background image

2800 Laura Lane  •  Middleton, WI 53562  |  800.288.9383  |  www.tcsbasys.com  

21

21

Configuration

Additional Configurations

This section describes how to configure many of the advanced options built into the UbiquiSTAT. Configuring these 

advanced options calls for an understanding of the use of BACnet objects, which are accessible through the BACnet 

Explorer (see the 

ADVANCED (2/2)

 screen .) Each subsection describing the advanced configurations includes the 

relevant BACnet object number(s). Refer to the 

UbiquiSTAT BACnet Explorer Guide

 for screen identification and other 

information. 

NOTE:

 Explanations of BACnet and BACnet objects is beyond the scope of this manual. Changing BACnet 

configurations

 

should only be performed by experienced, qualified HVAC technicians

Adding Heating and/or Cooling Stages 
By default, UbiquiSTATs ship with either one or two stages of heating and/or cooling enabled. However, the B/O and 

TC relays can be configured as additional stages of heating and/or cooling when the UbiquiSTAT is configured as a 

conventional thermostat. Reference BACnet IDs: MSV-316, MSV-317.

Scaling Analog Inputs 
The analog inputs (A1, A2) measure signals from sensors wired to the inputs. The scaling of those signals can be 

independently adjusted to match the ranges of the sensors. Because the input signals are scalable, the UbiquiSTAT must 

be configured to the sensors’ input ranges, signal minimums, and signal maximums:

• 

Input Range: Set the expected input range to 0 – 20mA or 4 – 20mA. Reference BACnet IDs: MSV-170, AV-171

• 

Scaled Minimum: Defines the sensor value when its signal is at the minimum range (0 or 4mA). Reference BACnet 

IDs: AV-161, AV-163

• 

Scaled Maximum: Defines the sensor value when its signal is at the maximum range (20mA). Reference BACnet IDs: 

AV-162, AV-164

In addition, there are four read-only analog BACnet objects which display the raw readings and the engineering scaled 

values. Reference BACnet IDs: AI-151, AI-152, AV-181, AV-182.

Setpoint Setback
The Setpoint Setback feature allows the user to increase the cool setpoint and decrease the heat setpoint by a 

predetermined amount based on the state of a Digital Input (DI). Reference BACnet IDs: AV-1254, BV-1536.

Economizer

 

4X4X 4X5X

The Economizer (also called “free cooling”) uses outdoor air for cooling, when appropriate, to reduce the need for 

mechanical cooling. Reference primary BACnet IDs: AO-200, AV-240; MSV-210, MSV-220, MSV-230, AO-201, AV-241, MSV-

211, MSV-221, MSV-231, MSV-1400, AV-1500, MSV-1501, MSV-1511, AV-1512. Reference secondary BACnet IDs relevant 

to your application: AV-1410, AV-1420, AV-1430, AV-1440, AV-1421, MSV-1431, AV-1441, AV-1510, AV-1513, AV-1514, AV-

1515, BV-1516, BV-1517.

Commissioning the UbiquiSTAT

When commissioning the UbiquiSTAT for the first time, do the following:

• 

Verify all wiring connections to the mounting plate are secure, with no loose strands. Check all screws for tightness

•  Ensure the front cover is lined up properly and snapped into place
• 

Ensure the UbiquiSTAT is connected to an appropriate power source. The screen should be lit

•  Ensure you have completed all programming correctly
•  Navigate to the 

SYSTEM TEST MODE

 screen and ensure the heating and cooling modes are functioning properly by 

turning on and off all outputs

•  Verify modulating outputs are changing and then resetting the milliamp output (refer to the 

SCALING ANALOG 

INPUTS

 screen).

• 

If the UbiquiSTAT is to be networked, verify it has the proper network address, baud rate, mode, and device ID. If the 

network is active, confirm the RS-485 link status is “Connected”: (refer to the 

NETWORK

 

screen).

4X4X 4X5X

Summary of Contents for UbiquiSTAT

Page 1: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com 202304 Configuration Guide UbiquiSTAT Commercial BACnet Controller...

Page 2: ...tents 4XXX Model 1 2 4 5 Series Wired 0 Wireless 1 Standard 0 Internal Humidity Sensor 1 4X1X US4010 Series 4X2X US4020 Series 4X4X US4040 Series 4X5X US4050 Series Model Number Definitions A Key to U...

