3
4. With the fan inlet still covered, touch Set Baseline to initiate the building baseline
measurement procedure on Channel A.
5. During a baseline measurement, Channel A will display a long-term average
baseline pressure reading while Channel B is used as a timer in seconds to
show the elapsed measurement time. When you are satisfied with the baseline
measurement, touch enter and enter the baseline reading into the gauge.
6. Channel A will now display the baseline adjusted building pressure value.
7.
Remove the No-Flow Plate from the Blower Door fan and install the flow ring
which you think best matches the needed fan flow (see table below.)
8.
Check (and adjust if necessary) the selected test device (i.e. fan) and configuration (i.e. flow ring) shown in the Gauge app to
match the fan and flow ring being used in the test.
9. Turn on the blower door fan.
Using Cruise Control
1. Turn the blower door speed control knob to the “just on” position (the controller is
on but turned all the way down).
2. Set the cruise target by touching the Cruise menu and selecting 50 Pa.
Note: The fan control cable must be connected to the DG-1000 and the fan speed
controller for this feature to work.
USING THE DG-1000 WITH THE MINNEAPOLIS BLOWER DOOR
(Optional)
(Optional)
(Optional)
Set baseline