CHAPTER 2
SPECIFICATIONS
1.Vout voltage programming
2.Iout voltage programming (*13)
3.Vout resistor programming
4.Iout resistor programming (*13
5.On/off control
6.Output current monitor (*13)
7.Output voltage monitor
8.Power supply OK signal
9.Parallel operation
10.Series operation
11.CV/CC indicator
12.Enable/Disable
13.Local/Remote analog control
14.Local/Remote analog indicator
)
2.6 ANALOG PROGRAMMING AND MONITORING
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.5% of rated Vout.
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-1% of rated Iout.
0~100%, 0~5/10Kohm full scale, user selectable. Accuracy and linearity: +/-1% of rated Vout.
0~100%, 0~5/10Kohm full scale, user selectable. Accuracy and linearity: +/-1.5% of rated Iout.
By electrical Voltage: 0~0.6V/2~15V or dry contact, user selectable logic.
0~5V or 0~10V, user selectable. Accuracy: +/-1%.
0~5V or 0~10V, user selectable. Accuracy : +/-1%.
4~5V-OK, 0V-Fail. 500ohm series resistance.
Possible , up to 4 units in master/slave mode with two wires current balance connection.
Possible (with external diodes), up to 2 units. 600Vdc max.from chassis ground.
Open collector. CC mode: On, CV mode: Off. Maximum voltage : 30V, maximum sink current: 10mA
Dry contact. Open: Off, Short: On. Max. voltage at Enable/Disable in: 6V.
By electrical signal or Open/Short: 0~0.6V or short: Remote, 2~15V or open: Local.
Open collector. Local: Open, Remote: On. Maximum voltage: 30V, maximum sink current: 10mA.
2.1 OUTPUT RATING
1.Rated output voltage(1*)
2.Rated output current (*2)
3.Rated output power
V
A
W
MODEL
GEN
8-300
8
300
2400
10-240
10
240
2400
16-150
16
150
2400
20-120
20
120
2400
30-80
30
80
2400
40-60
40
60
2400
60-40
60
40
2400
80-30
80
30
2400
100-24
100
24
2400
150-16
150
16
2400
300-8
300
8
2400
600-4
600
4
2400
10
V
8
10
16
20
40
30
60
80
100
150
600
300
2.5 CONSTANT CURRENT MODE
1.Max. Line regulation (*6)
2.Max. Load regulation (*11)
3.Load regulation thermal drift
4.Ripple r.m.s. 5Hz~1MHz (*12)
5.Temperature coefficient
6.Temperature stability
7.Warm-up drift
---
---
---
---
---
mA
PPM/ C
o
0.01% of rated output c 2mA
0.02% of rated output c 5mA
70PPM/ C from rated output current, following 30 minutes warm-up.
0.01% of rated Iout over 8hrs interval following 30 minutes warm-up. Constant line, load & temperature.
O
Less than 0.05% of rated output current over 30 minutes following load change.
500
400
250
700
90
150
12
30
60
40
10
5
8~16V model: Less than +/-0.2% of rated output current over 30 minutes following power on.
20V~600V model: Less than +/-0.1% of rated output current over 30 minutes following power on.
2.3 INPUT CHARACTERISTICS
1-Phase, 200Vac models:
3-Phase, 200Vac models:
---
---
%
3-Phase models: 0.94 @ 230Vac, 1-Phase models: 0.99 @ 230Vac, rated output power.
Single Phase, 2 Wire +Ground, 200Vac models: 170~265Vrms, 47~63Hz
3 Phase, 3 Wire +Ground, 200Vac models: 170~265Vrms, 47~63Hz
Less than 50A
V
8
10
16
20
30
60
40
150
100
80
600
300
17.3
10.5
17.3
10.5
17.3
10.5
16.6
10.1
16.6
10.1
16.6
10.1
16.8
10.2
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
3.Power Factor (Typ)
4.Efficiency (*4)
5.Inrush current (*5)
2.Maximum
Input current
at 100% load
1.Input voltage/freg. (*3)
A
84
84
86
86
88
86
88
88
88
88
88
87
---
8
10
16
30
20
40
60
80
150
100
300
600
2.4 CONSTANT VOLTAGE MODE
1.Max. Line regulation (*6)
2.Max. Load regulation (*7)
3.Ripple and noise (p-p , 20MHz) (*8)
4.Ripple r.m.s., 5Hz~1MHz
5.Temperature coefficient
6.Temperature stability
7.Warm-up drift
8.Remote sense compensation/wire
9.
11.Transient response time
12.Hold-up time (Typ)
Up-prog. response time, 0~Vomax.(*9)
10.Down-prog. response time
Full load(*9)
No load(*10)
V
---
---
mV
mV
---
---
V
mS
PPM/ C
o
mS
mS
mS
0.01% of rated output v2mV
0.015% of rated output v5mV
50
6
50
6
50
6
50
6
55
6
60
7
90
20
240
60
55
6
60
6
70
10
150
45
50PPM/ C from rated output voltage, following 30 minutes warm-up.
O
0.01% of rated Vout over 8 hrs interval following 30 minutes warm-up. Constant line, load & temp.
Less than 0.05% of rated output v2mV over 30 minutes following power on.
2
2
15
10
500
2
15
20
500
2
15
20
500
5
15
20
600
5
20
20
700
5
40
50
1200
5
30
30
1100
5
40
50
1500
5
60
80
2500
5
80
100
3000
5
100
100
3000
10
15
500
Time for output voltage to recover within 0.5% of its rated output for a load change 10~90% of rated output
current. Output set-point: 10~100%, Local sense.
Less than 1mS, for models up to and including 100V. 2mS, for models above 100V.
10mSec Typical. Rated output power.
2.2 AUXILIARY OUTPUTS
1. 15V output (*14)
2. 5V output (*14)
15V
5%, 0.2A Max Load, Ripple & Noise 100mVp-p. Referenced internally to the negative output potential.
5V
5%, 0.2AMax Load, Ripple & Noise 100mVp-p. Referenced internally ti IF_COM potential.
---
---
10