4. Go to programming step #16 and make the setpoint 

much higher than the current AI reading. If the digital 

output(s) are set for heat mode, the digital output(s) 

should come on. If the digital output(s) are set for cool 

mode, the digital output(s) should go off. If the analog 

output is set to direct acting, it should go to 0% (0 or 

4mA). If the analog output is set to reverse acting, it 

should go to 100% (20mA).

5. Go to programming step #21 and make the setpoint 

much lower than the current AI reading. If the digital 

output(s) are set for heat mode, the digital output(s) 

should go off. If the digital output(s) are set for cool 

mode, the digital output(s) should come on. If the ana-

log output is set to direct acting, it should go to 100% 

(20mA). If the analog output is set to reverse acting, it 

should go to 0% (0 or 4mA).

6. Go back and reprogram programming step #16 and/or 

#21 for operation.

TRouBLEShooTINg
No display

Check for 24 VAC on terminals 24VAC “R” and GND “C”.

Relay outputs do Not Come on

Check the setpoint, deadbands, offsets and differentials. 

Check to be sure that the digital outputs are programmed 

properly for "heating" or "cooling" (make on fall, make 

on rise), and that they are not disabled. Short "L1/2" to 

"M1" to bypass digital output one, and "L1/2" to "M2" to 

bypass digital output two. This is a check for a mechani-

cal relay failure.

Wrong Temperature display

If either of the two analog input readings is slightly high 

or low, the respective Low and High scaling limits can be 

adjusted slightly. Let’s say that the AI1 value is 5° Low 

and that AI1 has a span from -40 to 160°F. Change the 

scaling for the Low and High scaling limits to be -35°F to 

165°F, instead of  -40°F to 160°F. You can also measure 

DC voltage from "AI1" to GND "C" and "AI2" to GND 

"C". The 4 to 20mA inputs are represented as 1 to 5VDC 

signals here. Using this knowledge, you can determine 

whether the problem is with the controller or your input 

device.

outputs Will Not Shut off

First check the AI1 value and the setpoint and deadbands, 

then determine whether the output should be on. There are 

delays and minimum on and off times for the relay stages. 

Also, check the monitoring menus to verify that the digital 

outputs are on. Pulling the terminal with the 24VAC “R” 

and GND “C” wires off, will instantly turn all outputs off and 

reset the controller.

Analog output Not Working Properly

Check wiring. A separate transformer should be used for 

the SZ1143b and a separate transformer should be used 

for the modulating device. Check to make sure that the 

analog output is programmed correctly.

the analog output device open or closed during unoccu-

pied times. "Modulating" will modulate the analog output 

device to maintain the “unoccupied” setpoint.). Enter a 

proportional band (throttling range) in percent.
For proportional only control, set the integral and deriva-

tive values to zero.
If using integral and/or derivative control, also enter the 

integral and derivative values. If either the integral or the 

derivative values is non-zero, the proportional band is no 

longer a proportional value, but a gain value.
For PID control, lowering each of the three constants 

slows down the response, and raising each of the three 

constants speeds up the response.

dI2 AQuASTAT

When DI2 is selected to have an aquastat function, 

operation is as follows.
With DI2 "Open", the analog output operates in its pro-

grammed mode. When DI2 is "Closed", the analog out-

put uses the opposite of the selected direct or reverse 

action, and if the analog output has been selected to 

modulate from endpoint, the analog output uses the 

opposite of the selected heat or cool mode.

BuILT-IN dELAyS

The SZ1143b has delays built into the programming 

sequences to protect equipment. Each stage has a 

minimum on and off time of two minutes. There is a 

minimum of two minutes between when one stage turns 

on until the next stage is allowed to turn on, as well as 

when one stage turns off until the next stage is allowed 

to turn off.

Checkout & Troubleshooting       

ChECKouT
Note:

 The stages have a minimum on and off time of 2 min-

utes. 
You may verify the status of the stages and analog 

output in monitoring screens 3, 4, and 5, which are 

accessed by pressing the “Scroll” key. 
1. Verify all wiring prior to powering the controller.
2. Turn power on. The controller will display a momen-

tary screen with the model number, another momen-

tary screen with the version number and then the 

main monitoring screen with the current AI1 value. 

3. Take note of the current AI1 reading. Go into program-

ming mode. Go to programming step #16 and set AI2 

mode to monitor.

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

8

* SZ1143b *

TCS V2.2 (c)

AI1 

0

AI2 

 

0

Summary of Contents for SZ1143b

Page 1: ...a broad variety of transducers Two digital inputs for switches alarms clocks etc One 4 20 mA modulating output Two relay outputs Adjustable P I D control on modulating output Adjustable offsets and d...

Page 2: ...r sensing Powering the SZ1143b The SZ1143b is powered from 24 VAC 20 Caution Do not connect to 120 VAC When multiple TCS Basys Controls devices are using a single transformer the polarity of the power...

Page 3: ...the analog output range will be 0 20mA or 4 20mA This screen is the last screen if High Low control mode is enabled and is the same as step 22 when not enabled Enable Dew Point Control Select yes to e...

Page 4: ...t Type Screen Select whether the analog output will be modulated from an endpoint or the mid point Note Set to MIDPOINT if dew point control is selected Analog Output Unoccupied Action Screen Select w...

Page 5: ...e IN1 or IN2 terminal of the first SZ1143b Remove the RTN1 or RTN2 jumper from the second SZ1143b Refer to Sharing analog inputs on an SZ1143b Application note for more detail HIGH LOW CONTROL The ana...

Page 6: ...gramming screens 22 through 31 AI2 MODE PARAMETERS Analog input two can be selected as either Monitor Remote Setpoint or Reset If monitor is chosen the analog output and digital out puts are controlle...

Page 7: ...point In most cases the first stage is set to zero The differential value is the differ ence between the on and off points Setpoint O N O N O N O N O FF O FF O FF O FF Differential Differential O ffse...

Page 8: ...res off will instantly turn all outputs off and reset the controller Analog Output Not Working Properly Check wiring A separate transformer should be used for the SZ1143b and a separate transformer sh...

Page 9: ...ed Setpoint and Analog Output Screen Shows the current setpoint used for control and the output value for the analog output The analog output is dis played as a percentage 0 100 Analog Output Screen S...

Reviews: