Important Installation Notes for Air Conditioners

Seal

Ambient

Air

Path

Enclosure

Internal Air

Path

Mounting Styles:

Vertical (Side/Front/Back) Mounting:

Condensate Removal System:

Top Mounting:

Maintenance:

Cautions:

Notes on condensation:

Both ‘thru mount’ and ‘flush mount’ units can be positioned in

any orientation and on any enclosure surface. It is important to consider interior
air flow patterns when determining the mounting location. Also of importance
is an unrestricted flow of ambient air thru the hot side heat exchanger. Ease
of access and inspection must be considered for those applications in
particularly severe environments which may require occasional
maintenance.

Vertical mounting refers to the vertical direction of the cold side
or interior fins and is recommended for applications with high
humidity, poor and incomplete cabinet seals or any condition which
may cause the cold side fins to be maintained at temperatures
below the dew point for long periods of time allowing for the
formation of condensation. The vertical fin direction provides a drip
path whereupon condensation can be collected via a moisture
removal system (standard on FHP-units) or a drip pan positioned
below the cold side fins. Drip pans are optional for thru mount units.

All FHP-Series and AHP-1400 air conditioners contain a built-in condensate removal system. The condensate kit consists of a
antifungal sponge with a condensate wick. PVC tubing is also provided for drainage. Drip pans are optional for thru mount units
which must be evaluated on an individual basis. Equations defining a relationship between the cold side fin and enclosure
temperatures are provided to assist in the evaluation.

Though often the easiest location to mount it is often the most difficult to protect from condensation in this orientation due to the
fin orientation, gravity and any susceptible components below. If a drip pan is employed by the end user use caution to place
the pan far enough away from the internal fan to minimize the restriction of air flow. The pan should cover the fin ends as well as
the fan area. When there is a choice, the vertical orientation is preferred by most users.

Since the technology is solid-state, there are no filters, compressors, or fluorocarbons to maintain. The only moving parts are
the fans.

It is recommended for harsh or dirty environments that the heat sinks be cleaned from time to time. This can be

accomplished by directing compressed air over the external fins or on NEMA 4 versions by hosing the unit down. This will
increase the overall life and performance of the system.

Take care when mounting not to damage the seal between the hot and cold side sinks. Do not attempt to mount a unit to a
warped surface or try to make the units mounting surface conform to an unflat surface. Do not pinch or damage any leads when
mounting. Do not over tighten any installation screw, use reasonable force. Always mount with any condensate drain down.
Do not compress the cold side between the hot side and any other surface. Do not obstruct the airflow on either side. When
mounting consider the natural air flows of the enclosure. Connect power only after the installation is complete.

Condensation occurs at the cold side fins when the surface temperature goes below the dew point. To reduce or remove
condensate, consider the following:
• Regulate the Fin Temperature above the Dewpoint.
• Keep Enclosure Closed and Sealed from Outside Humidity.
• Use Desiccant (Moisture absorbing Granules.)
• Employ Condensate Removal System/Drip Pans.

If you have any questions regarding your installation, Please feel free to contact our technical department for assistance at 773-
342-4900.

Summary of Contents for 0-0135-1-000

Page 1: ...efully before installation Only qualified technicians should install this equipment If you have any questions regarding your equipment please do not hesitate to call us at 773 342 4900 and we will be...

Page 2: ...is often the most difficult to protect from condensation in this orientation due to the fin orientation gravity and any susceptible components below If a drip pan is employed by the end user use caut...

Page 3: ...n Integral temperature controller Operating ambient temperature range 40 65 C Operating enclosure temperature range 10 60 C Weight 55 LBS CONTROL TEMPERATURES INCLUDES Temperature controller Mounting...

Page 4: ...YLE Through Mounted ENVIRONMENTS SERVED NEMA 12 IP 52 NEMA 4 4X IP 56 RATING TRADITIONAL 1100 BTU hr 0 F T 1420 BTU hr 20 F T RATING DIN 3168 322 Watts L35 L35 210 Watts L35 L50 AHP 1800 DIMENSIONS Ai...

Page 5: ......

Page 6: ...H S FAN H S FAN TE TE TE C S FAN 1 2 TE TE TE TE TE TE 1 2 6 4 3 5 7 8 6 5 4 3 8 7 250 VDC Input TE TE TE TE TE TE TE TE TE TE TE TE TE TE TE 13469 10 F 1N4148 C S FAN...

Page 7: ...re utilis par des personnes enfants compris dont les capacit s physiques sensorielles ou mentales ou le manque d exp rience et de connaissances moins qu ils aient t donn s de surveillance ou d instruc...

Page 8: ...d most cost effective way to control a cooling or heating device VAC or VDC without a need for a relay For circuits that have higher current draw simply use them in conjunction with a solid state rela...

Page 9: ...ee of charge to Buyer or credit to buyer the price of the defective products ALL OTHER WARRANTIES EXPRESS OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY...

Reviews: