TCF PA Series Instruction, Operation And Maintenance Manual Download Page 13

 

 

TCF Termoventilatori Condizionatori Felsinea  Srl 

40057 Cadriano di Granarolo Emilia (Bologna), via Giuseppe di Vittorio 5 

www.tcf.it 

12 

 

 
If the tension is not correct, the following will occur: 

-

 

if  the  belt  is  slack,  it  will  wear  out  rapidly  and  the 
drive system will be inefficient 

-

 

if  the  belt  is  too  tight,  the  motor  and  fan  bearings 
will be damaged 

 
whenever  the  belts  are  tightened,  you  must  check  that  the 
drive belts are aligned using an ordinary RULER (fig. 27) 
 
FIG.27 

 

 
If the pulleys are of different thickness, you must check their 
equivalence as shown in fig. 28 to ensure correct installation. 
 

 

 
5.4.3.2

 

Replacement of driving belt 

 
To REPLACE THE DRIVING “V” BELT: 

-

 

loosen the drive and remove the worn-out belt 

-

 

check  the  condition  and  wear  of  the  pulleys  and 
replace them if necessary 

-

 

introduce the new belt without forcing; any forcing 
could  impair  the  transmission  and  shorten  its 
service life 

-

 

align the drive and tension the belt 

-

 

check the belt tension after about 10 working hours 

 
 
 

5.4.3.3

 

Drive with multiple-race pulleys 

 

-

 

in case of drives with several belts, the belts must be 
replaced  at  the  same  time.  This  means  that  there 
must not be belts presenting different states of wear 
in the same transmission system 

-

 

the number of belts must always match the number 
of races 

-

 

in  this  type  of  drive  system,  the  belt  slack  must  be 
on the same side, as shown in fig. 29, before they are 
tightened 

FIG. 29 

 

 
5.5

 

TROUBLESHOOTING 

 
The most common MALFUNCTIONS in air-conditioning units 
are: 

-

 

reduced flow rate 

-

 

increased flow rate (excluding TA units) 

-

 

reduction in heat exchanger efficiency 

-

 

abnormal noise 

 
5.5.1

 

Reduction in flow rate 

 
This is the result of an uncontrolled increase in resistance in 
the air moving circuit which alters the fan operating point. 
The most frequent causes are: 

-

 

excessively clogged filters 

-

 

formation  of  frost  or  ice  on  the  front  surface of  the 
prefilters in particularly damp and cold climates on 
units operating entirely with external air 

-

 

blockage  of  the  intake  grille(s)  (especially  external 
air intake) 

-

 

fully or partially closed control air locks 

-

 

activation of fire dampers 

-

 

deposits on cell blocks and heat exchangers 

-

 

inefficient fan motor unit drive 

 
5.5.2

 

Increased flow rate 

 
If  the  sum  of  the  resistances  in  the  aeraulic  circuits  is  less 
than  the  value  considered  at  the  design  stage,  the  most 
common causes are: 

-

 

incorrect setting of any mechanical flow controls or 
zone air locks 

-

 

non-replacement 

of 

filters 

after 

ordinary 

maintenance operations 

-

 

open or partially closed inspection doors 

 

5.5.3

 

Reduced heat exchanger efficiency

             

 

The most common causes are: 

-

 

clogging of finned pack 

-

 

formation of air bubbles inside the exchangers 

 

Summary of Contents for PA Series

Page 1: ...INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL AIR CONDITIONING UNITS SERIES T TS TA PA ...

Page 2: ...tion and protection 7 accessories 4 5 2 Fan 7 4 5 3 Transmission 8 4 6 FAN MOTOR UNITS 1 PHASES series TA PA TA 8 4 6 1 Electric motors 8 4 6 1 1 3 speed fans series TS and PA 8 4 6 1 2 Self regulating fans series TA 8 4 6 1 2 1 Selection of the airflow 9 4 6 1 2 2 Alarm on the pressure 9 4 7 Fan 9 4 8 NOISE LEVEL 9 5 MAINTENANCE 10 5 1 FOREWORD 10 5 2 FILTRATING SECTIONS 10 5 2 1 Reconditionable ...

Page 3: ...he various safety rules in force Integrity of all the system s component parts Application of the identification operation and safety notices On completion of the inspection the Chief Inspector applies the EC mark demonstrating product compliance with prevailing European Union machine directives 2 2 PACKING The air conditioning units are usually supplied as fully assembled monoblocks Only if the c...

