TDK-Lambda
HWS1000/ME Series
INSTRUCTION MANUAL
5-12. Isolation Test
Isolation resistance between output and E (chassis) shall be more than 100M
W
at 500VDC and between output and
CNT
・
PF shall be more than 10M
W
at 100VDC. For safety operation, voltage setting of DC isolation tester must be done
before the test. Ensure that it is fully discharged after the test.
CNT TOG PF
PC
+S
+
-
-
S
E
AC(L)
AC(N)
Output
-
E (chassis)
500VDC 100M
W
or more
CNT TOG PF
PC
+S
+
-
-
S
E
AC(L)
AC(N)
Output
-
CNT
・
PF
100VDC 10M
W
or more
Isolation
tester
Isolation
tester