Page 3: ...loud or TCS Insight software which is available for download on the TCS website If you have any questions regarding your UbiquiSTAT room controller contact TCS Technical Support at 800 288 9383 ext 2...

Page 4: ...DI This allows the controller to increase the cooling setpoint and decrease the heating setpoint by a predetermined amount and effectively create a setback response to an energy demand The indicator...

Page 5: ...inimum air circulation requirements Cool The fan runs only when there is a call for cool available only when thermostat type is conventional Choose Fan Mode Screen Fan Mode Selection Example System Mo...

Page 6: ...east two degrees for most conditions Occupancy Schedule Settings NOTE While all UbiquiSTAT models allow you to configure weekly schedules from the touchscreen holiday schedule settings are only availa...

Page 7: ...To create a schedule setting Occupancy Schedule Screen STEP 1 Touch the EDIT button on the Occupancy Schedule Entries screen Edit Schedule Days Screen STEP 2 Select the days of the week you wish to as...

Page 8: ...is assigned Touch DONE to save your entry On the EDIT SCHEDULE screen touch SAVE to save the changes NOTES The first time you connect the UbiquiSTAT to Ubiquity Cloud the schedule settings will be au...

Page 9: ...wish to attach to the new date Touch DONE to save the settings NOTE Schedule periods stay in effect until the next schedule period start time assigned to that day or until midnight at which point the...

Page 10: ...n the SETTINGS screen brings up the first of two screens ADVANCED 1 2 has buttons for Network Settings wireless models RS 485 Network wired models Thermostat Type Analog Outputs Display Options and Te...

Page 11: ...ettings for mode type baud rate device address and device instance Touch the SAVE button on each screen to save any changes RS 485 Communication Mode Screen RS 485 Baud Rate Screen RS 485 Network Sett...

Page 12: ...ice Instance Number Screen BACnet Wi Fi Settings After selecting BACNET WI FI on the NETWORK SETTINGS screen touch the ENABLE SETTINGS button This will activate the screens for scanning available Wi F...

Page 13: ...on the ADVANCED 1 2 screen allows you to configure either of the UbiquiSTAT s Analog output ports for HVAC mode to the type of action you wish to assign to the port and the range Analog Output Program...

Page 14: ...fine tune the weighting between the internal sensor and the external sensor in five percent increments Room Temperature Source Screen Room Temperature Source Averaging Screen Temperature Sensor Calib...

Page 15: ...D button to confirm your desire to reset the UbiquiSTAT this cannot be undone You will then return to the INITIAL SETUP screen at the beginning of the Startup Wizard refer to the UbiquiSTAT Quick Setu...

Page 16: ...l logic is disabled and outputs will revert to inactive or zero percent inputs Relay Inputs W1 W2 Y1 Y2 G B O TC Touching the Relay Outputs buttons activates the connected equipment after a three seco...

Page 17: ...eported when the UbiquiSTAT detects an unexpected behavior Report any faults to TCS technical support System Event Log Screen Internal Dehumidification Sensor Programming Touching the DEHUMIDIFICATION...

Page 18: ...up the Status section from which you can verify all settings in real time The screens in this section are grouped into three categories System Advanced and Network The information on each screen vari...

Page 19: ...l sensors e g outside temperature humidity CO2 etc NOTES Inputs for Mixed Air and CO2 are only available on 4X4X 4X5X Input for Humidity is only available on 4X5X Relay Outputs The current state of he...

Page 20: ...update the status About Section Touching the ABOUT button on the bottom of the HOME screen brings up the About section The main About screen displays the following information Model number Device Name...

Page 21: ...or value when its signal is at the maximum range 20mA Reference BACnet IDs AV 162 AV 164 In addition there are four read only analog BACnet objects which display the raw readings and the engineering s...

Page 22: ...is showing on display Faulty wiring Faulty relay Room temperature is above the cooling setpoint or below the heating setpoint Check wiring Check for a relay failure by connecting a jumper across termi...

Page 23: ...ing and cooling setpoints are correct Reset the UbiquiSTAT by touching and holding the STATUS button for five seconds Analog outputs not working Faulty wiring Improper programming UbiquiSTAT is being...

Reviews: