background image

In the following picture, both Type A and C are shown. 

Three pulses are shown, labeled 1, 2, and 3. Notice 

how the Type A output closes and opens for each pulse, 

where the Type C output simply changes state.

If you have a Type C device (3 terminals KYZ), you will 

need to double the multiplier. The SE1000 only counts 

the contact closures for the K and Z terminals. Doubling 

the multiplier will correct this problem.

Programming the meter Constants:

CT Value:  

The value of the CT wired to the meter. 

This value is usually provided on the CT or on the util-

ity output meter. This value is only used for and electric 

meter.
P/REV:   

The Pulses per revolution for the meter. 

This value is usually provided from the utility company.  
CONSTANT:   The value of the constant for the meter 

is usually provided from the utility company and many 

times is located on the electric or gas bill.  
CU FT/P:  

The value for Cubic Feet per pulse. This 

only applies to Water, GAS and BTU, and is usually 

found on the utility meter itself. 
MULT:    

The multiplier for the meter can be used 

to scale the meter output or correct for KYZ meter. The 

multiplier is used to convert the pulses to engineering 

unit data. For example, if your meter provides one pulse 

per 0.01KWH, then a constant of 0.01 is required.

muLtiPLier:

Each model of power meter is different and has a differ-

ent multiplier. For example, if the meter is a Type A and 

reports 1/10 kWh per pulse, set the input multiplier to 

0.1. If the meter is a Type C and reports 1/10 kWh per 

pulse, set the input multiplier to 0.2.
You must obtain the correct pulse multiplier from the 

meter manufacturer prior to configuring the SE1000.
Some power meters have an option to configure the 

multiplier. Options often include 1, 0.1, 0.01, kWh per 

pulse. The best method to configure the pulse is to 

select the smallest multiplier available, considering the 

maximum load and pulse rate. To calculate the pulse 

rate, use the following formula: 
Pulses = KW*3600*multiplier
Second 
In general, the SE1000 calculates electric meter con-

sumption and demand as follows: 

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

5

SET ACCESS CODE:  

                248

access Code screen. 

Enter an access code (0 to 255) that will 

be used to enter the programming mode. 

The default is 248.

Meter 1 Demand

                0.00  kW

main monitoring screen. 

 

Operation                              

meter inPuts

There are four meter inputs available. Each one is setup 

for a dry contact and cannot be changed. Each input 

(Meter 1, Meter 2, Meter 3 & Meter 4) can be configured 

to accept signals representing electrical, BTU, water or 

gas usage. The required parameters will be provided 

by either the utility company involved or on the current 

transducer (CT) used to generate the pulse signal.

meter tyPes

The SE1000 supports various meter types. Selecting a 

meter type changes the default values as they are used 

to calculate meter consumption and demand for that par-

ticular meter. For each of the four SE1000 meter inputs, 

there are five selectable options: 

 

ELEC 1 PH: Electric single phase meter.

 

ELEC 3 PH: Electric three phase meter.

 

GAS: Gas meter.

 

WATER: Water meter

 

BTU: BTU meter

Utility pulse meters can be one of two different types, 

depending on whether they count the leading and trail-

ing edges of the pulse or only the leading edge of the 

pulse as a single count. A pulse output can be either a 

mechanical relay or solid state device. The pulse output 

corresponds to a unit/time of a monitored quantity. The 

amount of time between states of a pulse output corre-

sponds to the meter demand and the number of pulses 

is proportional to the meter’s consumption. 
Below is a diagram depicting two types of utility meter 

pulse outputs. Meter Type A counts only the leading 

edge as a single pulse and the trailing edge is ignored. 

Meter Type C is known as a true KYZ meter and counts 

both the leading and trailing edges as a pulse, effectively 

doubling the number of pulses as seen by Meter Type 

A. The SE1000 measures Type A output only; however, 

KYZ functionality can be mimicked by using a “Meter 

Multiplier” value of 2.

 

32.

33.

Summary of Contents for SE1000

Page 1: ...3 Operation 5 Checkout Troubleshooting 6 LED Description 7 Communicating Controls Description The SE1000 is a microprocessor based pulse monitor ing interface designed to monitor up to four pulse inp...

Page 2: ...K y Z K y Z Wiring The SE1000 uses terminal designations for wiring See diagram below Powering the sE1000 The SE1000 is powered from 24 VAC 20 If wiring for communications dedicated power must be use...

Page 3: ...nstant Screen Enter the value for the constant for meter input 1 this value is provided from utility company This screen does not show if NO was selected in step 4 METER 1 CU FT P 5 00 Meter 1 Cubic F...

Page 4: ...the constant for meter input 3 this value is provided from utility company This screen does not show if NO was selected in step 18 14 15 16 17 18 19 20 21 22 METER 3 CU FT P 5 00 Meter 3 Cubic Feet Pe...

Page 5: ...formula Pulses KW 3600 multiplier Second In general the SE1000 calculates electric meter con sumption and demand as follows R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsb...

Page 6: ...SE1000 is not retrieving a pulse signal Verify the pulse signal is being generated at the meter or CT and check the input wiring Troubleshooting No Display Check for 24 VAC on terminals R and C Incor...

Page 7: ...Demand units will vary based on type of meter selected METER 4 COUNT 0 Meter 4 Count Screen Displays Current Consumption units will vary based on type of meter selected CONSUMPTION 0 00 kWh Meter 4 Co...

Reviews: