recovered refrigerant and labelled for that refrig-
erant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with
pressure relief valve and associated shut-off
valves in good working order. Empty recovery
cylinders are evacuated and, if possible, cooled
before recovery occurs.
- The recovery equipment shall be in good work-
ing order with a set of instructions concerning
the equipment that is at hand and shall be
suitable for the recovery of flammable refriger-
ants. In addition, a set of calibrated weighing
scales shall be available and in good working
order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Be-
fore using the recovery machine, check that it is
in satisfactory working order, has been properly
maintained and that any associated electrical
components are sealed to prevent ignition in
the event of a refrigerant release. Consult man-
ufacturer if in doubt.
- The recovered refrigerant shall be returned to
the refrigerant supplier in the correct recovery
cylinder, and the relevant Waste Transfer Note
arranged. Do not mix refrigerants in recovery
units and especially not in cylinders. If compres-
sors or compressor oils are to be removed,
ensure that they have been evacuated to an
acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
The evacuation process shall be carried out pri-
or to returning the compressor to the suppliers.
Only electric heating to the compressor body
shall be employed to accelerate this process.
When oil is drained from a system, it shall be
carried out safely.
COMPETENCE OF SERVICE
PERSONNEL
GENERAL
- Special training additional to usual refrigerat-
ing equipment repair procedures is required
when equipment with flammable refrigerants is
affected.
- In many countries, this training is carried out by
national training organisations that are accred-
ited to teach the relevant national competency
standards that may be set in legislation.
- The achieved competence should be docu-
mented by a certificate.
TRAINING
- The training should include the substance of
the following:
- Information about the explosion potential of
flammable refrigerants to show that flammables
may be dangerous when handled without care.
- Information about potential ignition sources,
especially those that are not obvious, such
as lighters, light switches, vacuum cleaners,
electric heaters.
- Information about the different safety concepts:
- Unventilated – (see Clause GG.2) Safety of the
appliance does not depend on ventilation of
- the housing. Switching off the appliance or
opening of the housing has no significant effect
on the safety. Nevertheless, it is possible that
leaking refrigerant may accumulate inside the
enclosure and flammable atmosphere will be
released when the enclosure is opened.
- Ventilated enclosure – (see Clause GG.4) Safe-
ty of the appliance depends on ventilation of
- the housing. Switching off the appliance or
opening of the enclosure has a significant effect
- on the safety. Care should be taken to ensure a
sufficient ventilation before.
- Ventilated room – (see Clause GG.5) Safety of
the appliance depends on the ventilation of
- the room. Switching off the appliance or open-
ing of the housing has no significant effect on
- the safety. The ventilation of the room shall not
be switched off during repair procedures.
- Information about the concept of sealed compo-
nents and sealed enclosures according to IEC
60079-15:2010.
- Information about the correct working proce-
dures:
COMMISSIONING
- Ensure that the floor area is sufficient for the
refrigerant charge or that the ventilation duct is
assembled in a correct manner.
- Connect the pipes and carry out a leak test
before charging with refrigerant.
- Check safety equipment before putting into
service.
MAINTENANCE
- Portable equipment shall be repaired outside or
in a workshop specially equipped for servicing
units with flammable refrigerants.
Summary of Contents for ALPATEC DH101
Page 2: ......
Page 99: ...DH101 DH201 TAURUS ALPATEC 4 2 R290 45 g R290 DH101 85 g R290 DH201 R290...
Page 100: ...8 20 cm 20 cm...
Page 101: ...3T 4T Series 2A 250V AC T L 16 30 mA...
Page 103: ...DH 201 2 2 1 24 2 0 2 1 24 DH 201 A3 on off 3 15 pH 2...
Page 104: ...2014 35 E 2014 30 E 2011 65 2009 125 R290...
Page 105: ...CO2...
Page 106: ...LFL 25 OFN...
Page 107: ...OFN OFN OFN OFN a b c d e f g h 80 i j k...
Page 108: ...GG 2 GG 4...
Page 109: ...GG 5 IEC 60079 15 2010 5...
Page 110: ...5 5...
Page 111: ...DH101 DH201 TAURUS ALPATEC 4 2 R290 45 R290 DH101 85 R290 DH201 R290...
Page 112: ...8 20...
Page 113: ...20 3T 4T 2A 250V AC T L 16 30 H...
Page 115: ...95 HI DH 201 A7 15 DH 201 Timer A2 A2 1 24 A2 0 A2 1 24 DH 201 A3 on off 15 pH...
Page 116: ...2 WEEE 2014 35 EU 2014 30 EU 2011 65 EU 2009 125 EC R290...
Page 117: ...CO 2...
Page 118: ...LFL 25 OFN...
Page 119: ...OFN OFN OFN OFN a b c d e f g h 80 i j k...
Page 120: ...GG 2 GG 4...
Page 121: ...GG 5 IEC 60079 15 2010 5...
Page 122: ...5 5...
Page 123: ......
Page 135: ...DH101 DH201 TAURUS ALPATEC 4 m2 R290 45 g R290 DH101 85 g R290 DH201 R290...
Page 136: ...8 XX cm...
Page 137: ...XX cm 3T 4T Series 2A 250V AC T L 16 30 mA...
Page 139: ...A7 15 DH 201 2 A2 A2 1 24 A2 0 A2 1 24 DH 201 A3 N OFF 3 15 pH...
Page 140: ...2 2014 35 UE 2014 30 UE 2011 65 U 2009 125 CE R290...
Page 141: ...CO2...
Page 142: ...LFL 25 OFN...
Page 143: ...OFN OFN 0 OFN OFN a b c d e f g h 80 i j...
Page 144: ...k...
Page 145: ...GG 2 GG 4 GG 5 IEC 60079 15 2010 5...
Page 146: ...5 5...
Page 147: ......
Page 148: ...5 5 5...
Page 149: ...2 GG 4 GG 5 GG 0102 51 97006 CEI...
Page 150: ...LFL 52 NFO NFO NFO NFO NFO a b c d e f g 08 h i j k...
Page 151: ...EU 03 4102 EU 53 4102 EC 521 9002 UE 56 1102 092R...
Page 152: ...2A 42 1 0 2A 2A 42 1 102 HD 3A on off 3 51 2 EEEW...
Page 154: ...8 02 02 3T 4T Series 2A 250V AC T L 61 03...
Page 155: ...DH101 DH201 TAURUS ALPATEC 2 4 092R 092R 092R 54 101HD 092R 092R 58 102HD...
Page 160: ...Avda Barcelona s n E 25790 Oliana Spain Pub 21 marzo 2019...