Page 4: ...at the hydraulic connections are protected by the relevant caps as they were delivered by TCF If they are not plug them in order to protect them exchangers 3 3 POSITIONING 3 3 1 Dimensions of installation room The air conditioning unit installation room must be of sufficient size to permit easy inspection maintenance and component replacement Accordingly the following dimensions are recommended fi...

Page 5: ...to enhance the seal If the connection is made with rubber canvas joints make sure they are not tightened on assembly completion so as to prevent damage or the transmission of vibrations In order to ensure the tightness of the connections and the integrity of the unit the weight of the ducts must under no circumstances bear down on the unit The ducts must be supported by BRACKETS 4 2 CONNECTION OF ...

Page 6: ... may be provided fig 10 This configuration must be determined at the design stage and not during installation since on obvious reduction in efficiency will result if a heat exchanger sized for reverse current is used for equicurrent operation FIG 9 FIG 10 The diagram fig 15 shows the standard installation of a water type heat exchanger 4 3 DRAINAGE AND SIPHONING Before positioning the air conditio...

Page 7: ... motors Before starting up the unit inspect the motor CONTROL BOARD and check that the motor protection devices are sized for the maximum amperage corresponding to the rated value on the plate The TERMISTORS if present must not be connected to the power supply line of the electric motors since otherwise they would be damaged irreparably operating voltage 1V Check that the MAINS SUPPLY VOLTAGE is s...

Page 8: ...DAHLANDER commutable winding fig 18 offer the advantage of generating greater power than motors of the same size but with separate windings 4 5 1 4 Permitted start up time Because of the temperature increase the start up time of a motor may not exceed the value shown in table 1 The data refer to start ups at exercise temperature whereas for cold start ups such timings may be doubled 4 5 1 5 Recomm...

Page 9: ...be connected to the power supply line of the electric motors since otherwise they would be damaged irreparably Check that the MAINS SUPPLY VOLTAGE is suited to that of the motors as indicated on the relevant plates 4 6 1 1 3 speed fans series TS and PA The scheme on fig 21 shows the code colour of the terminal plate installed on the fans used for the TS and PA series FIG 21 WHITE COMMON RED LOW SP...

Page 10: ...he initial operating point of the system i e with clean filters To elaborate the built in alarm you nee to memorize this pressure with the microprocessor Memorizing procedure see attachment 2 page 18 ATTENTION The alarm in pressure is fixed only for ONE selected air volume Changing this air volume modifies the pre set alarm Paref is no longer correct and has to be re initialized b how to fix the i...

Page 11: ...aphragm as long as possible the condition of the prefilters must be carefully monitored Moreover TCF recommends to check the state of the gaskets of the frame and the springs every week to prevent air from by passing the bag without being filtered 5 2 2 1 Replacement load loss chart TABLE 2 Pressure drop to substitute the filters 5 3 HEAT EXCHANGERS 5 3 1 Water heat exchangers In order to maintain...

Page 12: ...bject to the environmental conditions and the maximum temperature range during operation TABLE 3 Lubrication of fan support bearings 5 4 2 Motor In order to maintain the motor in perfect working order TCF recommends the FOLLOWING MONTHLY CHECKS Cleanliness remove any deposits Absence of abnormal noise due to deterioration of the bearings Powerful motors fitted with grease nipples require periodic ...

Page 13: ...umber of belts must always match the number of races in this type of drive system the belt slack must be on the same side as shown in fig 29 before they are tightened FIG 29 5 5 TROUBLESHOOTING The most common MALFUNCTIONS in air conditioning units are reduced flow rate increased flow rate excluding TA units reduction in heat exchanger efficiency abnormal noise 5 5 1 Reduction in flow rate This is...

Page 14: ...danger connected with moving parts and warning him to disconnect the system power before opening the inspection doors fig 30 FIG 30 6 3 PRACTICAL ACCIDENT PREVENTION TIPS Open the inspection doors only when the fan is at a standstill Before carrying out maintenance work on the fan motor unit make sure that the motor cannot be restarted by accident Before operating on the motor make sure that it ha...

Page 15: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 14 8 ATTACHMENT 1 ...

Page 16: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 15 ...

Page 17: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 16 9 ATTACHMENT 2 ...

Page 18: ... control box In order to prevent all interferences we recommend to separate the cable of all the external sources of disturbance Use one of the cables of the following list or equivalent 2 Connecting cables between the power box and the control box UTP cable category 5 8 threads Maximum length 100 m RJ45 connectors no particular specification External contacts K 1 and K 2 Contacts free from potent...

Page 19: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 18 ...

Reviews: