![Taurus ALPATEC DH101 Manual Download Page 23](http://html1.mh-extra.com/html/taurus/alpatec-dh101/alpatec-dh101_manual_3742399023.webp)
ders. The system shall be “flushed” with OFN to
render the unit safe. This process may need to
be repeated several times. Compressed air or
oxygen shall not be used for this task. Flushing
shall be achieved by breaking the vacuum in
the system with OFN and continuing to fill until
the working pressure is achieved, then venting
to atmosphere, and finally pulling down to a
vacuum. This process shall be repeated until
no refrigerant is within the system. When the
final OFN charge is used, the system shall be
vented down to atmospheric pressure to enable
work to take place. This operation is absolutely
vital if brazing operations on the pipework are
to take place.
- Ensure that the outlet for the vacuum pump is
not close to any ignition sources and there is
ventilation available.
CHARGING PROCEDURES
- In addition to conventional charging proce-
dures, the following requirements shall be
followed.
-Ensure that contamination of different refrig-
erants does not occur when using charging
equipment. Hoses or lines shall be as short as
possible to minimise the amount of refrigerant
contained in them.
-Cylinders shall be kept upright.
-Ensure that the refrigeration system is earthed
prior to charging the system with refrigerant.
-Label the system when charging is complete (if
not already).
-Extreme care shall be taken not to overfill the
refrigeration system.
- Prior to recharging the system, it shall be
pressure tested with OFN. The system shall be
leak tested on completion of charging but prior
to commissioning. A follow up leak test shall be
carried out prior to leaving the site.
DECOMMISSIONING
- Before carrying out this procedure, it is essen-
tial that the technician is completely familiar
with the equipment and all its detail. It is rec-
ommended good practice that all refrigerants
are recovered safely. Prior to the task being
carried out, an oil and refrigerant sample shall
be taken in case analysis is required prior to
re-use of reclaimed refrigerant. It is essential
that electrical power is available before the task
is commenced.
a) Become familiar with the equipment and its
operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
mechanical handling equipment is available, if
required, for handling refrigerant cylinders; all
personal protective equipment is available and
being used correctly; the recovery process is
supervised at all times by a competent person;
recovery equipment and cylinders conform to
the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold
so that refrigerant can be removed from vari-
ous parts of the system.
f) Make sure that cylinder is situated on the
scales before recovery takes place.
g) Start the recovery machine and operate in
accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 %
volume liquid charge).
i) Do not exceed the maximum working pressure
of the cylinder, even temporarily.
j) When the cylinders have been filled correctly
and the process completed, make sure that
the cylinders and the equipment are removed
from site promptly and all isolation valves on
the equipment are closed off.
k) Recovered refrigerant shall not be charged
into another refrigeration system unless it has
been cleaned and checked.
LABELLING
- Equipment shall be labelled stating that it has
been de-commissioned and emptied of refriger-
ant. The label shall be dated and signed.
- Ensure that there are labels on the equipment
stating the equipment contains flammable
refrigerant.
RECOVERY
- When removing refrigerant from a system,
either for servicing or decommissioning, it is
recommended good practice that all refrigerants
are removed safely. When transferring refriger-
ant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for
holding the total system charge are available.
All cylinders to be used are designated for the
Summary of Contents for ALPATEC DH101
Page 2: ......
Page 99: ...DH101 DH201 TAURUS ALPATEC 4 2 R290 45 g R290 DH101 85 g R290 DH201 R290...
Page 100: ...8 20 cm 20 cm...
Page 101: ...3T 4T Series 2A 250V AC T L 16 30 mA...
Page 103: ...DH 201 2 2 1 24 2 0 2 1 24 DH 201 A3 on off 3 15 pH 2...
Page 104: ...2014 35 E 2014 30 E 2011 65 2009 125 R290...
Page 105: ...CO2...
Page 106: ...LFL 25 OFN...
Page 107: ...OFN OFN OFN OFN a b c d e f g h 80 i j k...
Page 108: ...GG 2 GG 4...
Page 109: ...GG 5 IEC 60079 15 2010 5...
Page 110: ...5 5...
Page 111: ...DH101 DH201 TAURUS ALPATEC 4 2 R290 45 R290 DH101 85 R290 DH201 R290...
Page 112: ...8 20...
Page 113: ...20 3T 4T 2A 250V AC T L 16 30 H...
Page 115: ...95 HI DH 201 A7 15 DH 201 Timer A2 A2 1 24 A2 0 A2 1 24 DH 201 A3 on off 15 pH...
Page 116: ...2 WEEE 2014 35 EU 2014 30 EU 2011 65 EU 2009 125 EC R290...
Page 117: ...CO 2...
Page 118: ...LFL 25 OFN...
Page 119: ...OFN OFN OFN OFN a b c d e f g h 80 i j k...
Page 120: ...GG 2 GG 4...
Page 121: ...GG 5 IEC 60079 15 2010 5...
Page 122: ...5 5...
Page 123: ......
Page 135: ...DH101 DH201 TAURUS ALPATEC 4 m2 R290 45 g R290 DH101 85 g R290 DH201 R290...
Page 136: ...8 XX cm...
Page 137: ...XX cm 3T 4T Series 2A 250V AC T L 16 30 mA...
Page 139: ...A7 15 DH 201 2 A2 A2 1 24 A2 0 A2 1 24 DH 201 A3 N OFF 3 15 pH...
Page 140: ...2 2014 35 UE 2014 30 UE 2011 65 U 2009 125 CE R290...
Page 141: ...CO2...
Page 142: ...LFL 25 OFN...
Page 143: ...OFN OFN 0 OFN OFN a b c d e f g h 80 i j...
Page 144: ...k...
Page 145: ...GG 2 GG 4 GG 5 IEC 60079 15 2010 5...
Page 146: ...5 5...
Page 147: ......
Page 148: ...5 5 5...
Page 149: ...2 GG 4 GG 5 GG 0102 51 97006 CEI...
Page 150: ...LFL 52 NFO NFO NFO NFO NFO a b c d e f g 08 h i j k...
Page 151: ...EU 03 4102 EU 53 4102 EC 521 9002 UE 56 1102 092R...
Page 152: ...2A 42 1 0 2A 2A 42 1 102 HD 3A on off 3 51 2 EEEW...
Page 154: ...8 02 02 3T 4T Series 2A 250V AC T L 61 03...
Page 155: ...DH101 DH201 TAURUS ALPATEC 2 4 092R 092R 092R 54 101HD 092R 092R 58 102HD...
Page 160: ...Avda Barcelona s n E 25790 Oliana Spain Pub 21 marzo 2019...