moins qu ils aient été donnés de surveillance ou d instructions concernant l utilisation de l appareil par une personne responsable de leur sécurité Les enfants doivent être surveillés afin de s assurer qu ils ne jouent pas avec l appareil Achtung Wenn das N...

Page 8: ...rates the same technology as the TC 6F It contains a single setting each for both heating and cooling as referenced below TC 1C AND TC 1H POWER TEMPERATURE SWITCHES Models TC 1C and TC 1H power temperature controllers with their small tolerance and reset differential are the simplest and most cost effective way to control a cooling or heating device VAC or VDC without a need for a relay For circui...

Page 9: ...ree of charge to Buyer or credit to buyer the price of the defective products ALL OTHER WARRANTIES EXPRESS OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IN NO EVENT SHALL TECA BE LIABLE FOR ANY CLAIM BASED UPON BREACH OF EXPRESS OR IMPLIED WARRANTY OR ANY OTHER DAMAGES WHETHER SPECIAL INDIRECT INCIDENTAL CONSEQUE...

Reviews: