background image

2800 Laura Ln, Middleton WI 53562  |  800.288.9383 Fax: 608.836.9044  |  www.tcsbasys.com  

27

CHECKOUT 

AND  

TROUBLESHOOTING

• 

Fan Proving

: The Fan Proving feature allows the controller to safely shut down the system in the case where the fan fails 

to operate correctly, avoiding damage to the heating or cooling units. The input to this feature is an external sensor that 

is connected to a Digital Input (DI) indicating that the fan is operating (closed) or not (open).

• 

External Time Clock: The user has the option of configuring the TC relay output as an external time clock. In this mode, 

the relay is configured as being active when the unit is occupied and inactive when the unit is unoccupied.

 

Auto+Recirc

: This fan mode allows the user to satisfy building air recirculation requirements without running the fan 

continuously, therefore saving energy. The feature guarantees that the fan runs a certain percentage of time over a given 

period (both programmable), even if the fan operation due to the normal calls for heat and cool is insufficient.

• 

Heating And Cooling Lockout: The Outdoor Air Lockout feature provides the ability to prevent (lockout) activation of any 

heat stages or cool stages based on the current outdoor air temperature reading. This is useful when implementing an 

energy savings policy or preventing a furnace from running in the summer, or a cooling compressor running in the winter.

• 

Discharge Air Limits

: The Discharge Air Limit feature provides the ability to force a shutdown to prevent the heat or cool 

stages from operating based on the current discharge air temperature reading. This is useful for protecting equipment 

from damage to out of normal (or runaway) operation, while still allowing for an attempt to condition the space. When 

discharge air high or low limit is in effect, heating or cooling is disabled. 

• 

Offsets and Differentials

: Heating turns on when the space temperature falls below the heating setpoint minus the 

heating offset minus the heating differential. Heating turns off when the space temperature rises to the heating setpoint 

minus the heating offset. Cooling turns on when the space temperature rises above the cooling setpoint plus the cooling 

offset plus the cooling differential. Cooling turns off when the space temperature falls to the cooling setpoint plus the 

cooling offset. Offsets effectively create new heating and cooling setpoints. The differential determines the temperature 

difference between the stage On point and the stage Off point, creating a hysteresis in the control output and preventing 

rapid cycling of equipment. 

• 

Equipment Protection Delays: Each relay output (DO) has minimum on/off times to protect connected HVAC equipment 

from short cycling. These delays may be configured via the Minimum-On-Time and Minimum-Off-Time properties of the 

binary output objects corresponding to each of the relays. By default minimum on & off times are two (2) minutes for all 

relays except for TC,B/O, and G, which are 30 seconds.

6  Checkout and Troubleshooting

6.1  Checkout

1.  Verify wiring. Wiring should be secure with no loose strands, and screws are tightened. 

2. 

Install the cover on the UbiquiSTAT. Make sure the cover is lined up properly and gently press the cover until it snaps 

into place. Make sure that the tether does not get pinched in the case. 

3. 

Power up the UbiquiSTAT. Ensure the stat powers up and screen lights up. 

4. 

Ensure all programming has been completed correctly. See 

Section 3

 for initial setup instructions. 

5. 

Navigate to the system test mode screen (Settings>Advanced>System Test Mode). 

6.  Turn on and off all outputs to check for proper operation. 

7.  Verify and test modulating outputs by incrementing and decrementing the milliamp output. 

8.  Run the heating test and watch the inputs for proper operation.

9.  Run the cooling test and watch the inputs for proper operation.

If this unit is to be networked:

10. 

Verify the UbiquiSTAT has the proper network address, baud rate, mode, and device ID.

If the network is active, verify communication by confirming that the RS-485 link status is “Connected” on the network 

status screen (Status>Network Screen). 

Summary of Contents for US4010

Page 1: ...S4120 Multi Stage RTU Thermostat US4040 US4140 Advanced RTU Thermostat US4050 US4150 Advanced Application Thermostat The UbiqiSTAT is a feature rich multifunction touchscreen thermostat which provides...

Page 2: ...Sensor Wiring 6 2 2 Remote Analog Sensor Wiring 6 2 3 Powering The Ubiquistat 6 3 Initial Setup 11 3 1 Room Temperature Sensor Selection 11 3 2 Additional Remote RTD Sensors 11 3 3 Analog Input AI Sen...

Page 3: ...SCHED I B 5 Heat Cool setpoint groups Includes all TCS SZ Series thermostat features Includes many additional features and enhancements 4 temperature inputs 1 built in 3 remote Outdoor discharge remot...

Page 4: ...ol a a Dehumidification monitoring Pressure monitoring General purpose monitoring a a Analog Outputs Hot and chilled water valve control a Modulating zone damper control w reheat a Economizer control...

Page 5: ...ld air from diffusers If using a remote room sensor the sensor should be mounted in the same manner The thermostat should be mounted in an area which is accessible for adjusting settings The UbiquiSTA...

