7
Automatic operation
is activated by pressing the
“
ON/OFF
”
button (3) The air damper is
fully opened. In 2hrs the fireplace ought to heat itself and reach the preset temperature stabilized by
air damper movements. From that moment the temperature fall to the preset temperature by more
than 10 C (the
parameter) existing for 30mins is treated as a burnout of
the fireplace. The control unit ends the operation cycle setting the air damper to the rest position.
Pressing the
“
ON/OFF
”
button (3) once more starts another operation cycle.
The green status diode (1) lights during the fireplace operation and goes out after recognizing the
burnout state of the fireplace.
operation icon in waiting for the start of a new cycle (that is, before its start or after
its end
operation icon during the cycle
It
’
s a stable state, that is, in order to change it you need to press the CHOOSE button.
It
’
s a stable state, that is, in order to change it you need to press the CHOOSE button.
AUTO
<23> FPLACE OFF Temp.
AUTO
AUTO
o
i
Operation screen of the whole system
10
Screen of pumps operation for the basic operation configuration
Screen of the operation modes
enables changing the operation mode of the fireplace
and WAW container.
Possible operation modes of the fireplace are as follows (described above):
Possible operation modes of the WAW container are as follows (described above):
MAN/OFF/AUTO/ON
SUMMER/ON
Icon of the
current mode
Selection of the mode
from the list (+/-)
Temperature of the
water jacket (T3)
KSL pump
runs
KSL temperature
T2
Relay CONTROL
Operation mode
of the CH pump
BUF pump
runs
BUF temperature
T1
CH pump doesn't
run
24
21
PARAMETERS LEVEL 3
PARAMETERS CAN BE CHANGED AT THE UNLOCKED PASSWORD
No
NAME
RANGE
DEFAULT
SETTING
FUNCTION
Buffer limit temperature (T1) at which the alarm generates.
75...95
o
C
85
o
C
Fireplace temperature (T3) at which the alarm turns on.
5...25
o
C
10
o
C
Decreasing fireplace temperature in relation to preset temperature
at whose exceeding the countdown of 30mins begins up to the
switch-off of fireplace (stop condition at
)
FIREPLACE MODE=AUTO
BUF ALARM
Temp.
ALARM
Temp.
FPLACE OFF
Temp.
23
0...6
2
Switch-on of the
relay if
CONTROL
2
KSL temperature is higher than
“
ControlRelayTemp
”
3
4
5
6
BUF pump (P2) runs
CONTROL
Relay
1...2
2
1
2
ChokeV
Mode
Control type of the air damper
Dynamic control - servomotor of the
is active
only if the position change of the valve is needed.
air damper
Continuous control - servomotor of the air damper is always
active.
12
51
!
Parameter number (No.) is of auxiliary role - it helps to identify the name e.g. for different
language versions
63
Rundown
Time
-
BUF
0..30mins
1min
Rundown time of the BUF pump. Extending the run time of
the pump after ending the loading of the BUF
75...95
o
C
85
o
C
0
1
fireplace temp. higher than
“
ControlRelayTemp
”
Buffer temp. higher than
“
ControlRelayTemp
”
KSL pump (P1) runs
CH pump (P3) runs
ALARM is turned on (see
“
Alarm screens
”
)
16
Control-
RelayTemp
5..195
o
C
60
o
C
Limit temperature at which the CONTROL relay turns on.
(Depending on the <12> CONTROL Relay parameter.)
64
DeltaKSL
Minimal temperature difference between BUF and KSL
required for the KSL pump P1 to run.
0...20
o
C
5
o
C
26
KSL (solar collector) limit temperature (T2) at which
the alarm generates.
ALARM Temp.
KSL
80..200
o
C
175
o
C
P
ARAMETERS LEVEL 4
OFF/ON
OFF
Setting the value of
“
ON
”
causes the recall of all parameters to
their default pre-sets and restarts the control unit
RESET
FUNCTION
NAME
RANGE
DEFAULT
90
91
No
ProdNo.
0.....n
1
Number of the parameters set - dependent on fireplace producer
99
Service
Screen
OFF
OFF
The ON value causes diagnostics screen to be added
for servicing.
92
PASSWORD
0
…
9999
0000
„
0000
”
PASSWORD OFF
----
”
PASSWORD ON
PUMPS
MODE