Pointmap Table for SZ1024N (continued)
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
ADDITIONAL NOTES
ADI
41
Wednesday
0-1440
ADI
42
Thursday
0-1440
ADI
43
Thursday
0-1440
ADI
44
Thursday
0-1440
ADI
45
Thursday
0-1440
ADI
46
Friday
0-1440
ADI
47
Friday
0-1440
ADI
48
Friday
0-1440
ADI
49
Friday
0-1440
ADI
50
Saturday
0-1440
ADI
51
Saturday
0-1440
ADI
52
Saturday
0-1440
ADI
53
Saturday
0-1440
ADI
54
Sunday
0-1440
ADI
55
Sunday
0-1440
ADI
56
Sunday
0-1440
ADI
57
Sunday
0-1440
BD
1
DI1 control mode
0=fan proving,
See "Operation" (page 8).
1=Monitor
BD
2
Occ fan mode
0=On, 1= Auto
"Fan Switch" button on key pad
BD
3
Enable occupied fan switch
0 = No, 1=Yes
Enables "Fan Switch" button.
BD
4
Enable system switch
0 = No, 1=Yes
Enables "System Switch" button.
BD
5
Use of discharge air sensor
0 = No, 1=Yes
Always monitored, enables discharge
air function.
BD
6
Enable smart recovery routine
0 = No, 1=Yes
4° per hour setpoint ramp prior to oc-
cupancy for both heating and cooling.
BD
7
Require access code
0 = No, 1=Yes
Programming access from keypad.
for programming?
BD
8
Require access code
0 = No, 1=Yes
Clock/Schedule access from keypad.
for clock/schedule?
BD
9
Enable compressor 2
0=disable, 1=enable
Disable unused stages (recommended).
BD
10
Enable auxiliary heat 1
0=disable, 1=enable
BD
11
Enable auxiliary heat 2
0=disable, 1=enable
BD
12
Reverse valve action for cooling
0=Normally Open
State of relay output during occupied
1=Normally Closed
period.
BD
13
Time clock relay output
0=Normally Open
State of relay output during occupied
1=Normally Closed
period.
BD
14
Control mode
0=Proportional
Stages turned on and off using offsets
and differentials only.
1=Prop. + Integral
Stages turned on and off using offsets
and differe a time factor.
BD
15
DI1 source
0=local contact
"Local" means read by or controlled by
Thermostat.
1=remote request
"Remote" means the state of the input or
output is controlled only by computer.
BD
16
DI2 source
0=local contact
1=remote request
BD
17
DI3 source
0=local contact
1=remote request
BD
18
Override function source
0=local keypad
1=remote request
BD
19
Fan relay source
0=local mode
1=remote request
BD
20
Remote DI1 request
0=off, 1=on
When selected to be "Remote", turns
input or output on and off.
BD
21
Remote DI2 request
0=off, 1=on
BD
22
Remote DI3 request
0=off, 1=on
BD
23
Remote override request
0=off, 1=on
This is a permanent override.
BD
24
Remote Fan request
0=off, 1=on