2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

6

Demand =  ((CTValue*MtrConst*MtrMult))
 

      (PPRValue*PulseTimeDiff)

Consumption =  ((PulseCount*CTValue*MtrConst*MtrMult))
 

 

PPRValue

 
 
The above diagram depicts how a single pulse and the 

pulse time difference are represented on a pulse waveform 

input into the SE1000.

Checkout & Troubleshooting      

CheCKout

You may verify the status of each meter input by press-

ing the "Scroll" key and then using the "Increment" and 

"Decrement" keys to cycle through the various screens.
1. Verify all wiring prior to powering the controller.
2. Turn power on. The controller will display a momentary 

screen with the model and version number, and then the 

main monitoring screen.

Meter 1 Demand

 

*SE1000*

TCS V3.0(C)

3. Take note of the current readings for all meters. Since 

the SE1000 is used only for monitoring, and if the read-

ings appear to be correct, you are done.

4. If a value does not appear to be correct, scroll through 

the meters to view the desired input and verify that a 

value (other than 0) is being shown.

5. Go back into programming mode and adjust various 

parameters as required to make the value appear cor-

rectly. 

6  If a value shown as 0, the SE1000 is not retrieving a 

pulse signal. Verify the pulse signal is being generated 

at the meter or CT and check the input wiring.

trouBLeshooting
no display

Check for 24 VAC on terminals “R” and “C”.

incorrect monitoring Value displayed

If any of the meter inputs are showing incorrect values, 

verify the programming parameters for that meter. If any of 

the meter inputs are showing 0, verify the pulse signal is 

working. See checkout for details.

monitoring sCreens

Continually pressing the scroll button or next button and 

the increment/decrement button allow more extensive 

monitoring. The screens are shown below. 

           

METER 1 DEMAND

 0.00 kW

main monitoring screen 

 

METER 1 DEMAND  

                0.00kW

meter 1 demand screen. 

Displays Current Demand, units will vary 

based on type of meter selected.

METER 1 COUNT

                0

meter 1 Count screen. 

Displays Current Consumption, units will 

vary based on type of meter selected

CONSUMPTION 1

        0.00 kWh

meter 1 Consumption screen. 

Displays Current pulse count, units will 

vary based on type of meter selected.

METER 2 DEMAND 

                0.00kW

meter 2 demand screen. 

Displays Current Demand, units will vary 

based on type of meter selected.

METER 2 COUNT

                0

meter 2 Count screen. 

Displays Current Consumption, units will 

vary based on type of meter selected

CONSUMPTION 2  

                0.00  kWh

meter 2 Consumption screen. 

Displays Current pulse count, units will 

vary based on type of meter selected.

1.

2.

3.

4.

5.

6.

Summary of Contents for SE1000

Page 1: ...3 Operation 5 Checkout Troubleshooting 6 LED Description 7 Communicating Controls Description The SE1000 is a microprocessor based pulse monitor ing interface designed to monitor up to four pulse inp...

Page 2: ...K y Z K y Z Wiring The SE1000 uses terminal designations for wiring See diagram below Powering the sE1000 The SE1000 is powered from 24 VAC 20 If wiring for communications dedicated power must be use...

Page 3: ...nstant Screen Enter the value for the constant for meter input 1 this value is provided from utility company This screen does not show if NO was selected in step 4 METER 1 CU FT P 5 00 Meter 1 Cubic F...

Page 4: ...the constant for meter input 3 this value is provided from utility company This screen does not show if NO was selected in step 18 14 15 16 17 18 19 20 21 22 METER 3 CU FT P 5 00 Meter 3 Cubic Feet Pe...

Page 5: ...formula Pulses KW 3600 multiplier Second In general the SE1000 calculates electric meter con sumption and demand as follows R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsb...

Page 6: ...SE1000 is not retrieving a pulse signal Verify the pulse signal is being generated at the meter or CT and check the input wiring Troubleshooting No Display Check for 24 VAC on terminals R and C Incor...