Configuration
System Event Log
Touching the SYSTEM EVENT button on the
screen will bring up log entries for the last 100 events. An
event can be one of three classes: information, actions, and faults. Events contain a time stamp, description, and may
contain an internal programming code. Additional information may also be displayed.
•
Info: Describes events in the system for informational purposes only. An example is service status history, which
records any service status activity including duration.
•
Action: Describes changes made to the device from a local user or an outside programming source (e.g., Ubiquity
Cloud).
•
Fault: These are only reported when the UbiquiSTAT detects an unexpected behavior. Report any faults to TCS
technical support.
System Event Log Screen
Internal Dehumidification Sensor Programming
Touching the DEHUMIDIFICATION button on the
screen brings up the DEHUMIDIFICATION
PROGRAMMING screen.
Dehumidification Programming Screen
This screen has three dehumidification programming options:
•
DEHUMID allows you to turn off dehumidification, limit it to one or all available cooling stages, and control either a
digital output or analog output.
•
REHEAT allows you to select the reheat settings, depending on available heat stages or analog output. You can also
choose to conduct reheating by activating the UbiquiSTAT’s Digital Output (as in the case of controlling a heat pump),
or you can suspend reheating entirely.
•
SETPOINT allows you to determine the dehumidification setpoints for Occupied or Unoccupied modes.
4X11 4X21 4X41 4X51