6­13. Remote Sensing (+S, ­S terminal) 

Remote Sensing function is provided.
This function compensates voltage drop of wiring from output terminals to load terminals. Connect "+S" terminal
to "+" terminal of load and "­S" terminal to "­" terminal of load with sensing wires. 
The total line voltage drop (+ side line and ­ side line) shall be less than 0.3V. 
In case that sensing line is too long, it is recommended to connect electrolytic capacitor in the following locations:

1) Across the load terminal,
2) Between "+S" terminal and "+Vm" terminal,
3) Between "­S" terminal and "­Vm" terminal.

Connect  "+S"  terminal to  "+Vm"  terminal,  "­S"  terminal  to  "­Vm"  terminal with  short  pieces when  remote 
sensing function is not used. If disconnected, OVP function may trigger and voltage will be shut down.

6­14. Low Output Voltage Detection Signal (PF Signal) 

Low output voltage detection signal is provided on option model /FO and /RFO. Power Fail (PF) signal will 
turn “High” level to indicate the abnormal status when the output voltage becomes Less than 80% of rated 
value caused by either the drop or brownout of the input voltage , OCP, OVP or Delay Shut Down operation. 
When the built­in FAN motor of this power supply unit stops, PF signal will turn to “High”. The PF signal is 
isolated from input and output by a photo­coupler. It uses the open collector method shown in below.

6­15. Remote ON/OFF Control

Remote ON/OFF control function is provided on option model /R, /RFO and /S. 
Using this function allows the user to turn the output on and off without having to turn the AC input off and on.
It is controlled by the voltage applied to +R and ­R. This circuit is in the secondary side of the power supply 
unit. 
Never connect to primary side.

/R, /RFO

18/23

+R & ­R terminal condition

Fan condition

SW ON (Higher than 4.5V)

Operate

SW OFF (Lower than 0.5V)

Not Operate

Output condition

ON

OFF

External voltage : E

4.5 ~ 12.5VDC

12.5 ~ 24.5VDC

External resistance : R

No required

1.5kΩ

Vce max  = 50V
Ic max  = 5mA

E

Power supply

780Ω

+R

­R

SW

R

R : External resistans

E : External voltage

Summary of Contents for RWS 1500B Series

Page 1: ...roduct nor remove the cover as you might get an electric shock or might damage the product We will not be held responsible after the product has been modified changed or dis assembled Do not use this...

Page 2: ...gn matter or dust there is possibility of product failure or malfunction Provide countermeasure for prevention of lightning surge voltage as there is risk of damage due to abnormal voltage Connect tog...

Page 3: ...ations of Foreign Exchange and Foreign Trade Control Act Catalogue contents of the instruction manual may be changed without a prior notice Refer to latest catalogue or instruction manual Reproduction...

Page 4: ...ew V Output terminal 62 5A max terminal M5 screw V Output terminal 62 5A max terminal M5 screw Output voltage adjustment trimmer Output monitoring indicator Green LED Terminal cover 1 Terminal cover 2...

Page 5: ...Output monitor terminal V Internally connected to Output terminal Vm terminal can not supply load current 2 S Remote sensing terminal for output For remote sensing function which compensates for line...

Page 6: ...As the output voltage drops or FAN stop and AC input voltage down PF signal will be High 6 PF GND for PF signal 7 COM Current balance terminal For current balancing in parallel operation 8 PC Current...

Page 7: ...terminal when remote sensing function unnecessary 3 R Remote ON OFF control terminal 4 R GND for Remote ON OFF control terminal 5 NC No cnnection 6 NC No cnnection 7 NC Do not connect If connected ma...

Page 8: ...500B 30A 8 23 COM PC Line Filter Rectifier Inrush Current Limit Circuit Filter Control Circuit L N OCP Circuit Photo coupler Rectifier Filter Input 85 265VAC V Output S S V Vm Vm R R R Remote ON OFF C...

Page 9: ...n 0 5V Output off This sequence is using external voltage 3 Target option FO RFO 4 Target option S 9 23 PF PF Signal 3 Open collector 0V Vout 0V Input on Input off Input on Input off OVP point 1 Input...

Page 10: ...No 1 and S terminal Pin No 10 to Vm terminal Pin No 9 with the attached short pieces Short pieces are mounted at time of shipment Recommended torque M3 5 screw 1 0N m 10 2kgf cm 1 6N m 16 3kgf cm M5 s...

Page 11: ...to COM terminal Pin No 7 the current balancing function activates and output current of each power supply is equivalently supplied to load Wires to PC terminals COM terminals shall be as short as poss...

Page 12: ...OVP remove the input of power supply for a few minutes and then re input Or use Remote ON OFF reset on option model R and RFO only Remote OFF to ON In addition the setting value of OVP is fixed and n...

Page 13: ...the probe ground lead of oscilloscope is too long 6 9 Series Operation For series operation either method A or B is possible Method A Method B Note Ensure that all units must be in operation Never us...

Page 14: ...valently supplied to load Wires to PC terminals COM terminals shall be as short as possible and same length and twisted 1 Adjust the output voltage of each power supply to be same value within 1 2 Use...

Page 15: ...C between output and R PF STB terminal each for 1 minute When testing withstand voltage set current limit of withstand voltage test equipment at 20mA The applied voltage must be gradually increased fr...

Page 16: ...M PC PF PF CN83 or CN84 L N V V Withstand Voltage Tester Input Term Output Term CN83 or CN84 L N V V Vm S Vm S R R COM PC PF PF Output Term Input Term Withstand Voltage Tester Vm S Vm S R R STB STB CN...

Page 17: ...Please check the voltage between Output and terminal If the voltage exceeding withstand voltage please add external capacitor to Output and It can decrease the voltage On the other hand no need to che...

Page 18: ...and RFO Power Fail PF signal will turn High level to indicate the abnormal status when the output voltage becomes Less than 80 of rated value caused by either the drop or brownout of the input voltage...

Page 19: ...tion OVP is inverter shut down method and manual reset type OVP function operates within 105 170 When OVP triggers the output will be shut down To reset OVP remove the input of power supply for a few...

Page 20: ...mplete thread of mounting screw should not be penetrated 3 Recommended torque for mounting screw M4 screw 1 27N m 13 0kgf cm 7 2 Output Derating according to the Mounting Directions The standard mount...

Page 21: ...e Load is percent of maximum output current value in a rated output voltage 21 23 Mounting A D Load Mounting A D 20 50 100 60 60 Ta C 0 20 40 60 80 100 120 20 10 0 10 20 30 40 50 60 70 80 Load Ta 60 8...

Page 22: ...mended Recommended wire type and crimp type terminal vary depending on use conditions Choice most appropriate wire type and crimp type terminal by refering to wire maker recommended allowable current...

Page 23: ...cluding that the unit is at fault Before concluding that the unit is at fault make the following checks 1 Check if the rated input voltage is connected 2 Check if the wiring of input and output is cor...

Reviews: