Automatic operation

is activated by pressing the

ON/OFF

button (3) The air damper is

fully opened. In 2hrs the fireplace ought to heat itself and reach the preset temperature stabilized by
air damper movements. From that moment the temperature fall to the preset temperature by more
than 10 C (the

parameter) existing for 30mins is treated as a burnout of

the fireplace. The control unit ends the operation cycle setting the air damper to the rest position.
Pressing the

ON/OFF

button (3) once more starts another operation cycle.

The green status diode (1) lights during the fireplace operation and goes out after recognizing the
burnout state of the fireplace.

operation icon in waiting for the start of a new cycle (that is, before its start or after

its end

operation icon during the cycle

It

s a stable state, that is, in order to change it you need to press the CHOOSE button.

It

s a stable state, that is, in order to change it you need to press the CHOOSE button.

AUTO

<23> FPLACE OFF Temp.

AUTO

AUTO

o

i

Operation screen of the whole system

10

Screen of pumps operation for the basic operation configuration

Screen of the operation modes

enables changing the operation mode of the fireplace

and WAW container.
Possible operation modes of the fireplace are as follows (described above):

Possible operation modes of the WAW container are as follows (described above):

MAN/OFF/AUTO/ON

SUMMER/ON

Icon of the

current mode

Selection of the mode

from the list (+/-)

Temperature of the
water jacket (T3)

KSL pump
runs

KSL temperature
T2

Relay CONTROL

Operation mode
of the CH pump

BUF pump
runs

BUF temperature
T1

CH pump doesn't
run

24

21

PARAMETERS LEVEL 3

PARAMETERS CAN BE CHANGED AT THE UNLOCKED PASSWORD

No

NAME

RANGE

DEFAULT

SETTING

FUNCTION

Buffer limit temperature (T1) at which the alarm generates.

75...95

o

C

85

o

C

Fireplace temperature (T3) at which the alarm turns on.

5...25

o

C

10

o

C

Decreasing fireplace temperature in relation to preset temperature
at whose exceeding the countdown of 30mins begins up to the
switch-off of fireplace (stop condition at

)

FIREPLACE MODE=AUTO

BUF ALARM

Temp.

ALARM
Temp.

FPLACE OFF

Temp.

23

0...6

2

Switch-on of the

relay if

CONTROL

2

KSL temperature is higher than

ControlRelayTemp

3
4
5
6

BUF pump (P2) runs

CONTROL
Relay

1...2

2

1

2

ChokeV
Mode

Control type of the air damper

Dynamic control - servomotor of the

is active

only if the position change of the valve is needed.

air damper

Continuous control - servomotor of the air damper is always
active.

12

51

!

Parameter number (No.) is of auxiliary role - it helps to identify the name e.g. for different

language versions

63

Rundown
Time

-

BUF

0..30mins

1min

Rundown time of the BUF pump. Extending the run time of
the pump after ending the loading of the BUF

75...95

o

C

85

o

C

0

1

fireplace temp. higher than

ControlRelayTemp

Buffer temp. higher than

ControlRelayTemp

KSL pump (P1) runs
CH pump (P3) runs
ALARM is turned on (see

Alarm screens

)

16

Control-
RelayTemp

5..195

o

C

60

o

C

Limit temperature at which the CONTROL relay turns on.
(Depending on the <12> CONTROL Relay parameter.)

64

DeltaKSL

Minimal temperature difference between BUF and KSL
required for the KSL pump P1 to run.

0...20

o

C

5

o

C

26

KSL (solar collector) limit temperature (T2) at which
the alarm generates.

ALARM Temp.

KSL

80..200

o

C

175

o

C

P

ARAMETERS LEVEL 4

OFF/ON

OFF

Setting the value of

ON

causes the recall of all parameters to

their default pre-sets and restarts the control unit

RESET

FUNCTION

NAME

RANGE

DEFAULT

90

91

No

ProdNo.

0.....n

1

Number of the parameters set - dependent on fireplace producer

99

Service
Screen

OFF

OFF

The ON value causes diagnostics screen to be added
for servicing.

92

PASSWORD

0

9999

0000

0000

PASSWORD OFF

----

PASSWORD ON

PUMPS

MODE

Summary of Contents for RT-08G-BUF-SOLAR

Page 1: ...ion Housing protection class IP41 Fuse 6 3A 250V Number of outputs to control pumps 3 250W 230V 50Hz Number of nonvoltage outputs 1 Number of outputs to control the air damper drive 1 5V 500mA DC Numb...

Page 2: ...tainer from the solar collector KSL P1 The pump of the collector P1 runs if the temperature of the collector T2 exceeds the temperatureofthebuffer T1 bytheparametervalue 64 DeltaKSL The next function...

Page 3: ...p P1 2 4 2 5Summermode CH The collector pump P1 runs if the collector temperature T2 exceeds the buffer temperature T1 by thevalue Exceeding the maximum collector temperature parameter causes the KSLp...

Page 4: ...ver to the screen of the fireplace 12 CONTROL Relay 3 3 2 7 6 4 5 7 6 Fig 2 Control panel view Connection cable of the control may be replaced only by producer or his authorized service locations WARR...

Page 5: ...ce toohigh temp ofthebuffer toohigh temp ofthecollector Alarm screen ALARM the limittemperatureof thefireplace definedbythe parameter the limit temperature of the buffer defined by the parameter the l...

Page 6: ...ION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED PASSWORD OF PRODUCER S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER S PASSWORD IT SHOUDN T BE EXPOSED TO THE USER INSTEAD OF THAT...

Page 7: ...at which the alarm generates 75 95 o C 85 o C Fireplace temperature T3 at which the alarm turns on 5 25 o C 10 o C Decreasing fireplace temperature in relation to preset temperature at whose exceedin...

Page 8: ...3 4 5 8 00 End of the 1st time zone 72 0 00 23 4 5 14 00 73 0 00 23 4 5 17 30 74 0 00 23 4 5 20 00 75 0 00 23 4 5 22 30 76 ECO4 from 0 00 23 4 5 23 00 Start of the 4th time zone economic 77 ECO4 to 0...

Reviews: