background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

7

The software allows you to override the thermostat by putting the 

override parameter into the remote mode, and thus disabling the timed 

override.

SetBACk And oveRRide APPliCAtionS

In most applications, it is desired to maintain a regular schedule, 

and allow timed override with the button on the face or with a remote 

momentary contact.
To allow a regular schedule, and also automatically override with the 

use of occupancy or light sensor, set DI3 to override and set it up so 

that the contact is closed when you want the override. 
For applications where a room might not be used on a regular sched-

ule, such as conference rooms, set DI3 to external time clock and 

close the contact when you want the room occupied, such as with a 

switch or wind-up timer. If each occupancy period is about the same, 

(theaters, meetings) another option is to set the DI3 to external time 

clock, and use the timed override button to put the unit in occupied 

mode.
To make the unit always occupied, set DI3 to external time clock and 

short the DI3 terminal to ground.

tWo-PiPe FAn Coil oPeRAtion

For two-pipe fan coil operation, in step #28 select NO. In step #29, 

select YES. You must then select whether the system is HEATing only, 

COOLing only or heating and cooling (H&C) in step #30.
When using a two-pipe system to do both heating and cooling, the 

SZ1063 and SZ1064 need to know whether hot or cold water is avail-

able. This is accomplished by either the use of a mechanical aquastat 

(bulb thermostat) connected to terminals DI1 and 24-, or by the use of 

a temperature sensor connected to T2 and T2 (SZ1064 only). If using 

a mechanical thermostat, select DIGITAL in step #31, and select nor-

mally closed N.C. or normally open N.O. In step #32. If using a tem-

perature sensor, select ANALOG in step #31 and place a changeover 

setpoint in step #33. When the temperature is greater than this set-

point, it is assumed hot water is available and heating is done. When 

the temperature is less than this setpoint, it is assumed cold water is 

available and cooling is done.
When using a two-pipe system to do both heating and cooling, only 

AO2 is used. When using a two-pipe system to do only heating, only 

AO1 is used. When using a two-pipe system to do only cooling, only 

AO2 is used.

thRee-PiPe FAn Coil oPeRAtion

For three-pipe fan coil operation, in step #28 select YES.
Three-pipe fan coil operation assumes that there are two water 

sources available (hot and cold), and that the water to the fan coil will 

be a mixture of these. Only analog output two is used for three-pipe 

operation. The output will be 12mA (4-20mA) when there is no need 

for heating or cooling. As there becomes a need for heating or cool-

ing, the analog output modulates toward 4mA or 20mA depending on 

whether analog output two is direct or reverse acting.

FoUR-PiPe FAn Coil oPeRAtion

For four-pipe fan coil operation, in step #28 select NO. In step #29, 

select NO. 
Four-pipe fan coil operation assumes that there are two water sourc-

es available (hot and cold), that are each controlled by its own valve. 

Analog output one is used for heating and analog output two is used 

for cooling.

PiPe temPeRAtURe SenSing

The SZ1063 and SZ1064 accepts a remote pipe temperature sen-

sor for monitoring purposes or for changeover in a two-pipe system.  

(See setup instructions for dipswitch placement for this option.)
The pipe temperature span is 0 to 150°F (-17.8 to 65.6°C).

AnAlog oUtPUtS

The analog outputs on the SZ1063 and SZ1064 are used to control 

the heating and cooling in a space. Analog output 1 is used to control 

heating and analog two is used to control cooling with a four pipe 

system. Only analog output 2 is used with a three-pipe or with two-

pipe system set for heat and cool (H&C).

di2 SetPoint ShiFt

The SZ1063 and SZ1064 allow DI2 to be set for setpoint shift for 

energy demand setback. A digital contact that closes when setback 

is needed should be wired into DI2. You may specify a number of 

degrees such that, when the thermostat is operating in the occu-

pied mode, and DI2 is closed, the heating setpoint will be lowered 

this number of degrees, and the cooling setpoint will be raised this 

number of degrees. The fan will continue to operate according to its 

occupied setting. If you are using DI2 as monitor for another pur-

pose, make sure to set the setpoint shift value to zero.