Page 6: ...igurable as 0 20mA or 4 20mA for connecting remote sensors These inputs can be used for any current based sensors such as CO and humidity Use 18 AWG shielded twisted pair wire grounded at the sensor m...

Page 7: ...from equipment transformer 6 GND terminal is used for self powered 4 20mA inputs and outputs 3 24 VAC transformer See powering instructions 7 4 20mA transmitter sensor input wiring 18 AWG twisted shie...

Page 8: ...20mA transmitter sensor input wiring 18 AWG twisted shielded pair AI1 is shown as Self Powered sensor This input can be used for either 2 wire or self powered 3 24 VAC transformer See powering instruc...

Page 9: ...1c 1 For communication wiring use 3 con ductor twisted shielded 22 AWG 4 Dry contact Must not be powered 2 Control signals may be up to nominal 28 VAC from equipment transformer 5 For sensor input wi...

Page 10: ...onal 500ohm resistor included 1 For communication wiring use 3 con ductor twisted shielded 22 AWG 5 For sensor input wiring use 2 conductor twisted shielded 18 AWG 2 Control signals may be up to nomin...

Page 11: ...rced from an average of the internal sensor and a sensor wired to the T1 input terminals The weight of the average is also configurable and can be used to divide the input of each sensor equally Singl...

Page 12: ...third stage must also be enabled Both of these stages are optional and must be configured using the internal BACnet Explorer Figure 3 Terminals Relays Conventional US4010 US4110 Only Conventional Fan...

Page 13: ...by default where 4mA is minimum cooling damper is closed and 20mA is maximum cooling damper is open by default By default the economizer is enabled when the following conditions are met Outdoor air i...

Page 14: ...gation automatically returns to the home screen and the display dims after 10 minutes of inactivity no touches detected The basic components of the home screen are shown below Figure 4 1 Room Temp and...

Page 15: ...ame The device name is typically used describe what area or unit the thermostat is controlling The device name can only be changed using Ubiquity Cloud or an external BACnet configuration tool The tim...

Page 16: ...n the control behavior When an input value is not avail able not configured or no sensor connected dashes are displayed The following inputs are shown Room Temperature The temperature of the space zon...

Page 17: ...r Enabled Indicates whether the economizer is currently allowed to modulate open This depends on the occupancy state whether free cooling is available and if cooling is needed Free Cooling Indicates w...

Page 18: ...t Yellow The UbiquiSTAT is able to communicate but is detecting problems with the network that may cause the communication to be unreliable Check the RS 485 wiring and network configuration on other d...

Page 19: ...n Section 5 The fan proving status can be reset from the service status screen thereby re enabling system control Check Filter When a DI is configured for Check Filter service status will indicate the...

Page 20: ...setpoint pair can be used multiple times to create up to eight schedule changes per day At midnight each day the system automatically transitions to unoccupied which uses the unoccupied heating and co...

Page 21: ...0 PM Monday Store closes and cleaning crew arrives System changes to Occupied B schedule which uses the B heating and cooling setpoints 11 00 PM Monday Cleaning crew leaves System changes to Unoccupie...

Page 22: ...ry calibrated However an installation may have inherent measurement inaccuracies from sources such as sensor lead resistance and sensor placement Therefore a field calibration may be required Factory...

Page 23: ...ch explorer screen shows a single property of a BAC net object These same object properties can also be viewed over the network with BACnet network tools See the BACnet Explorer Guide for a list of al...

Page 24: ...ly An example is service status history which records any service status activity including duration Action Describe changes made to the device from a local user or an outside programming source i e U...

Page 25: ...canceled with a countdown timer shown Also the affected analog outputs are driven immediately to the appro priate Max Min levels When a test is active the manual control of relays and analog outputs i...

Page 26: ...with the analog inputs AIx AV 151 and AV 152 This is the raw input reading in milliamps AIx Scaled AV 181 and AV 182 This is the scaled representation in engineering units The units property of this o...

Page 27: ...minus the heating differential Heating turns off when the space temperature rises to the heating setpoint minus the heating offset Cooling turns on when the space temperature rises above the cooling...

Page 28: ...sible check the following System Mode Heating and Cooling Setpoints Offsets and Differentials Room Temperature is above the Cooling Setpoint or below Heating Setpoint Outdoor Air Lockout Status Discha...

Page 29: ...t for proper operation of actuators see Section 4 5 2 10 Two conditions must be met before the economizer analog output is allowed to modulate First there must be a call for cooling Second the outdoor...

Page 30: ...to the BACnet Weekly_Schedule property and the TCSbus Holiday Schedule is synced to the BACnet Exception_Schedule property of the schedule object Due to the limitations of the TCSbus holiday schedule...

Page 31: ...it is not possible to upgrade a US4040 to a US4050 7 5 Backup Restore The Backup Restore feature of Insight can backup and restore all of the user settings on the thermostat This can be useful for pr...

Page 32: ...on against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in ac cordance with the instructions ma...

Reviews: