Solution
:
Check battery voltage; Check battery capacity; Check battery LVD setting.
Phenomenon 2
:
No output at inverter mode, No alarm, Burn smell.
Reason
:
DC input reverse polarity.
Solution
:
Replace DC fuses.
9.3.2 No output during operation
Phenomenon 1
:
No output at inverter mode upon load switch on, fault and power saving mode
lights illuminate.
Reason
:
Battery low voltage.
Solution
:
Check battery voltage; Check battery capacity; Check battery LVD setting.
Phenomenon 2
:
No output, long beep, fault and inverter lights illuminate.
Reason
:
Output shortcut .
Solution
:
Remove output shortcut.
Phenomenon 3
:
No output, fault and charging lights illuminate.
Reason
:
High DC voltage.
Solution
:
Check DC voltage.
Phenomenon 4
:
No output, fault and overload lights illuminate.
Reason
:
Overload shutdown.
Solution
:
Reducing load and switch on again.
Phenomenon 5
:
No output,fault and overtemp lights illuminate.
Reason
:
Over temperature shutdown.
Solution
:
Check if there is good ventilation on installation site; check if fan was blocked.