TDK-Lambda RWS 1500B Series Instruction Manual Download Page 4

INSTRUCTION MANUAL

RWS1000B

1500B Series

TDK­Lambda

<Page>

1. Model name identification method

RWS 1000B ­ 12 /

Option (*1)

Rated Output Voltage

Output Power type

Series Name

2. Terminal Explanation

Top side screw (Shipment condition)

Front side screw

Standard

N : Input terminal   Neutral line (M3.5 screw)
L : Input terminal   Live line (Fuse in line) (M3.5 screw)

: Earth terminal (M3.5 screw)

­V : ­ Output terminal

(62.5A max. / terminal, M5 screw)                                                                                                                   

+V : + Output terminal 

(62.5A max. / terminal, M5 screw)                                                                                                                            

Output voltage adjustment trimmer
Output monitoring indicator (Green LED)
Terminal cover 1
Terminal cover 2
Signal connector CN83 
Signal connector CN84 

4/23

(*1) Blank : Standard

/R

: Remote ON/OFF control

/FO : Power Fail (PF) signal

Parallel Operation

/RFO : Remote ON/OFF control

Power Fail (PF) signal
Parallel Operation

/RF

: Reverse fan (Intake air)

/ME : Approved by safety standards 

for medical equipment

/S

: Remote ON/OFF control

Standby supply

1
2
3

7

6

5

4

8
9

10

8

9

4

5

7

3

1

2

4

5

6

10

8

9

11

11

Summary of Contents for RWS 1500B Series

Page 1: ...roduct nor remove the cover as you might get an electric shock or might damage the product We will not be held responsible after the product has been modified changed or dis assembled Do not use this...

Page 2: ...gn matter or dust there is possibility of product failure or malfunction Provide countermeasure for prevention of lightning surge voltage as there is risk of damage due to abnormal voltage Connect tog...

Page 3: ...ations of Foreign Exchange and Foreign Trade Control Act Catalogue contents of the instruction manual may be changed without a prior notice Refer to latest catalogue or instruction manual Reproduction...

Page 4: ...ew V Output terminal 62 5A max terminal M5 screw V Output terminal 62 5A max terminal M5 screw Output voltage adjustment trimmer Output monitoring indicator Green LED Terminal cover 1 Terminal cover 2...

Page 5: ...Output monitor terminal V Internally connected to Output terminal Vm terminal can not supply load current 2 S Remote sensing terminal for output For remote sensing function which compensates for line...

Page 6: ...As the output voltage drops or FAN stop and AC input voltage down PF signal will be High 6 PF GND for PF signal 7 COM Current balance terminal For current balancing in parallel operation 8 PC Current...

Page 7: ...terminal when remote sensing function unnecessary 3 R Remote ON OFF control terminal 4 R GND for Remote ON OFF control terminal 5 NC No cnnection 6 NC No cnnection 7 NC Do not connect If connected ma...

Page 8: ...500B 30A 8 23 COM PC Line Filter Rectifier Inrush Current Limit Circuit Filter Control Circuit L N OCP Circuit Photo coupler Rectifier Filter Input 85 265VAC V Output S S V Vm Vm R R R Remote ON OFF C...

Page 9: ...n 0 5V Output off This sequence is using external voltage 3 Target option FO RFO 4 Target option S 9 23 PF PF Signal 3 Open collector 0V Vout 0V Input on Input off Input on Input off OVP point 1 Input...

Page 10: ...No 1 and S terminal Pin No 10 to Vm terminal Pin No 9 with the attached short pieces Short pieces are mounted at time of shipment Recommended torque M3 5 screw 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm M5 s...

Page 11: ...to COM terminal Pin No 7 the current balancing function activates and output current of each power supply is equivalently supplied to load Wires to PC terminals COM terminals shall be as short as poss...

Page 12: ...OVP remove the input of power supply for a few minutes and then re input Or use Remote ON OFF reset on option model R and RFO only Remote OFF to ON In addition the setting value of OVP is fixed and n...

Page 13: ...the probe ground lead of oscilloscope is too long 6 9 Series Operation For series operation either method A or B is possible Method A Method B Note Ensure that all units must be in operation Never us...

Page 14: ...valently supplied to load Wires to PC terminals COM terminals shall be as short as possible and same length and twisted 1 Adjust the output voltage of each power supply to be same value within 1 2 Use...

Page 15: ...C between output and R PF STB terminal each for 1 minute When testing withstand voltage set current limit of withstand voltage test equipment at 20mA The applied voltage must be gradually increased fr...

Page 16: ...M PC PF PF CN83 or CN84 L N V V Withstand Voltage Tester Input Term Output Term CN83 or CN84 L N V V Vm S Vm S R R COM PC PF PF Output Term Input Term Withstand Voltage Tester Vm S Vm S R R STB STB CN...

Page 17: ...Please check the voltage between Output and terminal If the voltage exceeding withstand voltage please add external capacitor to Output and It can decrease the voltage On the other hand no need to che...

Page 18: ...and RFO Power Fail PF signal will turn High level to indicate the abnormal status when the output voltage becomes Less than 80 of rated value caused by either the drop or brownout of the input voltage...

Page 19: ...tion OVP is inverter shut down method and manual reset type OVP function operates within 105 170 When OVP triggers the output will be shut down To reset OVP remove the input of power supply for a few...

Page 20: ...mplete thread of mounting screw should not be penetrated 3 Recommended torque for mounting screw M4 screw 1 27N m 13 0kgf cm 7 2 Output Derating according to the Mounting Directions The standard mount...

Page 21: ...e Load is percent of maximum output current value in a rated output voltage 21 23 Mounting A D Load Mounting A D 20 50 100 60 60 Ta C 0 20 40 60 80 100 120 20 10 0 10 20 30 40 50 60 70 80 Load Ta 60 8...

Page 22: ...mended Recommended wire type and crimp type terminal vary depending on use conditions Choice most appropriate wire type and crimp type terminal by refering to wire maker recommended allowable current...

Page 23: ...cluding that the unit is at fault Before concluding that the unit is at fault make the following checks 1 Check if the rated input voltage is connected 2 Check if the wiring of input and output is cor...