Wiring
The SZ1143b uses terminal designations for wiring. See
diagram below.
TRANSMITTER WIRINg
The SZ1143b accepts two 2-wire, 4-20mA transmitters.
Use our TH Series for relative humidity sensing, TS/TX
Series for temperature sensing, or TD/TL Series for dif-
ferential air sensing.
PoWERINg ThE SZ1143b
The SZ1143b is powered from 24 VAC +/- 20 %.
Caution
: Do not connect to 120 VAC. When
multiple TCS Basys Controls devices are using a
single transformer, the polarity of the power wir-
ing must be maintained because all TCS devices
are half-wave rectified and have common return
paths.
If wiring for communications, dedicated power must be
used to power the controller. Several S series controllers
may be powered from the same transformer, provided
that the transformer has sufficient power. (Supertrols
require 5 VA @ 24VAC.)