7. Wiring Method
(1) The output load line and input line shall be separated and twisted to improve noise sensitivity.
(2) The sensing lines shall be twisted or shield wire and separated from the output lines.
(3) Use all lines as thick and short as possible to make lower impedance. Wires are to be twisted or use shield wire to
improve noise sensitivity.
(4) Attaching a capacitor to the load terminals can eliminate noise.
(5) E terminal of this power supply is functional earthing. For safety purposes, connect protective earthing terminal to the
mounting set ground terminal.
(6) Recommended torque for the terminal piece:
(7) Recommended wiring
Recommended circuit protector : AC250V20A
Recommended noise filter : RSEN-2020 (TDK-Lambda Corp.)
Input terminal (M4 screw) : 1.27 N
・
m
Output terminal (M8 Bolt & Nut) : 10.8N
・
m
~
AC(L)
AC(N)
Noise Filter
Circuit
Protector
AC(L)
AC(N)
E
AC(L)
AC(N)
AC(L)
AC(N)
+
-
Load
HWS1000
Chassis of the equipment