AUXiliARy RelAy oUtPUt PARAmeteRS

The auxiliary relay of the SZ1064 will control one stage of either 

heating or cooling, or can be used as a timeclock output.
If the auxiliary relay is used as heating or cooling stage, you may 

specify an offset and a differential value. The offset value is the 

amount away from the setpoint a stage will turn off. By assigning a 

value other than zero, you "anticipate" that the residual heat or cool-

ing in the duct will bring the temperature back to setpoint. In most 

cases, a first stage is set to zero. The differential value is the differ-

ence between the on and off points. Using an offset value greater 

than or equal to the proportional band of an analog output will allow 

the relay to come on after full modulation is achieved. Strip heat, for 

example.
If the auxiliary relay is used as a timeclock output, it is selectable 

whether the relay is open or closed during the occupied period. 

During the unoccupied period, the opposite will occur.
Keep in mind that although it is an isolated relay (separate common 

terminal), it is rated at 24 VAC @ 2A. For loads that exceed this, use 

an external relay.

Summary of Contents for SZ1063

Page 1: ...rt up and power up for soft starts Smart recovery SZ1064 only Local and remote override capability External time clock and override options Auxiliary output for heat cool or time clock SZ1064 only Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 3 Sequence of Operation 3 Checkout Troubleshooting 9 LED Description 10 Mounting The SZ1063 and 64 are designed for wall mounting...

Page 2: ...on return paths When the Superstat is used as a stand alone thermostat without communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Black 1 For communication wiring use twisted shielded 18 AWG Must be run separately 2 Dry momentary contct Must not be p...

Page 3: ...oftware manual Programming through the keypad To access the programming screens press the program setup button Screens A thru F are monitoring screens and programming screens begin with 1 Access may be locked out with dipswitches or an access code may be required program setup ENTER ACCESS 000 CODE 9 OVERRIDE ON 178 MINUTES F program setup MOD OUT 1 00 MOD OUT 2 00 E program setup program setup PI...

Page 4: ...up to two occupied periods SZ1064 only Schedule Announcement Screen Announces the next screen SZ1064 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the next screen does not appear SZ1064 only Occupied Times Screen Set the hours and minutes of start and end times for up to two occupied periods SZ1064 only Occupied Times Screen Set the hours and mi...

Page 5: ... Fan Coil Enable Screen Choose YES if using a two pipe system Otherwise choose NO If NO is selected and skip to step 42 and it is assumed to be a four pipe system Digital Aquastat Input Screen Choose whether DI1 will be normally open N O or normally closed N C for cooling The next screen is skipped Analog Aquastat Input Screen If an analog aqua stat is selected choose the changeover setpoint to di...

Page 6: ...erride or Continuous Unoccupied Override is enabled then pressing the override once and then pressing and holding it for 5 seconds puts the thermostat into a hold mode the override LED on the thermostat will flash quickly In this mode the override setpoints are used until the next occupied period is reached or until the thermostat is manually taken out of the Continuous Override mode by pressing t...

Page 7: ...n there is no need for heating or cooling As there becomes a need for heating or cool ing the analog output modulates toward 4mA or 20mA depending on whether analog output two is direct or reverse acting FOUR PIPE FAN COIL OPERATION For four pipe fan coil operation in step 28 select NO In step 29 select NO Four pipe fan coil operation assumes that there are two water sourc es available hot and col...

Page 8: ...ow the day or time 2 Turn power on The thermostat will display a momentary screen with the model number and then the main monitoring screen with the time day fan speed and current temperature 3 Press the PROGRAM SETUP button until you reach screen 13 and set the System Mode to AUTO Continue on until you reach screen 14 and set the Occupied Fan Mode to AUTO Go to screen 22 which allows you to set t...

Page 9: ...and tunoccupied fan mode in programming If the Fan Status is OFF press the Low Medium or High button If the fan is off but the fan LED is on check wiring Short terminals R to GL GM or GH and see if the fan comes on This is a check for a mechanical relay failure Heating or Cooling Does Not Come On Heating is on whenever the heating LED is on and cooling is on whenever the cooling LED is on If heati...

Page 10: ...ability to put the unit into occupied mode by pressing the override button on the front By factory default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 23 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 49 Programm...

Reviews: